Trane ZN510 Controller Diagnostics, ZN510 controller diagnostics, Diagnostic Fan Other Outputs

Page 27

Diagnostics

Table 17: ZN510 controller diagnostics

Diagnostic

Fan

Other Outputs

 

 

 

Condensate overflow

Off

Compressors: Off

Damper: Closed

 

 

 

 

 

 

 

Compressor 1: Off

Low temp detect - Crt 1

Enabled

Compressor 2: See note below.

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: See note below.

Low temp detect - Crt 1

Enabled

Compressor 2: Off

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: Off

Low temp detect - Crt 1 and 2

Off

Compressor 2: Off

 

 

Damper: Closed

 

 

 

 

 

Compressor 1: Off

High/low press cutout - Crt 1

Enabled

Compressor 2: See note below.

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: See note below.

High/low press cutout - Crt 2

Enabled

Compressor 2: Off

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: Off

High/low press cutout - Crt 1 and 2

Off

Compressor 2: Off

 

 

Damper: Closed

 

 

 

Space temperature failure*

Off

Compressor(s): Off

Damper: Closed

 

 

 

 

 

 

 

Compressor 1: Off

Leaving water temp failure

Enabled

Compressor 2: See note below.

Damper: See note below.

 

 

 

 

 

Discharge air temp failure*

Enabled

Compressor(s): No action

Damper: No Action

 

 

 

 

 

Maintenance required

Enabled

Compressor(s): No action

(example: Filter Status)

Damper: No Action

 

 

 

 

Local setpoint failure*

Enabled

Compressor(s): Enabled

Damper: Enabled

 

 

 

 

 

Local fan mode failure*

Enabled

Compressor(s): Enabled

Damper: Enabled

 

 

 

 

 

Invalid unit configuration

Disabled

Compressor(s): Disabled

Damper: Disabled

 

 

 

 

 

High/low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate each circuit and independently disable compressor operation. For single compressor units, these diagnostics cause the compressor to shut down, the unit fan to be controlled off, and the outdoor air damper to be closed (when present).

When BOP 6 is configured as a generic binary output, BOP 6’s state is unaffected by all unit diagnostics.

* Note: Non-latching diagnostics automatically reset when the input is present and valid.

27

Image 27
Contents WSHP-IOP-2 Installation, Operation Literature History1998, American Standard Company Table of Contents Start-up Procedure Installation of New UnitsZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagCommunication Unit OperationPower Binary OutputsPosition Damper Actuator or Generic Binary Output Binary input configurations Binary Input Description Configuratio Contact Closure OpenOutput Overrides Occupancy Condensate OverflowHigh and Low Pressure Switches Description Communicated Request Hardwired State ResultGeneric Binary Input Discharge Air Sensor Leaving Water Sensor Circuit 24 VAC ComprCompr Binary Outputs Analog InputsFan Mode Input Local SetpointOccupied setpoints Filter Maintenance Timer Fan Off DelaySetpoint Operation Internal and External Setpoint AdjustmentZone Sensor Zone SensorCommunication Jack Zone Sensor Features Fan Switch OptionalZone Sensor Specifications Capacity Unit Between 100% 50% Heating or Cooling Control Mode OperationCompressor Minimum ON/OFF Timers Heating or Cooling OperationMorning Warm Up Single and Dual Compressor OperationMaster Controller Data SharingConfiguration Green Status LED TroubleshootingRed Service LED Yellow Service LEDPump Operation for Systems with ZN510 Loop Controller Manual Output Testing the HeatPump Configurations Testing the Heat Pump ConfigurationsWait time expires Questionable Unit OperationFan output does not energize Nicated informationOutdoor air damper stays open Compressors not runningOutdoor air damper stays closed Diagnostics ZN510 controller diagnosticsDiagnostic Fan Other Outputs Rover Service Tool Translating Multiple DiagnosticsResetting Diagnostics Cycling PowerWiring Diagram Wiring Diagram Agency Listings Hardware SpecificationsSpecifications Board Dimensions Operating Environment 32 to 140 F 0 to 60 CBinary Output J1-5 12 VA VAC RMS typical J1-6 J1-7 Binary InputsDescription Terminals Function Binary Output J1-1 12 VA VAC RMS typical J1-2 J1-4