Siemens 38-3AH3 38 kV instruction manual Introduction, Signal words Hazardous Procedures

Page 4

Introduction

Hazardous voltage and high-speed moving parts.

Will cause death, serious injury and property damage.

Always de-energize and ground the equipment before maintenance. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or by tampering by unqualified personnel will result in dangerous conditions that will cause death, severe injury or equipment damage. Follow all safety instructions contained herein.

Introduction

The 38-3AH3 family of vacuum circuit breakers is designed to meet all applicable ANSI, NEMA and IEEE standards. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the proper design and fabrication by Siemens.

The purpose of this instruction manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment.

Contact the nearest Siemens representative if any additional information is desired.

Signal words

The signal words "danger," "warning" and "caution" used in this instruction manual indicate the degree of hazard that may be encountered by the user. These words are defined as:

Danger - Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

Warning - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Caution - Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

Caution (without safety alert symbol) - Indicates a potentially hazardous situation which, if not avoided, may result in property damage.

Hazardous Procedures

In addition to other procedures described in this instruction manual as dangerous, user personnel must adhere to the following:

1.Always work only on a de-energized circuit breaker. The circuit breaker should be isolated, grounded and have all control power removed before performing any tests, maintenance or repair.

2.Always perform maintenance on the circuit breaker after the spring- charged mechanisms are discharged (except for test of the charging mechanisms). Check to be certain that the indicator flags read OPEN and

DISCHARGED.

3.Always let an interlock device or safety mechanism perform its function without forcing or defeating the device.

4

Image 4 Contents
Answers for energy Qualified person Table of contents Introduction Signal words Hazardous ProceduresIntroduction Field service operation and warranty issues IntroductionReceiving, handling and storage Introduction Receiving procedureShipping damage claims Handling procedure Receiving, handling and storageStorage procedure Indoor storageOutdoor storage Space heatingInspections, checks and tests without control power Installation checks and functional testsDe-energizing control power in switchgear Installation checks and functional tests Racking crank engagement procedure Type 38-3AH3 vacuum circuit breaker rackingPhysical inspections Manual-spring charging checkFinal mechanical inspections without control power Split-plug jumper connected to circuit breakerVacuum interrupter/ operator Vacuum interrupter/ operator Vacuum interruptersPrimary disconnects Phase barriersStored-energy operating mechanism Interrupter/operator module ConstructionCurrent-path assembly Switching operationCircuit-breaker pole Vacuum interrupterType 38-3AH3 vacuum circuit breaker pole section Stored-energy operating mechanism Auxiliary switch Mode of operationOperating mechanism Indirect releases tripping coilsClosing Use of manual-spring operation crankTrip-free functionality OpeningRapid auto-reclosing Manual operation62.2 62.5.2 50.3.1 53.0 Pawl roller 62.5.2 Close-latch pawl Vacuum interrupter/ operator Discharged Closing Standard Indirect releases dual-trip or Undervoltage optionalSecondary shunt release optional 54.2Position a locked Shock absorber Capacitor-trip deviceSecondary disconnect Mechanism-operated cell MOC switch optional Truck-operated cell TOC switchShutter-operating linkage Secondary disconnect Shutters Trip-free interlock Rating interlockCircuit-breaker frame Ground disconnectRacking mechanism Vehicle function and operational interlocksAlignment Interlocks Circuit breaker racking-interlocksRacking interlocks Closed circuit breaker interlock Automatic closing-spring energy release Trip-free interlock position mechanical interlock Maintenance Introduction and maintenance intervalsMaintenance Recommended hand toolsRecommended maintenance and lubrication Inspection items and testsChecks of the primary power path Removal from switchgearCleanliness check Maintenance and lubrication Circuit NumberInspection of primary disconnects Checks of the stored-energy operator mechanismTypical for all three-phases Fastener check Manual-spring charging and contact- erosion checksWiring and terminals check Automatic spring-charging check control power requiredElectrical-control checks Secondary-disconnect checkTypical vacuum interrupter contact curve Spring-charging motor checks Vacuum-interrupter mechanical checkHigh-potential tests Vacuum-integrity check using dielectric testHigh-potential test voltages Field-test voltage Voltage Frequency withstandInspection and cleaning of circuit- breaker insulation Continuous ContactRating a Functional testsReplacement at overhaul OverhaulCircuit-breaker overhaul Circuit breaker Number TypeVacuum interrupter replacement OverhaulSetting Vacuum interrupter replacement illustration Overhaul Checking the contact stroke Open the circuit breaker Hydraulic shock absorberMaintenance and troubleshooting Sub-assembly Inspect forMaintenance and troubleshooting Problem Symptoms Possible causes and remediesClosed Appendix Appendix Permissible tripping delay Y Maximum design voltageValues Voltage Voltage range factor K3 Insulation Withstand Voltage levels Lightning-impulse BILRated Maximum design voltage Levels Voltage levels Lightning-impulse BILRated Continuous4 Short-circuit at rated maximum design voltage I5, 6Remarks Appendix