Trane Tracer Translating Multiple Diagnostics, Resetting Diagnostics, Cycling Power, Alarm Reset

Page 28

Diagnostics

Translating Multiple

Diagnostics

The controller senses and records each diagnostic independently of the diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur.

Resetting Diagnostics

1.Automatically by the controller.

2.By initiating a manual output test at the controller.

3.By cycling power to the controller.

4.Through a building automation system such as ZN510 Loop Controller.

5.Through Rover, Trane’s service tool.

6.Through any communicating device with the ability to access the controller’s alarm reset input.

Automatic Diagnostic Reset The ZN510 controller includes an automatic diagnostic reset function. This function attempts to automatically recover a unit when the following diagnostics occur:

zLow temperature detection, Circuit 1

zLow temperature detection, Circuit 2

zLow temperature detection, Circuit 1 and 2

zHigh/low pressure cutout, Circuit 1

zHigh/low pressure cutout, Circuit 2

zHigh/low pressure cutout, Circuit 1 and 2

When one or more of these special diagnostics occurs, the controller responds to the diagnostic as defined in the table 17 on page 27. After the controller detects the first special diagnostic (listed on page 27), the unit waits 30 minutes before invoking the automatic diagnostic reset function. The automatic diagnostic reset function clears all special diagnostics and attempts to restore the controller to normal operation. The controller resumes normal operation until another diagnostic occurs.

If a special diagnostic occurs within 24 hours after an automatic diagnostic reset, the diagnostic must be manually reset.

Cycling Power

When the 24 VAC power to the controller has been turned off, the unit cycles through a power up sequence. By default, the controller attempts to reset all diagnostics at power up. Diagnostics present at power up and those that occur after power up are handled according to the table on page 27.

Building Automation System (CLC)

Some building automation systems can reset diagnostics in the ZN510 controller. The ZN510 Loop Controller can reset diagnostics in the ZN510 Controller. For complete information, refer to the building automation system product literature.

Rover Service Tool

Trane’s service tool, Rover, can reset diagnostics in the ZN510 controller. For complete information about Rover, refer to the Rover product literature.

Alarm Reset

Any device that can communicate alarm reset information can reset diagnostics in the ZN510 controller.

ZN510 Controller Replacement

1.Disconnect power or disable the circuit breaker to unit.

2.Remove bad or questionable ZN510 Controller.

3.Install controller in the unit with the heatsink placement at the top of the control box. (See page 32).

4.Connect the power to the ZN510 ONLY. (TB1-1 & TB1-2 on ZN510)

5.Connect Rover and properly configure the controller, unless a previously configured board is purchased.

6.Power down.

7.Connect the remaining input and output wiring to the controller.

8.Reapply power.

9.Complete sequence 7 and 8 above in the installation section of this manual.

10.Refer to BAS manual for instructions on how to install the new ZN510 into BAS system.

28

Image 28
Contents WSHP-IOP-2 Literature History Installation, Operation1998, American Standard Company Table of Contents Installation of New Units Start-up ProcedureZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagUnit Operation CommunicationBinary Outputs PowerPosition Damper Actuator or Generic Binary Output Binary Input Description Configuratio Contact Closure Open Binary input configurationsOutput Overrides Condensate Overflow OccupancyDescription Communicated Request Hardwired State Result High and Low Pressure SwitchesGeneric Binary Input 24 VAC Compr Compr Binary OutputsAnalog Inputs Discharge Air Sensor Leaving Water Sensor CircuitLocal Setpoint Fan Mode InputOccupied setpoints Fan Off Delay Filter Maintenance TimerInternal and External Setpoint Adjustment Zone SensorZone Sensor Setpoint OperationZone Sensor Features Fan Switch Optional Communication JackZone Sensor Specifications Heating or Cooling Control Mode Operation Compressor Minimum ON/OFF TimersHeating or Cooling Operation Capacity Unit Between 100% 50%Single and Dual Compressor Operation Morning Warm UpData Sharing Master ControllerConfiguration Troubleshooting Red Service LEDYellow Service LED Green Status LEDManual Output Testing the Heat Pump ConfigurationsTesting the Heat Pump Configurations Pump Operation for Systems with ZN510 Loop ControllerQuestionable Unit Operation Fan output does not energizeNicated information Wait time expiresCompressors not running Outdoor air damper stays openOutdoor air damper stays closed ZN510 controller diagnostics DiagnosticsDiagnostic Fan Other Outputs Translating Multiple Diagnostics Resetting DiagnosticsCycling Power Rover Service ToolWiring Diagram Wiring Diagram Hardware Specifications Specifications Board DimensionsOperating Environment 32 to 140 F 0 to 60 C Agency ListingsBinary Inputs Description Terminals FunctionBinary Output J1-1 12 VA VAC RMS typical J1-2 J1-4 Binary Output J1-5 12 VA VAC RMS typical J1-6 J1-7