Trane Tracer, ZN510 Controller manual VAC Compr, Compr Binary Outputs, Analog Inputs

Page 12

Unit Operation

24 VAC

 

 

Compr 2

 

 

 

 

 

 

 

 

 

 

 

HPC

LPC

Compr 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Binary Outputs

 

 

 

 

Figure 7: High and low pressure switch

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

The ZN510 controller includes an automatic diag-

1

2

3

4

5

6

7

nostic reset function that allows the controller to

 

 

 

 

 

 

 

automatically recover after a high or low pres-

 

 

 

 

 

 

 

sure cutout diagnostic. After 30 minutes the con-

 

 

 

 

 

 

 

troller will reset the diagnostics. Most

 

 

 

 

 

 

 

 

diagnostics occur due to intermittent water tem-

 

 

 

 

 

 

 

perature or flow problem. The “smart reset” may

 

 

 

 

 

 

 

eliminate many service calls.

 

 

 

 

 

 

 

 

Analog Inputs

The ZN510 controller has five available analog inputs (AI). These inputs are factory-configured for the following functions:

zZone = Space temperature.

zSet = Local setpoint.

zFan = Fan mode input.

zAI 1 = Leaving water tem- perature (Circuit 1).

zAI 2 = Discharge air tem- perature.

See Figure 8 for analog inputs.

TB3-1

TB3-2

Zone Sensor

TB3-3

 

TB3-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Inputs

TB3-5

J3-4

J3-3

J3-2

J3-1

AI 2

AI 1

Discharge Air Sensor

Leaving Water Sensor (Circuit)

Zone (1TB1-1)

Ground (1TB1-2)

Setpoint (1TB1-3)

Fan (1TB1-4)

 

 

 

Figure 8: Analog inputs.

12

Image 12
Contents WSHP-IOP-2 Installation, Operation Literature History1998, American Standard Company Table of Contents Start-up Procedure Installation of New UnitsZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagUnit Operation CommunicationPower Binary OutputsPosition Damper Actuator or Generic Binary Output Binary input configurations Binary Input Description Configuratio Contact Closure OpenOutput Overrides Condensate Overflow OccupancyHigh and Low Pressure Switches Description Communicated Request Hardwired State ResultGeneric Binary Input 24 VAC Compr Compr Binary OutputsAnalog Inputs Discharge Air Sensor Leaving Water Sensor CircuitFan Mode Input Local SetpointOccupied setpoints Fan Off Delay Filter Maintenance TimerInternal and External Setpoint Adjustment Zone SensorZone Sensor Setpoint OperationZone Sensor Features Fan Switch Optional Communication JackZone Sensor Specifications Heating or Cooling Control Mode Operation Compressor Minimum ON/OFF TimersHeating or Cooling Operation Capacity Unit Between 100% 50%Single and Dual Compressor Operation Morning Warm UpData Sharing Master ControllerConfiguration Troubleshooting Red Service LEDYellow Service LED Green Status LEDManual Output Testing the Heat Pump ConfigurationsTesting the Heat Pump Configurations Pump Operation for Systems with ZN510 Loop ControllerQuestionable Unit Operation Fan output does not energizeNicated information Wait time expiresCompressors not running Outdoor air damper stays openOutdoor air damper stays closed Diagnostics ZN510 controller diagnosticsDiagnostic Fan Other Outputs Translating Multiple Diagnostics Resetting DiagnosticsCycling Power Rover Service ToolWiring Diagram Wiring Diagram Hardware Specifications Specifications Board DimensionsOperating Environment 32 to 140 F 0 to 60 C Agency ListingsBinary Inputs Description Terminals FunctionBinary Output J1-1 12 VA VAC RMS typical J1-2 J1-4 Binary Output J1-5 12 VA VAC RMS typical J1-6 J1-7