Envision Peripherals IM1609 10, IM1609 08 installation manual LonWorks Point Description

Page 37

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

LonWorks

 

 

LonWorks

 

 

Point Description

 

 

 

 

 

 

LonWorks Name

SNVT Type

SNVT Index

SCPT Reference

SCPT Index

UCPT Index

 

 

 

 

 

 

 

 

Occupied Cooling Setpoint Input (Read/Write)

 

 

 

 

 

 

 

Standby Cooling Setpoint Input (Read/Write)

 

nciSetpoints

SNVT_temp_setpt

106

SCPTsetPnts

60

 

Unoccupied Cooling Setpoint Input (Read/Write)

 

 

Occupied Heating Setpoint Input (Read/Write)

 

 

 

 

 

 

 

 

 

 

 

 

Standby Heating Setpoint Input (Read/Write)

 

 

 

 

 

 

 

Unoccupied Heating Setpoint Input (Read/Write)

 

nciMinClgSetpt

SNVT_temp_p

105

 

 

4

Minimum Cooling Setpoint Input (Read/Write)

 

nciMaxHtgSetpt

SNVT_temp_p

105

 

 

3

Maximum Heating Setpoint Input (Read/Write)

 

nvoSpaceTemp

SNVT_temp_p

105

 

 

 

Space or Zone Temperature Value (Read Only)

 

nvoDischAirTemp

SNVT_temp_p

105

 

 

 

Discharge Air Temp Field Supplied Only (Read Only)

 

nvoEffClgSetpt

SNVT_temp_p

105

 

 

 

Effective Cooling Setpoint Value (Read Only)

 

nviSpaceTemp

SNVT_temp_p

105

 

 

 

Space or Zone Temperature Value Override(Write)

 

nvoEffHtgSetpt

SNVT_temp_p

105

 

 

 

Effective Heating Setpoint Value (Read Only)

 

nciAux5LevP

SNVT_lev_percent

81

 

 

 

Dehumidification Setpoint (Read/Write)

 

nciAux1Temp

SNVT_temp_p

105

 

 

147

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

 

nciAux2Temp

SNVT_temp_p

105

 

 

148

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

 

 

 

 

 

 

 

1st Stage Compressor Heating Output (Read Only)

 

nvoUnitStatus

SNVT_hvac_type

112

 

 

 

1st Stage Compressor Cooling Output (Read Only)

 

 

 

 

Fan Output (Read Only)

 

 

 

 

 

 

 

Unit Mode of Operation (Read Only)

 

 

 

 

 

 

 

Unit Alarm mode (Read Only)

 

nciPropBand

SNVT_temp_diff_p

147

 

 

177

Heating/Cooling Prop Band Input (Read/Write)

 

nciRemoteSetptMin

SNVT_temp_diff_p

147

 

 

98

Warm/Cool Adjust Span (Read/Write)

 

nciRemoteSetptMax

SNVT_temp_diff_p

147

 

 

97

Warm/Cool Adjust Offset Value (Read/Write)

 

nciTempOffset

SNVT_temp_diff_p

147

 

 

11

Space or Zone Temperature Sensor Calibration Input (Read/Write)

 

nviSetpoint

SNVT_temp_p

105

 

 

 

General Setpoint Input (Read/Write)

 

nvoHtgFrzPro1Tmp

SNVT_temp_p

105

 

 

 

Heating Freeze Sensing Temperature Value (Read Only)

 

nvoHtgFrzSetpt

SNVT_temp_p

105

 

 

 

Heating Freeze Sensing Temperature Setpoint Value (Read Only)

 

 

 

 

 

 

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge

 

 

 

 

 

 

Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing

nvoAlarms

SNVT_lev_cont

21

 

 

 

alarm, 8=Faulty Freeze Sensor alarm,

 

 

 

 

 

 

9=Loss of Charge]

 

 

 

 

 

 

(Read Only)

nvoPWMOut

SNVT_volt

44

 

 

 

