Siemens 38-3AH3 38 kV instruction manual Racking crank engagement procedure

Page 11

Installation checks and functional tests

Heavy weight.

Can result in death, serious injury or property damage.

Do not transport a circuit breaker using a lift truck with the lift truck in the raised position.

Figure 2: Type 38-3AH3 vacuum circuit breaker racking

5.Move the circuit-breaker release latch (on the floor of the cell near the right side of the circuit breaker) to the left and pull the circuit breaker out from the DISCONNECT position. The circuit breaker can now be removed from the cubicle and rolled out onto the two extension rails.

6.Remove the circuit breaker from the two extension rails using the approved Siemens circuit-breaker lifting device or Siemens lifting sling and a suitable crane.

7.Lift the two extension rails and withdraw them from the switchgear.

8.Close the circuit-breaker compartment door and secure all latches.

Type 38-3AH3 vacuum circuit breakers weigh between 800 and 1,000 lbs (364- 455 kg) depending upon ratings. The circuit breaker can be moved using a properly rated crane and lift sling. A lift sling can be attached to the circuit breaker, and then used to hoist the circuit breaker vertically clear of the extension rails. When clear, remove the rails and lower the circuit breaker to the floor.

Racking crank engagement procedure

A crank for racking the circuit breaker is provided as a standard accessory. Racking a circuit breaker can be accomplished with the drawout-compartment-front door open or through a small opening (or window) in the front door, with the door closed. Racking a rollout-fuse truck is accomplished with the compartment-front door open.

The racking crank consists of an offset handle with a custom socket assembly welded to the end. The socket end of the crank is designed to engage the shoulder of the racking-mechanism shaft and remain engaged during racking with spring plungers. The plungers operate in a manner similar to the retainers of an ordinary mechanic’s socket wrench.

The portion of the racking-mechanism shaft visible is cylindrical, and the shoulder of the racking-mechanism shaft is hidden by a shroud until the engagement procedure starts. The square socket-end of the crank will only engage the shoulder of the shaft if it is aligned properly.

Figure 3: Use of extension rails for voltage transformer (VT) fuse- rollout truck or circuit breaker not at floor level (VT fuse-rollout truck in upper cell shown. Procedure for circuit breaker in lower cell but not at floor level is similar.)

11

Image 11 Contents
Answers for energy Qualified person Table of contents Introduction Signal words Hazardous ProceduresIntroduction Introduction Field service operation and warranty issuesShipping damage claims Introduction Receiving procedureReceiving, handling and storage Receiving, handling and storage Handling procedureSpace heating Storage procedureIndoor storage Outdoor storageDe-energizing control power in switchgear Installation checks and functional testsInspections, checks and tests without control power Installation checks and functional tests Type 38-3AH3 vacuum circuit breaker racking Racking crank engagement procedureManual-spring charging check Physical inspectionsSplit-plug jumper connected to circuit breaker Final mechanical inspections without control powerVacuum interrupter/ operator Vacuum interrupters Vacuum interrupter/ operatorStored-energy operating mechanism Phase barriersPrimary disconnects Construction Interrupter/operator moduleVacuum interrupter Current-path assemblySwitching operation Circuit-breaker poleType 38-3AH3 vacuum circuit breaker pole section Stored-energy operating mechanism Indirect releases tripping coils Auxiliary switchMode of operation Operating mechanismUse of manual-spring operation crank ClosingManual operation Trip-free functionalityOpening Rapid auto-reclosing62.2 62.5.2 50.3.1 53.0 Pawl roller 62.5.2 Close-latch pawl Vacuum interrupter/ operator Discharged Closing Standard 54.2 Indirect releases dual-trip orUndervoltage optional Secondary shunt release optionalPosition a locked Secondary disconnect Capacitor-trip deviceShock absorber Truck-operated cell TOC switch Mechanism-operated cell MOC switch optionalShutter-operating linkage Secondary disconnect Shutters Ground disconnect Trip-free interlockRating interlock Circuit-breaker frameInterlocks Circuit breaker racking-interlocks Racking mechanismVehicle function and operational interlocks AlignmentRacking interlocks Closed circuit breaker interlock Automatic closing-spring energy release Trip-free interlock position mechanical interlock Introduction and maintenance intervals MaintenanceRecommended hand tools MaintenanceInspection items and tests Recommended maintenance and lubricationCleanliness check Removal from switchgearChecks of the primary power path Checks of the stored-energy operator mechanism Maintenance and lubricationCircuit Number Inspection of primary disconnectsTypical for all three-phases Manual-spring charging and contact- erosion checks Fastener checkSecondary-disconnect check Wiring and terminals checkAutomatic spring-charging check control power required Electrical-control checksTypical vacuum interrupter contact curve Vacuum-interrupter mechanical check Spring-charging motor checksHigh-potential test voltages Vacuum-integrity check using dielectric testHigh-potential tests Voltage Frequency withstand Field-test voltageFunctional tests Inspection and cleaning of circuit- breaker insulationContinuous Contact Rating aCircuit breaker Number Type Replacement at overhaulOverhaul Circuit-breaker overhaulOverhaul Vacuum interrupter replacementSetting Vacuum interrupter replacement illustration Overhaul Hydraulic shock absorber Checking the contact stroke Open the circuit breakerSub-assembly Inspect for Maintenance and troubleshootingProblem Symptoms Possible causes and remedies Maintenance and troubleshootingClosed Appendix Appendix Voltage levels Lightning-impulse BIL Permissible tripping delay YMaximum design voltage Values Voltage Voltage range factor K3 Insulation WithstandShort-circuit at rated maximum design voltage I5, 6 Rated Maximum design voltageLevels Voltage levels Lightning-impulse BIL Rated Continuous4Remarks Appendix