Siemens 38-3AH3 38 kV instruction manual Final mechanical inspections without control power

Page 13

Installation checks and functional tests

Note: Secondary-disconnect terminals are numbered 1-16, from right to left.

The automatic spring-charging features of the circuit breaker must be checked. Control power is required for automatic spring-charging to take place.

1.Open control-power circuit by opening the control-power disconnect device.

2.Install the circuit-breaker end of the split-plug jumper (if furnished) to the circuit breaker as shown in Figure 5: Split-plug jumper connected to circuit breaker. The split-plug jumper is secured over the circuit-breaker secondary contacts with thumb screws.

3.Install the switchgear end of the split- plug jumper to the secondary- disconnect block inside the switchgear cubicle as shown in Figure 6: Split-plug jumper connected to switchgear. The jumper slides into place and interconnects all control power and signal leads (for example, electrical trip and close contacts) between the switchgear and the circuit breaker.

4.Energize (close) the control-power circuit disconnect.

5.Use the close and trip controls (refer to Figure 1: Type 38-3AH3 vacuum circuit breaker front panel controls on page 8) to first close and then open the circuit-breaker contacts. Verify the contact positions visually by observing the OPEN/CLOSED indicator on the circuit breaker.

6.De-energize control power by repeating Step 1. Disconnect the split- plug jumper from the switchgear before disconnecting the circuit- breaker end.

7.Perform the spring discharge check again. Verify the closing springs are DISCHARGED and the primary contacts of the type 38-3AH3 vacuum circuit breaker are OPEN.

Final mechanical inspections without control power

1.Make a final mechanical inspection of the circuit breaker. Verify the contacts are in the OPEN position, and the closing springs are DISCHARGED.

2.Check the upper- and lower-primary studs and contact fingers shown in Figure 7: Circuit breaker primary disconnect. Verify mechanical condition of finger springs and the disconnect studs, check for loose hardware, damaged or missing primary-disconnect contact fingers and damaged disconnect studs.

3.Coat movable primary-contact fingers (refer to Figure 7: Circuit breaker primary disconnect) and the secondary-disconnect contacts (refer to Figure 23: Construction of secondary shunt release (shown charged) on page 30) with a light film of Siemens contact lubricant number 15-172-791-233.

4.The type 38-3AH3 vacuum circuit breaker is ready for installation into its assigned cubicle of the metal-clad switchgear. Refer to removal procedures and install the circuit breaker into the switchgear.

5.Refer to the switchgear instruction manual for functional tests of an installed circuit breaker.

Figure 5: Split-plug jumper connected to circuit breaker

Figure 6: Split-plug jumper connected to switchgear

Figure 7: Circuit breaker primary disconnects

13

Image 13 Contents
Answers for energy Qualified person Table of contents Introduction Signal words Hazardous ProceduresIntroduction Introduction Field service operation and warranty issuesReceiving, handling and storage Introduction Receiving procedureShipping damage claims Receiving, handling and storage Handling procedureIndoor storage Storage procedureOutdoor storage Space heating Inspections, checks and tests without control power Installation checks and functional tests De-energizing control power in switchgear Installation checks and functional tests Type 38-3AH3 vacuum circuit breaker racking Racking crank engagement procedureManual-spring charging check Physical inspectionsSplit-plug jumper connected to circuit breaker Final mechanical inspections without control powerVacuum interrupter/ operator Vacuum interrupters Vacuum interrupter/ operatorPrimary disconnects Phase barriersStored-energy operating mechanism Construction Interrupter/operator moduleSwitching operation Current-path assemblyCircuit-breaker pole Vacuum interrupterType 38-3AH3 vacuum circuit breaker pole section Stored-energy operating mechanism Mode of operation Auxiliary switchOperating mechanism Indirect releases tripping coilsUse of manual-spring operation crank ClosingOpening Trip-free functionalityRapid auto-reclosing Manual operation62.2 62.5.2 50.3.1 53.0 Pawl roller 62.5.2 Close-latch pawl Vacuum interrupter/ operator Discharged Closing Standard Undervoltage optional Indirect releases dual-trip orSecondary shunt release optional 54.2Position a locked Shock absorber Capacitor-trip deviceSecondary disconnect Truck-operated cell TOC switch Mechanism-operated cell MOC switch optionalShutter-operating linkage Secondary disconnect Shutters Rating interlock Trip-free interlockCircuit-breaker frame Ground disconnectVehicle function and operational interlocks Racking mechanismAlignment Interlocks Circuit breaker racking-interlocksRacking interlocks Closed circuit breaker interlock Automatic closing-spring energy release Trip-free interlock position mechanical interlock Introduction and maintenance intervals MaintenanceRecommended hand tools MaintenanceInspection items and tests Recommended maintenance and lubricationChecks of the primary power path Removal from switchgearCleanliness check Circuit Number Maintenance and lubricationInspection of primary disconnects Checks of the stored-energy operator mechanismTypical for all three-phases Manual-spring charging and contact- erosion checks Fastener checkAutomatic spring-charging check control power required Wiring and terminals checkElectrical-control checks Secondary-disconnect checkTypical vacuum interrupter contact curve Vacuum-interrupter mechanical check Spring-charging motor checksHigh-potential tests Vacuum-integrity check using dielectric testHigh-potential test voltages Voltage Frequency withstand Field-test voltageContinuous Contact Inspection and cleaning of circuit- breaker insulationRating a Functional testsOverhaul Replacement at overhaulCircuit-breaker overhaul Circuit breaker Number TypeOverhaul Vacuum interrupter replacementSetting Vacuum interrupter replacement illustration Overhaul Hydraulic shock absorber Checking the contact stroke Open the circuit breakerSub-assembly Inspect for Maintenance and troubleshootingProblem Symptoms Possible causes and remedies Maintenance and troubleshootingClosed Appendix Appendix Maximum design voltage Permissible tripping delay YValues Voltage Voltage range factor K3 Insulation Withstand Voltage levels Lightning-impulse BILLevels Voltage levels Lightning-impulse BIL Rated Maximum design voltageRated Continuous4 Short-circuit at rated maximum design voltage I5, 6Remarks Appendix