ECM PWM Control signal value (Read Only)

 

nvoECMOvrd

SNVT_volt

44

 

 

 

ECM PWM Control signal Override (Read/Write)

 

nvoHumidity

SNVT_volt

44

 

 

 

Space Humidity value (Read Only)

 

nviAO2

SNVT_lev_percent

81

 

 

 

Spare PWM Output AO2 Command (Write)

 

nvoAO2

SNVT_lev_percent

81

 

 

 

Spare PWM Output AO2 Value (Read Only)

 

nciBypassTime

SNVT_time_min

123

SCPTbypassTime

34

 

Temporary Occupancy Time Period Input (Read/Write)

 

nvoEffectOccup

SNVT_occupancy

109

 

 

 

Effective Occupancy State (Read Only)

 

nviOccManCmd

SNVT_occupancy

109

 

 

 

Occupancy Override Command Input (Read/Write)

 

nviEmergOverride

SNVT_hvac_emerg

103

 

 

 

Emergency Override Input (Read/Write)

 

nvoFanStatus

SNVT_lev_disc

22

 

 

 

Fan Output Status (Read Only)

 

nvoAccStatus

SNVT_lev_disc

22

 

 

 

Accessory 2 Output Status (Read Only)

 

nvoLP_WVStatus

SNVT_lev_disc

22

 

 

 

Accessory 1 Output Status (Read Only)

 

nvoAlarmStatus

SNVT_lev_disc

22

 

 

 

Alarm Output Status (Read Only)

 

nviAlarmReset

SNVT_lev_disc

22

 

 

 

Alarm Reset Input (Read/Write)

 

nviFanSpeedCmd.StateSNVT

_switch

95

 

 

 

Network equivelant of a thermostatic 'G' call. (Write)

 

nviComprEnable.State

SNVT_switch

95

 

 

 

Network equivelant of a thermostatic 'Y1' call. (Write)

 

nviComprEnable.State

SNVT_switch

95

 

 

 

Network equivelant of a thermostatic 'Y2' call. (Write)

 

nvoRV1Status

SNVT_lev_disc

22

 

 

 

Reversing Valve Output Status (Read Only)

 

nviOccSchedule

SNVT_tod_event

128

 

 

 

Occupancy Supervisory Scheduler Command Input (Read/Write)

 

nvoCompFanProv

SNVT_lev_disc

22

 

 

 

Compressor/Fan Proving Switch Status (Read Only)

 

nvoDirtyFilter

SNVT_lev_disc

22

 

 

 

Dirty Filter Switch Status (Read Only)

 

nvoComp2Status

SNVT_lev_disc

22

 

 

 

Compressor Hi Capacity Command Status (Read Only)

 

nviBO5

SNVT_lev_disc

22

 

 

 

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

 

nviBO9

SNVT_lev_disc

22

 

 

 

Command for output BO9(Read/Write)

 

nvoBO5

SNVT_lev_disc

22

 

 

 

Value output for BO5 used for Emg Heat (Read Only)

 

nvoBO9

SNVT_lev_disc

22

 

 

 

Value output for BO9 (Read Only)

 

nviDehumEna.State

SNVT_lev_disc

22

 

 

 

Dehumidification command-like a Humidistat (Read/Write)

 

