Baldor MN1851 Section Switch Setting and Start-Up, Switch AS1 Settings, Control Address Setting

Models: MN1851

1 95
Download 95 pages 28.33 Kb
Page 32
Image 32

Section 4

Switch Setting and Start-Up

Switch AS1 Settings

AS1

Monitor

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

Off / On

 

AS1 switches are located on the front panel between X1 and the “Monitor” LED.

Note: AS1–8 is shown in the “ON” position (Drive Enabled). All other switches are shown in the “OFF” position.

Address Setting, AS1-1 to AS1-4 (for Multi-Drop Applications)

Each control address can be set using switches AS1-1 to AS1-4 of each control. Each control must have a unique address. Refer to Table 4-1.

Table 4-1 Control Address Setting

AS1-1

AS1-2

AS1-3

AS1-4

Control Address (Hexadecimal)

OFF

OFF

OFF

OFF

0 (Factory Setting)

ON

OFF

OFF

OFF

1

OFF

ON

OFF

OFF

2

ON

ON

OFF

OFF

3

OFF

OFF

ON

OFF

4

ON

OFF

ON

OFF

5

OFF

ON

ON

OFF

6

ON

ON

ON

OFF

7

OFF

OFF

OFF

ON

8

ON

OFF

OFF

ON

9

OFF

ON

OFF

ON

A

ON

ON

OFF

ON

B

OFF

OFF

ON

ON

C

ON

OFF

ON

ON

D

OFF

ON

ON

ON

E

ON

ON

ON

ON

F

MN1851

Switch Setting & Start-Up 4-1

Page 32
Image 32
Baldor MN1851 manual Section Switch Setting and Start-Up, Switch AS1 Settings, Control Address Setting