Operating Mode Select the operating mode of the control. Choices are:

1.Current Mode

2.Velocity Mode

3.Positioning Mode (15 preset point to point moves) Click “Download” when finished.

Figure A-12 Operating Mode Selection Screen

Current Parameter

Nominal and peak current values are automatically entered for the motor type. For manual tuning only, set the control current limit value to a percentage of the continuous current rating. For example, if your control is rated for 5A continuous current and you desire to limit the output current to 4A, enter 80%. If you wish to use the full output power of the control, enter 100%. Click “Download” when finished.

Figure A-13 Current Parameter Screen

A-4 Manual Tuning