Trane ZN510 Controller, Tracer manual Generic Binary Input, High and Low Pressure Switches

Page 11

Unit Operation

In Occupied mode, the controller operates according to the occupied setpoints. In Occupied Standby Mode, the unit controller operates according to the Occupied Standby setpoints. When the controller receives a communicated unoccupied request, the controller

operates according to the unoccupied setpoints regardless of the state of the hardwired occupancy input.

If neither the binary input nor the communicated input is used to select the occupancy mode, the

controller defaults to occupied mode because the occupancy binary input (if present) typically is configured as normally open without an occupancy device connected.

Table 4: Normally open hardwired input configuration (BI 3)

Description

Communicated Request

Hardwired State

Result

 

 

 

 

Standalone

NA

Open = Occupied

Occupied

 

 

 

 

Standalone

NA

Closed = Unoccupied

Unoccupied

 

 

 

 

Communicating

Occupied

Open = Occupied

Occupied

 

 

 

 

Communicating

Unoccupied

Open = Occupied

Unoccupied

 

 

 

 

Communicating

Occupied Standby

Open = Occupied

Occupied Standby

 

 

 

 

Communicating

Occupied

Closed = Occupied Standby

Occupied Standby

 

 

 

 

Communicating

Unoccupied

Closed = Occupied Standby

Unoccupied

 

 

 

 

Communicating

Occupied Standby

Closed = Occupied Standby

Occupied Standby

 

 

 

 

Note:

If configured for normally closed, all states are opposite of Table 4.

Generic Binary Input

Building automation systems can monitor the status of the generic binary input. This input does not affect controller operation.

High and Low Pressure

Switches

The high and low pressure cutout switches are wired in series with the compressor contactor in the unit. The ZN510 controller detects the state of each switch circuit by monitoring the controller’s compressor triac outputs. If either the high pressure switch (HPC) or the low pressure switch (LPC) switch opens, a fault condition occurs. This open circuit prevents the

compressor contactor from energizing keeping the compressor from running. The controller automatically detects the fault condition by measuring the compressor triac output signal.

By default, when the HPC or LPC switches detect a high or low pressure condition in the refrigerant circuit, the special input detects the diagnostic and disables all compressor operation for that circuit. The unit fan continues to operate, if only one circuit is disabled in a two compressor unit. When the HPC/LPC diagnostic is present on both circuits, the ZN510 shuts off the unit fan and disables

unit operation. See Figure 7 for high and low pressure switch.

When the refrigerant circuit returns to normal, the HPC and the LPC switches automatically reset. The high or low pressure cutout diagnostic may need to be manually reset to clear the diagnostic and enable compressor operation for the fault circuit.

11

Image 11
Contents WSHP-IOP-2 1998, American Standard Company Installation, OperationLiterature History Table of Contents Zone Sensor Placement Start-up ProcedureInstallation of New Units Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagCommunication Unit OperationPosition Damper Actuator or Generic Binary Output PowerBinary Outputs Output Overrides Binary input configurationsBinary Input Description Configuratio Contact Closure Open Occupancy Condensate OverflowGeneric Binary Input High and Low Pressure SwitchesDescription Communicated Request Hardwired State Result Discharge Air Sensor Leaving Water Sensor Circuit 24 VAC ComprCompr Binary Outputs Analog InputsOccupied setpoints Fan Mode InputLocal Setpoint Filter Maintenance Timer Fan Off DelaySetpoint Operation Internal and External Setpoint AdjustmentZone Sensor Zone SensorCommunication Jack Zone Sensor Features Fan Switch OptionalZone Sensor Specifications Capacity Unit Between 100% 50% Heating or Cooling Control Mode OperationCompressor Minimum ON/OFF Timers Heating or Cooling OperationMorning Warm Up Single and Dual Compressor OperationMaster Controller Data SharingConfiguration Green Status LED TroubleshootingRed Service LED Yellow Service LEDPump Operation for Systems with ZN510 Loop Controller Manual Output Testing the HeatPump Configurations Testing the Heat Pump ConfigurationsWait time expires Questionable Unit OperationFan output does not energize Nicated informationOutdoor air damper stays open Compressors not runningOutdoor air damper stays closed Diagnostic Fan Other Outputs DiagnosticsZN510 controller diagnostics Rover Service Tool Translating Multiple DiagnosticsResetting Diagnostics Cycling PowerWiring Diagram Wiring Diagram Agency Listings Hardware SpecificationsSpecifications Board Dimensions Operating Environment 32 to 140 F 0 to 60 CBinary Output J1-5 12 VA VAC RMS typical J1-6 J1-7 Binary InputsDescription Terminals Function Binary Output J1-1 12 VA VAC RMS typical J1-2 J1-4