5-3 Alarms
Use the Alarm History screen to monitor system alarms. From the Main Menu screen, press the Alarms button to access the Alarm History screen. The three most recent alarms appear at the top of the Alarm History screen. Use the DOWN and UP buttons to scroll through the alarms.
(Alarm History Screen)
5-4 Alarm Descriptions
Alarm | Alarm | Alarm | |
Comment | Description | Effect | |
VALVE | The Main Air Valve did not maintain | Immediate | |
position. | |||
POSITION | Shut Down | ||
Possible Motor or Limit Switch Failure. | |||
|
| ||
VALVE | The Main Air Valve did not find | Immediate | |
MTR | position. | ||
Shut Down | |||
OVERRIDE | Possible Motor or Limit Switch Failure. | ||
| |||
VALVE | The Main Air Valves expected and actual | Immediate | |
MOTOR FAIL | positions do not match. | Shut Down | |
Possible Motor or Limit Switch Failure. | |||
|
| ||
PROCESS | The process supply air temperature | Process | |
thermocouple is out of range. | |||
SENSOR FAIL | Shut Down | ||
Possible thermocouple failure. | |||
|
| ||
REGEN | The regeneration air temperature | Regeneration | |
thermocouple is out of range. | |||
SENSOR FAIL | Shut Down | ||
Possible thermocouple failure. | |||
|
| ||
PROCESS | Process air temperature deviation is | Process | |
above high limit value. | |||
HIGH TEMP | Shut Down | ||
Possible solid state relay failure. | |||
|
| ||
PROCESS | Process air temperature deviation is |
| |
below low limit value. | Alert Only | ||
LOW TEMP | |||
Possible heater failure. |
| ||
|
| ||
| Process air temperature control loop is |
| |
PROCESS | unable to maintain the process air | Process | |
temperature set point. | |||
LOOP BREAK | Shut Down | ||
Possible Missing thermocouple, Failed | |||
|
| ||
| heater, Failed solid state relay. |
| |
REGEN | Regeneration air temperature deviation is | Regeneration | |
HIGH TEMP | above high limit value. | Shut Down |