Envision Peripherals IM1609 08 Optional FX10 Microprocessor and BAS Interface, Zone Sensors

Page 30

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

Control Timing & Fault Recognition Delays

Lead compressor “ON” delay

90 seconds

(not applicable for single compressor models)

Minimum compressor “ON” time

2 minutes

(except for fault condition)

 

Short cycle delay

5 minutes

Random start delay

0-120 seconds

High pressure fault

<1 second

Low pressure fault

30 seconds

Water coil low temperature (freeze sensing) fault

30 seconds

Condensate overflow fault

30 seconds

Low pressure fault bypass

2 minutes

Water coil low temperature (freeze sensing)

 

fault bypass

2 minutes

Notes: Refer to Submittal Data SD1981, Application Guide AGFX10, or BACnet Protocol Implementation Conformance Statement for more information.

Optional FX10 Microprocessor and BAS Interface

The FX10 is a microprocessor based control that not only monitors and controls the heat pump but also can com- municate any of this information back to the building automation system (BAS). This means that not only does the control monitor the heat pump at the unit you can also monitor and control many the features over the BAS. This clearly puts the FX10 in a class of its own.

The control will enumerate all fault conditions (HP, LP, CO, LOC, and Water Coil Low Temp (Freeze Sensing)) over a BAS as well as display them on a medium user interface (MUI). HP, LP, CO and Water Coil Low Temp (Freeze Sens- ing) faults can all be reset over a BAS. A Loss Of Charge fault can not be reset or bypassed until the problem has been corrected. A MUI is invaluable as a service tool for the building service team.

can be changed over a BAS or with a MUI. The control has an input programmed to enable field installed emergency heat in the event that the compressor is locked out. This input can also be commanded on from a BAS as needed. An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled. Relative humidity can be read by a 0-5VDC humidity sensor that is displayed over the network. If you are using an ECM fan motor the control can enable dehumidification mode based on a set point in the control. The dehumidification set point itself can also be changed over a BAS or with a MUI. Dehumidification mode can also be enabled by the BAS. Because the FX10 is not factory configured to read CO2 levels, contact the factory for application assistance.

The FX10 control has unused analog and digital inputs for field installed items such as air temperature, water tem- perature, CO2 or current status switches. The control has unused binary and PWM outputs that can be commanded over the BAS for field use. An optional Medium User Inter- face (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK1 - Panel mount version and the MUIK2-Wall mount version.

Zone Sensors

There are two options for zone sensors that can be used with the FX10 control. Both sensors use a Johnson con- trols A99 positive temperature coefficient type sensor.

The TAXXJ02 has a set point adjustment now which will give the end user a +/- 5°F adjustment from the set point as well as a push button that can be used for temporary occupancy. The control leaves the factory set to operate with a TAXXJ02 sensor and can be changed to read the TAXXA01 sensor through a building automation system or with a user interface.

Standard Features

Anti Short Cycle

High Pressure Protection

Low Pressure Protection

Water Coil Low Temperature (Freeze Sensing)

Loss Of Charge Detection

Random Start

Display for diagnostics

Reset Lockout at disconnect or through BAS

2 Accessory outputs

Optional BAS add-on controls

The unit can be commanded to run by a typical heat pump thermostat or run based on heating and cooling set points supplied by a BAS. The control board is wired with quick connect harnesses for easy field change out of a bad control board. All ECM variable fan speed settings

DDC Operation & Connection

Other optional network protocol boards that can be added to the FX10 are:

Johnson Control N2

LonWorks

BACnet

29

Image 30
Contents Envision Console Installation Manual Page Table of Contents Model Nomenclature NC CRefrigerant Systems General Installation InformationSafety Considerations Moving and StorageDimensional Data Flat Top Cabinet NCW09-18NCS09-18 Dimensional Data Slope Top CabinetConfiguration Slope TopDimensional Data Extended Slope Top Cabinet NCE09-18Ext. Slope Top Dimensional Data Right Return Controls Detail Dimensional Data Right Return Chassis Dimensional Data Left Return Controls Detail Dimensional Data Left Return Chassis #Installation Steps Mark Unit PositionProvide Water and Condensate Drain Connections Pipe LocationsFinal Electrical Connection Provide Line Voltage WiringChassis Installation Final Water ConnectionField Converting Console Top view Side viewSystem Cleaning and Flushing Cleaning and FlushingGround Source Loop System Checkout Open Loop Ground Water Systems Water QualityAuxiliary Heat Ratings Microprocessor Remote Thermostat WiringElectrical Connections GeneralUnit Electrical Data Fan Performance DataWiring Schematic 208-230-265/60/1CCM w/EH Electronic Thermostat 208-230-265/60/1 Control ModuleLED Display Mode Table 208-230-265/60/1 Schematic a Versatec Control EH & Remote Wall ThermostatFX10 EH 208-230-265/60/1 PSCStandard CCM Control Features Envision Console Controls Optional Versatec Microprocessor Control Features Logic Board DIP Switch Settings Control Tables for Optional Versatec MicroprocessorOptional FX10 Control Optional FX10 Microprocessor and BAS Interface Control Timing & Fault Recognition DelaysStandard Features Zone SensorsControl and Safety Feature Details Sequence of OperationCompressor Minimum On Delay Random Start DelayCompressor Fixed On Delay Time Compressor Short Cycle Delay TimeInputs & Outputs Configuration Control AccessoriesInfo Status Temps Outputs Settings FX10 User Interface MUI Physical Layout Login Required N2 Open LonWorks LonWorks Point DescriptionBACNet BACnet Point DescriptionAnalog Output Type BACnet VariablesAnalog Input Type Analog Value TypeMultistate Input Type Multistate Output TypeEmergency Electric Resistance Heat Hydronic Loop Controller for Boiler/Tower InstallationsUnit Startup Notes Electrical DisconnectUnit Startup Checklist / Unit Startup Steps Before Powering Unit, Check The FollowingStartup Steps Unit Operating Parameters Unit Operating LimitsSingle Speed Models Startup/Troubleshooting Form Pressure Drop Water Coil Maintenance Preventive MaintenanceReplacement Procedures Other MaintenancePage Envision Series Console