4-4. Connecting 3-Phase Input Power
3
= GND/PE Earth Ground
4
7
2
|
| L1 |
|
3 |
| L2 | 5 |
| 6 | L3 |
|
|
|
|
1
1
Tools Needed:
YInstallation must meet all National and Local Codes − have only quali- fied persons make this installation.
YDisconnect and lockout/tagout in- put power before connecting input conductors from unit.
YAlways connect green or green/ yellow conductor to supply grounding terminal first, and nev- er to a line terminal.
.The
1Input Power Cord.
2Disconnect Device (switch shown in the OFF position)
3Green Or Green/Yellow Grounding Conductor
4Disconnect Device Grounding Terminal
5Input Conductors (L1, L2 And L3)
6Disconnect Device Line Terminals
Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.
Connect input conductors L1, L2, and L3 to disconnect device line terminals.
7 Overcurrent Protection
Select type and size of overcurrent protec- tion using Section
Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.