Siemens 38-3AH3 38 kV instruction manual Removal from switchgear, Checks of the primary power path

Page 43

Maintenance

Removal from switchgear

Prior to performing any inspection or maintenance checks or tests, the circuit breaker must be removed from the switchgear. The "Installation checks and initial functional tests" section (refer to page 8) describes the removal procedure in detail. The principal steps are repeated here for information and guidance, but without the details of the preceding section.

1.The first step is to de-energize the circuit breaker. Figure 36: Trip-control pushbutton (lower button) illustrates the location of the trip control on the circuit-breaker operator panel. Depressing the trip pushbutton opens the circuit breaker prior to removal from the switchgear.

2.The second step in the removal procedure is to de-energize control power to the circuit breaker. Open the control-power disconnect device.

3.Rack the circuit breaker to the DISCONNECT position.

4.Perform the spring discharge check. This is done by first depressing the red trip pushbutton. Second, depress the black close pushbutton. Third, depress the red trip pushbutton again, and observe the spring condition indicator. It should read DISCHARGED.

5.Remove the circuit breaker from the switchgear. Refer to page 10 of "Installation checks and initial functional tests" section of this instruction manual for special instructions and precautions regarding removal of a circuit breaker not at floor level.

6.The circuit breaker can be located either on the floor or on a pallet. Each circuit breaker has four wheels and handles to allow one person to maneuver the unit on a level surface without assistance.

Checks of the primary power path

The primary power path consists of three vacuum interrupters and three upper- and three lower-primary disconnects. These components are checked for cleanliness and condition. The vacuum interrupters are also checked for vacuum integrity.

Some test engineers prefer to perform the contact-erosion check during the manual- spring charging check of the operator, since charging of the springs is necessary to place the contacts in the CLOSED position.

Also, the vacuum-integrity check is usually performed in conjunction with the high- potential test.

These instructions follow the recommendation these tests (contact- erosion/manual-spring charging check and vacuum integrity/high-potential tests) should be combined as described.

Cleanliness check

Figure 37: Type 38-3AH3 vacuum circuit breaker showing vacuum interrupters and primary disconnects (outer phase barrier removed) is a side view of the type 38- 3AH3 vacuum circuit breaker with the outer-insulating barriers removed to show the vacuum interrupter and the upper- and lower-primary disconnects.

All of these components must be cleaned and free of dirt or any foreign objects. Use a dry lint-free cloth. For stubborn dirt, use a clean cloth saturated with isopropyl alcohol (except on a vacuum interrupter).

For stubborn dirt on a vacuum interrupter, use a cloth and warm water and a small amount of mild liquid-household detergent as a cleaning agent. Dry thoroughly using a dry lint-free cloth.

Figure 36: Trip-control pushbutton (lower button)

Figure 37: Type 38-3AH3 vacuum circuit breaker showing vacuum interrupters and primary disconnects (outer-phase barrier removed)

43

Image 43 Contents
Answers for energy Qualified person Table of contents Introduction Signal words Hazardous ProceduresIntroduction Introduction Field service operation and warranty issuesReceiving, handling and storage Introduction Receiving procedureShipping damage claims Receiving, handling and storage Handling procedureSpace heating Storage procedureIndoor storage Outdoor storageInspections, checks and tests without control power Installation checks and functional testsDe-energizing control power in switchgear Installation checks and functional tests Type 38-3AH3 vacuum circuit breaker racking Racking crank engagement procedureManual-spring charging check Physical inspectionsSplit-plug jumper connected to circuit breaker Final mechanical inspections without control powerVacuum interrupter/ operator Vacuum interrupters Vacuum interrupter/ operatorPrimary disconnects Phase barriersStored-energy operating mechanism Construction Interrupter/operator moduleVacuum interrupter Current-path assemblySwitching operation Circuit-breaker poleType 38-3AH3 vacuum circuit breaker pole section Stored-energy operating mechanism Indirect releases tripping coils Auxiliary switchMode of operation Operating mechanismUse of manual-spring operation crank ClosingManual operation Trip-free functionalityOpening Rapid auto-reclosing62.2 62.5.2 50.3.1 53.0 Pawl roller 62.5.2 Close-latch pawl Vacuum interrupter/ operator Discharged Closing Standard 54.2 Indirect releases dual-trip orUndervoltage optional Secondary shunt release optionalPosition a locked Shock absorber Capacitor-trip deviceSecondary disconnect Truck-operated cell TOC switch Mechanism-operated cell MOC switch optionalShutter-operating linkage Secondary disconnect Shutters Ground disconnect Trip-free interlockRating interlock Circuit-breaker frameInterlocks Circuit breaker racking-interlocks Racking mechanismVehicle function and operational interlocks AlignmentRacking interlocks Closed circuit breaker interlock Automatic closing-spring energy release Trip-free interlock position mechanical interlock Introduction and maintenance intervals MaintenanceRecommended hand tools MaintenanceInspection items and tests Recommended maintenance and lubricationChecks of the primary power path Removal from switchgearCleanliness check Checks of the stored-energy operator mechanism Maintenance and lubricationCircuit Number Inspection of primary disconnectsTypical for all three-phases Manual-spring charging and contact- erosion checks Fastener checkSecondary-disconnect check Wiring and terminals checkAutomatic spring-charging check control power required Electrical-control checksTypical vacuum interrupter contact curve Vacuum-interrupter mechanical check Spring-charging motor checksHigh-potential tests Vacuum-integrity check using dielectric testHigh-potential test voltages Voltage Frequency withstand Field-test voltageFunctional tests Inspection and cleaning of circuit- breaker insulationContinuous Contact Rating aCircuit breaker Number Type Replacement at overhaulOverhaul Circuit-breaker overhaulOverhaul Vacuum interrupter replacementSetting Vacuum interrupter replacement illustration Overhaul Hydraulic shock absorber Checking the contact stroke Open the circuit breakerSub-assembly Inspect for Maintenance and troubleshootingProblem Symptoms Possible causes and remedies Maintenance and troubleshootingClosed Appendix Appendix Voltage levels Lightning-impulse BIL Permissible tripping delay YMaximum design voltage Values Voltage Voltage range factor K3 Insulation WithstandShort-circuit at rated maximum design voltage I5, 6 Rated Maximum design voltageLevels Voltage levels Lightning-impulse BIL Rated Continuous4Remarks Appendix