4-8.  Electrical Service Guide For 240 VAC
YCAUTION: INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of 60 Hz (+10%) power at +10% of rated input voltage. Phase to ground voltage shall not exceed +10% of rated input voltage. Do not use a generator with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
NOTE
Actual input voltage should not exceed ± 10% of indicated required input voltage. If actual input voltage is outside of this range, output may not be available.
| 
 | 60 Hz | |
| 
 | Single | |
| 
 | Phase | |
| 
 | 
 | |
| Input Voltage | 240 | |
| 
 | 
 | |
| Input Amperes At Rated Output | 13.9 | |
| 
 | 
 | |
| Max Recommended Standard Fuse Rating In Amperes | 
 | |
| Circuit Breaker 1,  | 15 | |
| Normal Operating 3 | 20 | |
| Min Input Conductor Size In AWG 4 | 14 | |
| Max Recommended Input Conductor Length In Feet (Meters) | 91 | |
| (28) | ||
| 
 | ||
| 
 | 
 | |
| Min Grounding Conductor Size In AWG 4 | 14 | |
| Reference: 2005 National Electrical Code (NEC) (including article 630) | 
 | 
1Choose a circuit breaker with 
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.
4-9.  Extension Cord Data
NOTE
When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
| 
 | Input Power | 
 | 
 | 
 | 
| Input Voltage | Phase | Hertz | Conductor Size | Max. Cord Length | 
| 
 | 
 | 
 | 
 | 
 | 
| 120 V | 1 | 60 | 14 AWG | 22 ft (7 m) | 
| 
 | 
 | 
 | 
 | 
 | 
| 240 V | 1 | 60 | 14 AWG | 91 ft (28 m) | 
| 
 | 
 | 
 | 
 | 
 |