Baldor MN1851 manual Wire Size for units without Power Supply, X1 Power Connections, Breaker, Mm2

Models: MN1851

1 95
Download 95 pages 28.33 Kb
Page 16
Image 16

Table 3-1 Wire Size and Protection Devices (for units with Power Supply)

Catalog Number

 

 

Incoming Power

 

 

 

 

Continuous

Input

Input

Wire Gauge

 

Nominal Input

Fuse

 

Output

Breaker

 

 

 

Voltage

Time

AWG

mm2

 

Amps (RMS)

(A)

 

 

Delay (A)

(USA)

(Europe)

 

 

 

 

 

 

 

 

 

 

 

LP1A02SR-EXXX

115V (1f)

2.0A

8

8

14

2.5

LP2A02SR-EXXX

230V (3f)

2.5A

10

10

14

2.5

LP1A02TR-EXXX

115V (1f)

2.0A

8

8

14

2.5

LP2A02TR-EXXX

230V (1f)

2.5A

10

10

14

2.5

LP4A02TB-EXXX

400/460V (3f)

2.5A

10

10

14

2.5

LP1A05SR-EXXX

115V (1f)

5A

20

20

14

2.5

LP1A05SR-EXXX

230V (3f)

5A

20

20

14

2.5

LP1A05TR-EXXX

115V (1f)

5A

20

20

14

2.5

LP2A05TR-EXXX

230V (1f)

5A

20

20

14

2.5

LP4A05TB-EXXX

400/460V (3f)

5A

20

20

14

2.5

LP1A07TR-EXXX

115V (1f)

7.5A

30

30

14

2.5

LP2A07TR-EXXX

230V (1f)

7.5A

30

30

14

2.5

LP4A07TR-EXXX

400/460V (3f)

7.5A

30

30

14

2.5

LP1A10SR-EXXX

115V (1f)

10A

40

40

14

2.5

LP2A10SR-EXXX

230V (3f)

10A

40

40

14

2.5

LP1A15SR-EXXX

115V (1f)

15A

60

60

12

2.5

 

 

 

 

 

 

 

LP2A15SR-EXXX

230V (3f)

15A

60

60

12

2.5

 

 

 

 

 

 

 

LP4A15TR-EXXX

400/460V (3f)

15A

60

60

12

2.5

 

 

 

 

 

 

 

LP4A20TR-EXXX

400/460V (3f)

20A

60

60

12

2.5

 

 

 

 

 

 

 

Table 3-2 Wire Size (for units without Power Supply)

Catalog Number

Bus

Continuous

Wire Gauge

 

Output

AWG

mm2

 

Voltage

 

Amps

(USA)

(Europe)

 

 

 

 

 

 

 

LP1A02PO-EXXX

160VDC

2.0A

14

2.5

LP2A02PO-EXXX

300VDC

2.5A

14

2.5

LP1A05PO-EXXX

160VDC

5.0A

14

2.5

LP2A05PO-EXXX

300VDC

5.0A

14

2.5

LP1A10PO-EXXX

160VDC

10.0A

12

2.5

LP2A10PO-EXXX

300VDC

10.0A

12

2.5

LP1A15PO-EXXX

160VDC

15.0A

10

2.5

LP2A15PO-EXXX

300VDC

15.0A

10

2.5

Note: All wire sizes are based on 75° C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 25° C ambient, maximum continuous control output current and no harmonic current.

X1 Power Connections

Power connections are shown in Figures 3-5 through 3-8.

MN1851

Receiving & Installation 3-5

Page 16
Image 16
Baldor MN1851 manual Wire Size for units without Power Supply, X1 Power Connections, Breaker, Mm2, Voltage