ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls
prevent loss of refrigerant charge and a low suction tem- perature thermistor for freeze sensing. Upon a continuous
Control Tables for Optional Versatec Microprocessor
Logic Board DIP Switch Settings
Switch | OFF | ON |
|
|
|
SW1 - 1 | Test - Selected timings sped up to facilitate troubleshooting | Normal - Standard timings |
|
|
|
SW1 - 2 | Loop - Closed loop freeze sensing setting (15°F) | Well - Open loop freeze sensing setting (30°F) |
|
|
|
SW1 - 3 | Commercial - Enables NS features when TA32U02 thermostat is used | Normal - Standard thermostat operation |
|
|
|
SW1 - 4 | IO Display* - Enables Input/Output display on external LED board | Normal* - Unit status display |
|
|
|
SW1 - 5 | Configures board for | Configures board for |
|
|
|
Normal Control Timing
Blower off delay | 30 seconds |
|
|
Compressor on delay | 10 seconds |
|
|
Short cycle delay | 5 minutes |
|
|
Miniumum compressor on time | 2 minutes (except for fault condition) |
|
|
High pressure fault recognition delay | Less than 1 second |
|
|
low pressure fault recognition delay | 30 seconds |
|
|
Freeze sensing fault recognition delay | 30 seconds |
|
|
Condensate overflow fault recognition delay | 30 seconds |
|
|
Low pressure fault bypass delay | 2 minutes |
|
|
Freeze sensing fault bypass delay | 2 minutes |
|
|
Power on delay | 5 minutes |
|
|
Operational Logic
Mode | Inputs | Fan | Comp | RV |
|
|
|
|
|
Htg | Y | ON | ON | OFF |
|
|
|
|
|
Clg | Y,O | ON | ON | ON |
|
|
|
|
|
Fan | G | ON | OFF | OFF |
|
|
|
|
|
Test Control Timing
Blower off delay | 5 seconds |
|
|
Compressor on delay | 2 seconds |
|
|
Short cycle delay | 15 seconds |
|
|
Miniumum compressor on time | 5 seconds (except for fault condition) |
|
|
High pressure fault recognition delay | Less than 1 second |
|
|
low pressure fault recognition delay | 30 seconds |
|
|
Freeze sensing fault recognition delay | 30 seconds |
|
|
Condensate overflow fault recognition delay | 30 seconds |
|
|
Low pressure fault bypass delay | 0 seconds |
|
|
Freeze sensing fault bypass delay | 0 seconds |
|
|
Power on delay | 15 seconds |
|
|
Fault off time | 5 minutes |
|
|
Diagnostic Modes
| LED | Current Fault Status | Inputs | Outputs |
| SW1 - #4 On, SW2 On | SW1 - #4 Off, SW2 Off | SW1 - #4 Off, SW2 On | |
|
| |||
|
|
|
|
|
Drain |
| Drain pan overflow | Y | Compressor |
|
|
|
|
|
Water Flow |
| FS thermistor (loop <15°F, well <30°F) | G | FAN |
|
|
|
|
|
High Press |
| High pressure >600 PSI | O | O |
|
|
|
|
|
Low Press |
| Low pressure <40 PSI | ES | ES |
|
|
|
|
|
Air Flow |
| Not used | NS | NS |
|
|
|
|
|
Status |
| Not used | LS | LS |
|
|
|
|
|
DHW Limit |
| Not used | Not used | Not used |
|
|
|
|
|
HWD |
| SW2 in the On position | Off position | On position |
|
|
|
|
|
27