| | | | | BACnet | | Point Description |
| Object Identifier | | Property | Full Reference |
Object Type | | Type Enumeration | Instance | Name | | Enumeration | | | |
Analog Value | | 2 | 1 | Present_Value | | 85 | WFI##########.Occupied Cool.Present_Value | Occupied Cooling Setpoint Input (Read/Write) | |
| | | | | | | | Standby Cooling Setpoint Input (Read/Write) | |
Analog Value | | 2 | 2 | Present_Value | | 85 | WFI##########.Unoccupied Cool.Present_Value | Unoccupied Cooling Setpoint Input (Read/Write) | |
Analog Value | | 2 | 3 | Present_Value | | 85 | WFI##########.Occupied Heat.Present_Value | Occupied Heating Setpoint Input (Read/Write) | |
| | | | | | | | Standby Heating Setpoint Input (Read/Write) | |
Analog Value | | 2 | 4 | Present_Value | | 85 | WFI##########.Unoccupied Heat.Present_Value | Unoccupied Heating Setpoint Input (Read/Write) | |
| | | | | | | | Minimum Cooling Setpoint Input (Read/Write) | |
| | | | | | | | Maximum Heating Setpoint Input (Read/Write) | |
Analog Input | | 0 | 1 | Present_Value | | 85 | WFI##########.Space Temp.Present_Value | Space or Zone Temperature Value (Read Only) | |
Analog Input | | 0 | 2 | Present_Value | | 85 | WFI##########.Discharge Air Temp.Present_Value | Discharge Air Temp Field Supplied Only (Read Only) | |
Analog Input | | 0 | 3 | Present_Value | | 85 | WFI##########.Effective Clg Setpt.Present_Value | Effective Cooling Setpoint Value (Read Only) | |
Analog Output | | 1 | 4 | Present_Value | | 85 | WFI##########.Space temp Ovrd.Present_Value | Space or Zone Temperature Value Override(Write) | |
Analog Input | | 0 | 4 | Present_Value | | 85 | WFI##########.Effective Htg Setpt.Present_Value | Effective Heating Setpoint Value (Read Only) | |
Analog Value | | 2 | 9 | Present_Value | | 85 | WFI##########.Dehumidify Setpt.Present_Value | Dehumidification Setpoint (Read/Write) | |
Analog Value | | 2 | 10 | Present_Value | | 85 | WFI##########.Low Temp Limit Adj.Present_Value | Heating Freeze Protection Temperature Setpoint Value (Read/Write) | |
| | | | | | | | Heating Freeze Protection Temperature Setpoint Value (Read/Write) | |
| | | | | | | | 1st Stage Compressor Heating Output (Read Only) | |
| | | | | | | | 1st Stage Compressor Cooling Output (Read Only) | |
| | | | | | | | Fan Output (Read Only) | |
Multistate Input | | 13 | 2 | Present_Value | | 85 | WFI##########.Mode.Present_Value | Unit Mode of Operation (Read Only) | |
| | | | | | | | Unit Alarm mode (Read Only) | |
| | | | | | | | Heating/Cooling Prop Band Input (Read/Write) | |
Analog Value | | 2 | 6 | Present_Value | | 85 | WFI##########.Remote Setpt Span.Present_Value | Warm/Cool Adjust Span (Read/Write) | |
Analog Value | | 2 | 7 | Present_Value | | 85 | WFI##########.Remote Setpt Bias.Present_Value | Warm/Cool Adjust Offset Value (Read/Write) | |
Analog Value | | 2 | 8 | Present_Value | | 85 | WFI##########.Space Temp Offset.Present_Value | Space or Zone Temperature Sensor Calibration Input (Read/Write) | |
Analog Output | | 1 | 1 | Present_Value | | 85 | WFI##########.Space Setpoint.Present_Value | General Setpoint Input (Read/Write) | |
Analog Input | | 0 | 6 | Present_Value | | 85 | WFI##########.Water Coil Temp.Present_Value | Heating Freeze Sensing Temperature Value (Read Only) | |
Analog Input | | 0 | 7 | Present_Value | | 85 | WFI##########.Low Temp Limit.Present_Value | Heating Freeze Sensing Temperature Setpoint Value (Read Only) |
| | | | | | | | Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge |
| | | | | | | | Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing |
Analog Input | | 0 | 9 | Present_Value | | 85 | WFI##########.Alarms Enumerated.Present_Value | alarm, 8=Faulty Freeze Sensor alarm, |
| | | | | | | | 9=Loss of Charge] |
