Trane Tracer manual Troubleshooting, Red Service LED, Green Status LED, Yellow Service LED

Page 22

Troubleshooting

Red Service LED

Table 9: Red LED activity

Red LED Activity

Description

LED off continuously when power is applied to the

Normal operation.

controller.

 

 

 

LED on continuously, even when power is applied to

Someone is pressing the service button or the controller has

the controller.

failed.

 

 

LED flashes once every second.

Use Rover, Trane’s service tool, to restore the unit to normal

operation or unconfigured.

 

 

 

!Warning! Service Button

The black Service button on the ZN510 board allows the user to send a service pin message, which allows efficient identification of the unit's location. However, if the Service button is held for more than 10 seconds, the ZN510 will shut down the software application and disable the unit's operation. The only method to restore the unit is through the use of Rover service tool. We strongly suggest that this function only be exercised under the strict direction of factory service personnel.

Green Status LED

The green LED normally indicates whether the controller is powered on (24 VAC).

Yellow Service LED

Table 11: Yellow LED activity

Table 10: Green LED activity

Green LED Activity

Description

 

 

LED on continuously.

Power on (normal operation).

 

 

LED blinks (one blink).

Manual output test mode (2-second hold), No

diagnostics present.

 

 

 

LED blinks (two blinks).

Manual output test mode (2-second hold),

One or more diagnostics are present.

 

 

 

 

“Wink” mode.

 

This feature allows the identification of a

 

controller. By sending a request from a device,

 

such as Rover, Trane’s service tool or ZN510

LED blinks (1/4 second on,

Loop Controller, a request to the controller

1/4 second off for 10 seconds.

can be made to “wink” a notification that the

 

controller received the signal. When the zone

 

sensor ON button is held for 10 seconds

 

“Wink” mode is sent from Comfort Link

 

Controller.

 

 

 

z Power off.

LED off.

z Abnormal condition.

 

z Test button is pressed.

 

 

Yellow LED Activity

Description

LED off continuously.

The controller is not detecting any communication.

(Normal for standalone applications).

 

 

 

LED blinks.

The controller detects communication. (normal for

communicating applications, including data sharing).

 

 

 

LED on continuously.

Abnormal condition.

 

 

22

Image 22
Contents WSHP-IOP-2 Literature History Installation, Operation1998, American Standard Company Table of Contents Installation of New Units Start-up ProcedureZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagUnit Operation CommunicationBinary Outputs PowerPosition Damper Actuator or Generic Binary Output Binary Input Description Configuratio Contact Closure Open Binary input configurationsOutput Overrides Condensate Overflow OccupancyDescription Communicated Request Hardwired State Result High and Low Pressure SwitchesGeneric Binary Input Analog Inputs 24 VAC ComprCompr Binary Outputs Discharge Air Sensor Leaving Water Sensor CircuitLocal Setpoint Fan Mode InputOccupied setpoints Fan Off Delay Filter Maintenance TimerZone Sensor Internal and External Setpoint AdjustmentZone Sensor Setpoint OperationZone Sensor Features Fan Switch Optional Communication JackZone Sensor Specifications Heating or Cooling Operation Heating or Cooling Control Mode OperationCompressor Minimum ON/OFF Timers Capacity Unit Between 100% 50%Single and Dual Compressor Operation Morning Warm UpData Sharing Master ControllerConfiguration Yellow Service LED TroubleshootingRed Service LED Green Status LEDTesting the Heat Pump Configurations Manual Output Testing the HeatPump Configurations Pump Operation for Systems with ZN510 Loop ControllerNicated information Questionable Unit OperationFan output does not energize Wait time expiresCompressors not running Outdoor air damper stays openOutdoor air damper stays closed ZN510 controller diagnostics DiagnosticsDiagnostic Fan Other Outputs Cycling Power Translating Multiple DiagnosticsResetting Diagnostics Rover Service ToolWiring Diagram Wiring Diagram Operating Environment 32 to 140 F 0 to 60 C Hardware SpecificationsSpecifications Board Dimensions Agency ListingsBinary Output J1-1 12 VA VAC RMS typical J1-2 J1-4 Binary InputsDescription Terminals Function Binary Output J1-5 12 VA VAC RMS typical J1-6 J1-7