36

Image 37
Contents Envision Console Installation Manual Page Table of Contents NC C Model NomenclatureSafety Considerations General Installation InformationRefrigerant Systems Moving and StorageNCW09-18 Dimensional Data Flat Top CabinetConfiguration Dimensional Data Slope Top CabinetNCS09-18 Slope TopNCE09-18 Dimensional Data Extended Slope Top CabinetExt. Slope Top Dimensional Data Right Return Controls Detail  Dimensional Data Right Return ChassisDimensional Data Left Return Controls Detail # Dimensional Data Left Return ChassisMark Unit Position Installation StepsPipe Locations Provide Water and Condensate Drain ConnectionsChassis Installation Provide Line Voltage WiringFinal Electrical Connection Final Water ConnectionTop view Side view Field Converting ConsoleCleaning and Flushing System Cleaning and FlushingGround Source Loop System Checkout Water Quality Open Loop Ground Water SystemsElectrical Connections Microprocessor Remote Thermostat WiringAuxiliary Heat Ratings GeneralFan Performance Data Unit Electrical Data208-230-265/60/1 Wiring SchematicControl Module CCM w/EH Electronic Thermostat 208-230-265/60/1LED Display Mode Table Versatec Control EH & Remote Wall Thermostat 208-230-265/60/1 Schematic aPSC FX10 EH 208-230-265/60/1Envision Console Controls Standard CCM Control FeaturesOptional Versatec Microprocessor Control Features Control Tables for Optional Versatec Microprocessor Logic Board DIP Switch SettingsOptional FX10 Control Standard Features Control Timing & Fault Recognition DelaysOptional FX10 Microprocessor and BAS Interface Zone SensorsSequence of Operation Control and Safety Feature DetailsCompressor Fixed On Delay Time Random Start DelayCompressor Minimum On Delay Compressor Short Cycle Delay TimeControl Accessories Inputs & Outputs ConfigurationFX10 User Interface MUI Physical Layout  Info Status Temps Outputs SettingsLogin Required N2 Open LonWorks Point Description LonWorksBACnet Point Description BACNetAnalog Input Type BACnet VariablesAnalog Output Type Analog Value TypeMultistate Output Type Multistate Input TypeUnit Startup Notes Hydronic Loop Controller for Boiler/Tower InstallationsEmergency Electric Resistance Heat Electrical DisconnectBefore Powering Unit, Check The Following Unit Startup Checklist / Unit Startup StepsStartup Steps Unit Operating Limits Unit Operating ParametersSingle Speed Models Startup/Troubleshooting Form Pressure Drop Replacement Procedures Preventive MaintenanceWater Coil Maintenance Other MaintenancePage Envision Series Console

IM1609 10, IM1609 08 specifications

Envision Peripherals has carved a niche in the realm of advanced display technology, and its IM1609 10 and IM1609 08 models are no exception. These cutting-edge monitors are designed to meet a wide array of professional needs while delivering outstanding performance and visual clarity.

One of the standout features of the IM1609 10 is its impressive 16:9 aspect ratio and full HD resolution. This setup ensures that users receive crisp and vibrant visuals, whether they're working on intricate designs, analyzing data, or enjoying multimedia content. The IM1609 08 shares similar visual capabilities, making both models ideal for professionals in graphic design, video editing, and other visually intensive fields.

Both displays incorporate advanced LED backlight technology, which not only enhances color accuracy but also contributes to energy efficiency. Users can expect deeper blacks and brighter whites, resulting in a more dynamic visual experience. Furthermore, the IM1609 series features wide viewing angles, allowing multiple users to view the screen simultaneously without loss of quality or color distortion.

In terms of connectivity, the IM1609 10 and IM1609 08 come equipped with a range of ports, including HDMI, DisplayPort, and USB-C. This versatility ensures seamless integration with various devices, from laptops and desktops to media players and more. The USB-C port also allows for quick data transfer and charging options, catering to the needs of modern tech users.

Ergonomics is another key characteristic of the IM1609 series. With adjustable stands that allow for height, tilt, and swivel adjustments, users can customize their viewing experience for maximum comfort, reducing neck and eye strain during long working hours.

Additionally, the IM1609 monitors feature built-in blue light filters and flicker-free technology, which help to create a healthier viewing environment by minimizing eye fatigue. This consideration for user well-being is increasingly important in today’s tech-driven world, especially for professionals who spend significant time in front of screens.

Overall, Envision Peripherals’ IM1609 10 and IM1609 08 models represent the company’s commitment to blending performance, usability, and comfort into one seamless package. Whether for professional or personal use, these monitors deliver exceptional quality, making them a noteworthy addition to any workspace.