HP R5500 manual Testing the LEDs, Available settings Parameter

Page 29

Available settings

Parameter

Associated LED

Explanation (when LED is illuminated)

 

 

 

 

 

230 Nom

Battery Fault

Nominal utility voltage level is set to 230

 

 

 

(red)

VAC (factory default for 326529-B31)

 

 

 

 

 

240 Nom

Site Wiring Fault

Nominal utility voltage level is set to 240

 

 

 

(red)

VAC

 

 

 

 

Wiring Fault Setting

Wiring Fault

Utility (green)

Audible alarm sounds when ground is

 

 

 

 

missing or line and neutral connections are

 

 

 

 

reversed

 

 

 

 

 

ERM Setting

0

ERMs

0% to 25% load

UPS is configured for no attached ERMs

 

 

 

(green)

(factory default)

 

 

 

 

 

 

1

ERM

26% to 50%

UPS is configured for 1 attached ERM

 

 

 

load (green)

 

 

 

 

 

 

 

2

ERMs

51% to 75%

UPS is configured for 2 attached ERMs

 

 

 

load (green)

 

 

 

 

 

 

To change the UPS configuration parameters:

1.Place the UPS in Configure mode (on page 28).

The LEDs associated with the currently configured parameters illuminate. A flashing green cursor indicates where you are in the configuration process as you scroll through the available settings.

2.To change the nominal voltage, press the On button to advance the cursor to the LED associated with the appropriate nominal voltage parameter. The selected voltage configuration LED flashes.

3.Press the Standby button to select the nominal voltage configuration. The LED associated with the old input voltage parameter turns off, and the LED associated with the new input voltage parameter illuminates solid green.

NOTE: Only one nominal utility voltage can be configured. When setting voltage configuration parameters, selecting an On value for any one parameter automatically sets the other possibilities to Off.

4.To enable the Wiring Fault parameter, press the On button to advance the cursor to the Utility LED, then press the Standby button. The LED illuminates solid green. This parameter is disabled by default, and should only be enabled for line-to-neutral connections. Enabling this feature for line-to-line power sources causes a false alarm.

5.To configure the UPS for the number of connected ERMs, press the On button to advance the cursor to the load LED associated with the number of ERMs attached to the UPS.

6.Press the Standby button to select the appropriate ERM configuration. The associated LED illuminates solid green.

7.To save the configuration settings and exit Configure mode, press the Test/Alarm Reset button.

NOTE: Configure mode times out after 2 minutes. If the Test/Alarm Reset button has not been pressed, any new selections are not saved.

Testing the LEDs

To test the LEDs, press and hold the Test/Alarm Reset button for 3 seconds.

UPS operations 29

Image 29
Contents Part Number 351643-004A September 2007 Fourth Edition HP UPS R5500 User GuideAudience assumptions Contents Ordering spares Verifying the Repo port connection Powering down the UPSPower management software Before you contact HP HP contact information UPS spare parts list Hardware optionsUPS R5500 overview Component identificationUPS front panel DescriptionUPS front panel controls Powers up the UPS Starting power toFront panel is shown with the bezel removed LED description UPS front panel LED indicatorsRepo port UPS rear panelERM rear panel Precautions InstallationPreparing to install the hardware Tools and materialsReadying the equipment Installing the mounting railsSelecting a site Installation Installation Tighten the hex nuts Installing the UPSPreparing the rails for integrated shipping Installation Removing the UPS battery bracket Installing the batteries Installation Installation Connecting the Repo port Connecting the ground bonding cable Ground bonding cable is not included Connecting the UPS to utility powerConnecting devices to the UPS Installation Starting power to the load Installing the ERMInstallation Installation Operate mode Standby modeUPS operations Modes of operationConfigure mode Configuring the UPSAuto-Bypass mode Explanation when LED is illuminatedAvailable settings Parameter Testing the LEDsVerifying the Repo port connection Silencing an audible alarmPowering down the UPS Power management software Power managementRemoving the UPS front bezel Removing the ERM front bezel MaintenanceReplacing the UPS electronics module Replacing the UPS option card Battery care and storage guidelines Important battery safety informationTo replace the component, reverse the removal procedure Replacing the batteriesUPS battery replacement procedure Replacing the ERM Replacing the UPSUpdating the UPS firmware LED and audible alarm troubleshooting TroubleshootingAlarm Be silenced 30?General alarm condition Battery conditionBypass is out of range Input voltage is not within ±12 percent of nominal voltageLow battery shutdowns Internal UPS fault conditionInput voltage is out of range Insufficient warning of low batteriesUPS does not provide the expected backup time Site wiring conditionOverload condition Repo conditionUPS is in Auto-Bypass mode UPS frequently switches between utility and battery powerUPS is on battery Utility power conditionUPS physical specifications SpecificationsERM physical specifications UPS input specificationsVoltage specifications Power protection specificationsUPS model Nominal power Rating W Voltage setting Configuration setting VAC Available nominal output voltageBattery runtime for NA/JPN model Battery specificationsBattery runtime for Intl model Output tolerance specificationsRepo port specifications Environmental specificationsSpares UPS spare parts listOrdering spares Description Spare part NumberHardware options HP contact information Technical supportBefore you contact HP Limited warranty Warranty information$250,000 Computer Load Protection Guarantee Pre-Failure Battery WarrantyFederal Communications Commission notice Regulatory compliance noticesRegulatory compliance identification numbers Cables ModificationsEuropean Union regulatory notice Canadian notice Avis CanadienJapanese notice Bsmi notice Battery replacement notice Power cord statement for Japan Taiwan battery recycling noticeGrounding methods to prevent electrostatic discharge Electrostatic dischargePreventing electrostatic discharge Acronyms and abbreviations Index Communications port, connectingInstallation instructions Repo port, connecting