Trane Tracer manual Questionable Unit Operation, Fan output does not energize, Nicated information

Page 24

Troubleshooting

Questionable Unit

Operation

Table 13: Fan output does not energize

Probable Cause

Explanation

 

 

Random start observed.

After power up, the controller always observes a random start from 0 to 25

seconds. The controller remains off until the random start time expires.

 

 

 

 

When power up control wait is enabled (non-zero time), the controller remains

 

off until one of two conditions occurs:

Power up control wait.

z The controller exits power up control wait once it receives commu-

nicated information.

 

 

z The controller exits power up control wait once the power up control

 

wait time expires.

 

 

 

When configured to cycle with capacity, normally the unit fan cycles off with

Cycling fan operation.

heating or cooling. The heating/cooling sources cycle on or off periodically with

 

the unit fan to provide varying amounts of capacity to the space.

 

 

 

Even when the controller is configured for continuous fan operation, the fan

Unoccupied operation.

normally cycles with capacity during unoccupied mode. While unoccupied, the

fan cycles on or off with heating/cooling to provide varying amounts of heating

 

 

or cooling to the space.

 

 

Fan mode off.

When a local fan mode switch determines the fan operation, the off position

controls the unit fan off.

 

 

 

 

The desired operating mode (such as off, heat and cool) can be communicated to

Requested mode off.

the controller. When off is communicated to the controller, the unit controls the

 

fan off. There is no heating or cooling.

 

 

Diagnostic present.

A specific list of diagnostics affects fan operation. See Diagnostics section on

page 27.

 

 

 

 

If the controller does not have power, the unit fan does not operate. For the

No power to the controller.

ZN510 controller to operate normally, it must have an input voltage of 24 VAC.

When the green LED is off continuously, the controller does not have sufficient

 

 

power or has failed.

 

 

Unit configuration.

The controller must be properly configured based on the actual installed end

devices and application.

 

 

 

 

The controller includes a manual output test sequence that may be used to verify

Manual output test.

output operation and associated output wiring. However, based on the current

step in the test sequence, the unit fan may not be on. Refer to the manual output

 

 

overrides on page 9.

 

 

Unit wiring.

The wiring between the controller outputs and the fan relays and contacts must

be present and correct for normal fan operation.

 

 

 

24

Image 24
Contents WSHP-IOP-2 Installation, Operation Literature History1998, American Standard Company Table of Contents Start-up Procedure Installation of New UnitsZone Sensor Placement Power Up Sequence Power Up SequenceUnit Identification Tag Unit Identification TagUnit Operation CommunicationPower Binary OutputsPosition Damper Actuator or Generic Binary Output Binary input configurations Binary Input Description Configuratio Contact Closure OpenOutput Overrides Condensate Overflow OccupancyHigh and Low Pressure Switches Description Communicated Request Hardwired State ResultGeneric Binary Input 24 VAC Compr Compr Binary OutputsAnalog Inputs Discharge Air Sensor Leaving Water Sensor CircuitFan Mode Input Local SetpointOccupied setpoints Fan Off Delay Filter Maintenance TimerInternal and External Setpoint Adjustment Zone SensorZone Sensor Setpoint OperationZone Sensor Features Fan Switch Optional Communication JackZone Sensor Specifications Heating or Cooling Control Mode Operation Compressor Minimum ON/OFF TimersHeating or Cooling Operation Capacity Unit Between 100% 50%Single and Dual Compressor Operation Morning Warm UpData Sharing Master Controller Configuration Troubleshooting Red Service LEDYellow Service LED Green Status LEDManual Output Testing the Heat Pump ConfigurationsTesting the Heat Pump Configurations Pump Operation for Systems with ZN510 Loop ControllerQuestionable Unit Operation Fan output does not energizeNicated information Wait time expiresCompressors not running Outdoor air damper stays openOutdoor air damper stays closed Diagnostics ZN510 controller diagnosticsDiagnostic Fan Other Outputs Translating Multiple Diagnostics Resetting DiagnosticsCycling Power Rover Service ToolWiring Diagram Wiring Diagram Hardware Specifications Specifications Board DimensionsOperating Environment 32 to 140 F 0 to 60 C Agency ListingsBinary Inputs Description Terminals FunctionBinary Output J1-1 12 VA VAC RMS typical J1-2 J1-4 Binary Output J1-5 12 VA VAC RMS typical J1-6 J1-7