Page 48

10.10 Typical Connections to Supply Standby Power

1Power Company Service Meter

2Main and Branch Overcurrent Protection

3Double-Pole, Double-Throw Transfer Switch

Obtain and install correct switch. Switch rating must be same as or greater than the branch overcurrent protection.

4Circuit Breakers or Fused Disconnect Switch

Obtain and install correct switch.

5 Extension Cord

Select as shown in Section 10.11. 6 Generator Connections

Connect terminals or plug of ade- quate amperage capacity to cord. Follow all applicable codes and safety practices.

Turn off or unplug all equipment connected to generator before starting or stopping engine. When starting or stopping, the engine has low speed which causes low volt- age and frequency.

7 Load Connections

S-0405-A

.Customer-supplied equipment is required if

generator is to supply standby power during emergencies or power outages.

1

240 V

 

 

 

120/240 Volt

120 V

 

60 Hz

 

Three-Wire

120 V

 

Service

 

 

 

2

Neutral

3

 

 

240 V

 

Load

120 V

 

120 V

 

 

 

7

 

4

 

 

 

 

CB

 

 

or

 

 

F1

 

 

5

6

 

 

 

240 V

 

120/240 Volt

120 V

 

Single-Phase

 

 

Three-Wire

120 V

 

Generator Output

 

 

Connection

Ground

 

44

OM-402

Image 48
Contents OM-402B ProcessesDescription From Miller to You Table of Contents Metro 250DPage Safety Precautions − Read Before Using Symbol UsageArc Welding Hazards Engine Hazards Battery Explosion can Blind Moving Parts can cause injuryEngine Exhaust Gases can kill Engine Heat can cause firePrincipal Safety Standards EMF InformationRadiation can cause interference ARC Welding can cause interferenceSignification des symboles Consignes de sécurité − lire avant utilisationUN Choc Électrique peut tuer LES Fumées ET LES GAZ peuvent être dangereuxLE Soudage peut provoquer un in- cendie ou une explosion DES Particules Volantes peuvent blesser les yeuxDES Pièces Chaudes peuvent provoquer des brûlures graves LE Bruit peut affecter l’ouïeDES Organes Mobiles peuvent provoquer des blessures ’EXPLOSION DE LA Batterie peutLA Chaleur DU Moteur peut pro- voquer un incendie LA Chute DE L’APPAREIL peut blesserPrincipales normes de sécurité Information sur les champs électromagnétiquesÉlectrostatiques peuvent endommager les circuits imprimés UNE Remorque QUI Bascule peut entraîner des blessuresSymbols and Definitions DefinitionsGeneral Precautionary Label Battery Charging Label Fan and Moving Parts LabelHot Muffler Label Diesel Fuel LabelFalling Equipment Label Activation Tag− 50 h Std Do Not Use Ether Label Manufacturer’s Rating LabelSpecifications Weld, Power, and Engine SpecificationsDimensions, Weights, and Operating Angles Volt-Ampere CurveFuel Consumption Duty Cycle and OverheatingInstallation AC Auxiliary Power CurveInstalling Welding Generator Location GroundingConnecting Battery and Installing Exhaust Pipe Engine Prestart ChecksStop engine Connect negative − cable lastConnecting to Weld Output Terminals Selecting Weld Cable Sizes100 ft 30 m or Less 10 − 60% 60 − 100% Duty 10 − 100% Duty CycleRemote 14 Receptacle RC1 Information Ref. ST-158Socket Information Using Idle Lock Switch Operating the Welding GeneratorFront Panel Controls PlugRemote Amperage and Contactor Control Auxiliary Power Receptacles Operating Auxiliary EquipmentMaintenance & Troubleshooting 100 Hrs Maintenance Changing Engine Oil and Oil Filter Servicing Air Cleaner To Clean air filterDo not clean housing with air hose Changing Fuel FiltersAdjusting Engine Speed Idle Speed AdjustmentWeld/Power Speed Adjustment Weld And Auxiliary Power Circuits Remote Control CircuitOverload Protection Engine Control CircuitWelding Troubleshooting Stop engine and let cool. Reinstall cleanout plugServicing Optional Spark Arrestor Trouble RemedyAuxiliary Power Troubleshooting Engine TroubleshootingUle OM-402 Electrical Diagram Circuit Diagram for Welding GeneratorSC-181 Run-In Procedure WetstackingHeavy loading during first Run-In Procedure Using Load Bank Load BankRun-In Procedure Using Resistance Grid Auxiliary Power Guidelines Selecting EquipmentGrounding Generator to Truck or Trailer Frame Grounding When Supplying Building Systems How Much Power Does Equipment Require?Amperes x Volts = Watts Approximate Power Requirements for Industrial Motors Approximate Power Requirements for Farm/Home EquipmentIndustrial Motors Rating Starting Watts Running Watts Farm/Home Equipment Rating Starting Watts Running WattsApproximate Power Requirements for Contractor Equipment Contractor Rating Starting Watts Running WattsPower Required to Start Motor How Much Power Can Generator Supply?Single-Phase Induction Motor Starting Requirements KVA/HP x HP x 1000 = Starting Amperage VoltsTypical Connections to Supply Standby Power Selecting Extension Cord Use Shortest Cord Possible Current Load Watts AmperesParts List Main AssemblyST-801 488-A 11.1 PC6CB9 Panel, Front w/Components .1 Item 11.2 CB5Generator .1 Item Control Box w/Components .1 Item Diode BoardOM-402 Page OM-402 Page Options and Accessories Metro 250DCall Miller for your local Miller distributor Owner’s Record Miller Electric Mfg. Co