| | | | | | | | (Read Only) |
Analog Input | | 0 | 8 | Present_Value | | 85 | WFI##########.ECM Cmd Output.Present_Value | ECM PWM Control signal value (Read Only) | |
Analog Output | | 1 | 2 | Present_Value | | 85 | WFI##########.ECM Fan Ovrd.Present_Value | ECM PWM Control signal Override (Read/Write) | |
Analog Input | | 0 | 5 | Present_Value | | 85 | WFI##########.Space Humidity.Present_Value | Space Humidity value (Read Only) | |
Analog Output | | 1 | 3 | Present_Value | | 85 | WFI##########.AO2 Override.Present_Value | Spare PWM Output AO2 Command (Write) | |
Analog Input | | 0 | 10 | Present_Value | | 85 | WFI##########.AO2 Value.Present_Value | Spare PWM Output AO2 Value (Read Only) | |
Analog Value | | 2 | 5 | Present_Value | | 85 | WFI##########.Temporary Occ Time.Present_Value | Temporary Occupancy Time Period Input (Read/Write) | |
Multistate Input | | 13 | 1 | Present_Value | | 85 | WFI##########.Effective Occupancy.Present_Value | Effective Occupancy State (Read Only) | |
Multistate Output | | 14 | 1 | Present_Value | | 85 | WFI##########.Occupancy Command.Present_Value | Occupancy Override Command Input (Read/Write) | |
Multistate Output | | 14 | 6 | Present_Value | | 85 | WFI##########.Emergency Override.Present_Value | Emergency Override Input (Read/Write) | |
Binary Input | | 3 | 1 | Present_Value | | 85 | WFI##########.Fan Cmd Status.Present_Value | Fan Output Status (Read Only) | |
Binary Input | | 3 | 6 | Present_Value | | 85 | WFI##########.Accessory 2 Output.Present_Value | Accessory 2 Output Status (Read Only) | |
Binary Input | | 3 | 5 | Present_Value | | 85 | WFI##########.Accessory 1 Output.Present_Value | Accessory 1 Output Status (Read Only) | |
Binary Input | | 3 | 8 | Present_Value | | 85 | WFI##########.Alarm Status.Present_Value | Alarm Output Status (Read Only) | |
Multistate Output | | 14 | 7 | Present_Value | | 85 | WFI##########.Alarm Reset.Present_Value | Alarm Reset Input (Read/Write) | |
Multistate Output | | 14 | 2 | Present_Value | | 85 | WFI##########.Fan Command (G).Present_Value | Network equivelant of a thermostatic 'G' call. (Write) | |
Multistate Output | | 14 | 3 | Present_Value | | 85 | WFI##########.Compressor Cmd (Y1).Present_Value | Network equivelant of a thermostatic 'Y1' call. (Write) | |
Multistate Output | | 14 | 3 | Present_Value | | 85 | WFI##########.Compressor Cmd (Y2).Present_Value | Network equivelant of a thermostatic 'Y2' call. (Write) | |
Binary Input | | 3 | 4 | Present_Value | | 85 | WFI##########.Reversing Valve.Present_Value | Reversing Valve Output Status (Read Only) | |
| | | | | | | | Occupancy Supervisory Scheduler Command Input (Read/Write) | |
| | | | | | | | Compressor/Fan Proving Switch Status (Read Only) | |
Binary Input | | 3 | 7 | Present_Value | | 85 | WFI##########.Dirty Filter (BI-12).Present_Value | Dirty Filter Switch Status (Read Only) | |
Binary Input | | 3 | 3 | Present_Value | | 85 | WFI##########.Comp Hi Capacity Cmd.Present_Value | Compressor Hi Capacity Command Status (Read Only) | |
Multistate Output | | 14 | 8 | Present_Value | | 85 | WFI##########.Emergency Heat BO5.Present_Value | Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write) | |
Multistate Output | | 14 | 9 | Present_Value | | 85 | WFI##########.BO9.Present_Value | Command for output BO9(Read/Write) | |
Binary Input | | 3 | 9 | Present_Value | | 85 | WFI##########.BO5 Output.Present_Value | Value output for BO5 used for Emg Heat (Read Only) | |
Binary Input | | 3 | 10 | Present_Value | | 85 | WFI##########.BO9 Output.Present_Value | Value output for BO9 (Read Only) | |
Multistate Output | | 14 | 10 | Present_Value | | 85 | WFI##########.Dehum Cmd.Present_Value | Dehumidification command-like a Humidistat (Read/Write) | |