Trane ZN510 Controller, Tracer manual Single and Dual Compressor Operation, Morning Warm Up

Page 19

Single and Dual

Compressor

Operation

Other Modes

Occupancy Operation Unoccupied operation normally is associated with evening hours when the space is vacant. In unoccupied mode, the controller always uses the default unoccupied heating and cooling setpoints stored in the controller. As the unit goes unoccupied, the compressors ON timers are ignored and the compressors are disabled.

When ZN510 controls the space to unoccupied mode, the occupant may have the ability to request timed override through the Trane zone sensor’s ON button. Based on the controller or system setup, the

controller interprets the request and initiates the occupied setpoint operation. During a timed override, the controller applies the occupied heating and cooling setpoint, but reports the effective occupancy mode as occupied bypass mode. In the occupied bypass mode, a building automation system can detect whether the occupancy mode was overrode.

Morning Warm Up

The damper (field installed or for the console product) remains closed during morning warm up until the space temperature is within two degrees of the effective heating setpoint. The 2-position outdoor air

damper normally is open during the occupied mode when the controller turns on the unit fan. The damper is normally closed during:

zoccupied mode when the fan is

OFF.

zwarm up/cool down mode.

zoccupied standby mode.

zunoccupied mode.

zcertain diagnostic conditions.

ZN510 keeps the 2-position outside air damper closed on a transition from unoccupied mode to occupied mode as part of the morning warm up sequence.

19

Image 19
Contents WSHP-IOP-2 Literature History Installation, Operation1998, American Standard Company Table of Contents Installation of New Units Start-up ProcedureZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagCommunication Unit OperationBinary Outputs PowerPosition Damper Actuator or Generic Binary Output Binary Input Description Configuratio Contact Closure Open Binary input configurationsOutput Overrides Occupancy Condensate OverflowDescription Communicated Request Hardwired State Result High and Low Pressure SwitchesGeneric Binary Input Discharge Air Sensor Leaving Water Sensor Circuit 24 VAC ComprCompr Binary Outputs Analog InputsLocal Setpoint Fan Mode InputOccupied setpoints Filter Maintenance Timer Fan Off DelaySetpoint Operation Internal and External Setpoint AdjustmentZone Sensor Zone SensorCommunication Jack Zone Sensor Features Fan Switch OptionalZone Sensor Specifications Capacity Unit Between 100% 50% Heating or Cooling Control Mode OperationCompressor Minimum ON/OFF Timers Heating or Cooling OperationMorning Warm Up Single and Dual Compressor OperationMaster Controller Data SharingConfiguration Green Status LED TroubleshootingRed Service LED Yellow Service LEDPump Operation for Systems with ZN510 Loop Controller Manual Output Testing the HeatPump Configurations Testing the Heat Pump ConfigurationsWait time expires Questionable Unit OperationFan output does not energize Nicated informationOutdoor air damper stays open Compressors not runningOutdoor air damper stays closed ZN510 controller diagnostics DiagnosticsDiagnostic Fan Other Outputs Rover Service Tool Translating Multiple DiagnosticsResetting Diagnostics Cycling PowerWiring Diagram Wiring Diagram Agency Listings Hardware SpecificationsSpecifications Board Dimensions Operating Environment 32 to 140 F 0 to 60 CBinary Output J1-5 12 VA VAC RMS typical J1-6 J1-7 Binary InputsDescription Terminals Function Binary Output J1-1 12 VA VAC RMS typical J1-2 J1-4