Figure 3-10 Connector Locations (Three Phase Controls)

X1 - Power Connector

The holes in the top and bottom of the

enclosure are for cable clamps. Be sure

PE

Earth

 

to use an M4 bolt 12mm in length.

L1

Phase 1 Input

Input Power

Longer bolts may short circuit the

L2

Phase 2 Input

electrical components inside the control.

L3

Phase 3 Input

 

U

Motor lead “U”

Motor

 

V

Motor lead “V”

 

W

Motor lead “W”

 

 

R1

Dynamic Brake

Dynamic Brake

 

R2

Dynamic Brake

(Regen Resistor)

 

+24V

Customer

LPxAxxxx-xxx3

 

0V

Provided

 

only 

 

 

 

 

Terminal tightening torque is

 

 

 

 

 

X9 - Encoder Input

0.5 lb-in (0.6Nm)

1

CHA+

9

Hall 3+

 

 

2

CHB+

10

Hall 2+

 

3

CHC+

11

+5VDC

 

4

Hall 1+

12

Reserved

 

5

Hall 1–

13

DGND

 

 

 

 

 

6

CHA-

14

Hall 3–

 

 

 

 

 

7

CHB-

15

Hall 2–

 

 

 

 

8

CHC-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X3 - Control Signals & Digital I/O

 

X6 - RS232 / 485

 

RS232

 

RS485

1

CMD+

 

 

1 Reserved

1

TX-

2

CMD-

2

Rx Data

2

TX+

3

AGND

3

Tx Data

3

RX+

4

Fault Relay+

4

DTR

4

RX-

5

Fault Relay-

5

DGND

5

DGND

6

CIV

6

DSR

6

RTS-

7

CREF

7

RTS

7

RTS+

8

CGND

8

CTS

8

CTS+

9

Enable

9

+5V

9

CTS-

10

MaI3

 

 

 

 

11

MaI4

 

 

 

 

12

Hold

 

X7 - Encoder Output

13

Fault Reset

1

CHA+

6

CHA–

14

Home Flag

15

Trigger

2

CHB+

7

CHB–

16

MaI1

3

CHC+

8

CHC–

17

MaI2

4

Reserved 9

Reserved

18

MaO1

5

DGND

 

 

19

MaO2

 

 

 

 

20

DrOK

 

 

 

 

 

 

Note: Reserved means no connection is required

 

 

 

and no connection should be made to this

 Important:

 

terminal. It is reserved for future use.

LPxAxxxx-xxx3 only.

A separate 24VDC supply to the “Logic Power” input is required for

operation. An LPxAxxxx-xxx3 control will not operate without 24VDC on this input.