Queries of System Variables, Status, Faults

Single Values:

Command

Description

Units

Range

Default

E2 / Par. set

ACTU

Query for actual current U

0.01 A

 

 

– /

CUR.ACTU

 

 

 

 

 

 

 

 

 

 

 

ACTV

Query for actual current V

0.01 A

 

 

– /

CUR.ACTV

 

 

 

 

 

 

 

 

 

 

 

ANAIN

Query for analog input

mV

 

 

– /

SYS.ANAIN

 

 

 

 

 

 

 

 

 

 

 

POS,

Queries motor position

 

 

 

– /

RPOS,

 

 

 

 

 

 

 

 

 

 

 

SYS.POS

Resolver bits / encoder counts

 

 

 

– /

POS.POS

 

 

 

 

 

 

 

 

 

 

 

VEL

Query feedback velocity

RPM

 

 

 

VEL.VEL

 

 

 

 

 

Data Record ( REC. prefixed ) Parameters:

Command

Description

Units

Range

Default

E2 / Par. set

REC.GAP

Specify gap between recording samples in

0 : 65535

1

E / –

 

number of servo loops (0.5 ms)

 

 

 

 

 

 

 

 

 

 

REC.TIME

Specify recording time

0.5 ms

1:65535

1000

– /

REC.VAR1,

Specify recording variable: “POS”: position,

s. left

“POS”

– /

REC.VAR2

“REF”: velocity command, “VEL”: velocity,

 

 

“VEL”

 

 

“CUR”: current command, “ACTU”: current

 

 

 

 

 

U, “ACTV”: current V, “FE”: position

 

 

 

 

 

following error.

 

 

 

 

Data Record ( REC. prefixed ) Variable:

Command

Description

Units

Range

Default

E2 / Par. set

REC.VFREE1

Specify recording address for REC.VAR1

Unsign.Long

 

– /

 

 

 

 

 

 

REC.VFREE1

Specify recording address for REC.VAR2

Unsign.Long

 

– /

Methods:

Command

Description

Parameter

Units

Range

GETD

Gets data from recording buffer in decimal form.

 

 

 

 

 

GETX

Gets data from recording buffer in hex form, data buffer is

 

cleared afterwards

 

 

 

 

 

 

 

 

REC

Starts(“on”) / stops (“off”) recording process

start / stop

“on”, “off”

B-10 Command Set

MN1851

Page 87
Image 87
Baldor MN1851 manual Queries of System Variables, Status, Faults Single Values, Data Record REC. prefixed Parameters