All installations and services must be performed by qualified service personnel.
D. CLOSET INSTALLATION
1.The return air opening into the closet is to have a minimum free area of 250
sq. in. (see Figure 5).
2. The return air opening may be
located in the top, center or (ideally) bottom of the closet door or side wall.
Figure 5.
: Do not obstruct any return air openings, including the return grille on the furnace. To do so may cause the furnace to activate the high limit and shut down.
3.The
4.The total free area of openings in the floor or ceiling registers serving the return duct system must be at least 350 square inches. At least one register must be located where it is not likely to be covered by carpeting, boxes, furniture or other objects.
5.Materials located in the return duct system must have a flame spread classification of 200 or less.
6.
7.Wiring materials located in the return duct system must conform to articles
8.Gas piping is not to be located in or through the return duct system .
14