Thermo Products CDX3-100N, CDX3-75N, CHX3-75N, CHX3-125N, CDX3-125N, CHX3-100N operation manual

Page 5
: The CHX3/CDX3 furnace models are sealed combustion design, which does not require an air shutter adjustment (air shutters are not used) for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace.

All installations and services must be performed by qualified service personnel.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background: The CHX3/CDX3 furnace models are sealed combustion design, which does not require an air shutter adjustment (air shutters are not used) for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background: Personal injury or property damage could result from repair or service of this furnace by anyone other than a qualified heating contractor. Only the homeowner/user routine maintenance described in the Users Information Manual may be performed by the user.

iv

Image 5
Contents TWO STAGE CONDENSING GAS FURNACE MODELSOR LP GAS PROPANE CDX3-75N CDX3-100N CDX3-125N I. SAFETY INFORMATION This and the previous page contain reproductions of the various warning and instruction labels placed on the Thermo Pride Two Stage Condensing Gas Furnaces. Please read and comply with the contents of these labels 1.A windows be opened The CHX3/CDX3 furnace models are sealed combustion design, which does not require an air shutter adjustment air shutters are not used for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace BEGINNING PAGE INDEXSECTION II. FURNACE SPECIFICATIONS CHX3 SERIES CDX3 SERIES INSTALLATION PARTS PACKAGES - CHX3-75 INSTALLATION PARTS PACKAGES - CDX3-75 Grounding instructions III. GENERAL INSTALLATION B1. CDX3 HORIZONTAL APPLICATION B. FURNACE LOCATIONPage PVC Pipe Designation Maximum Quantity of Elbows Outside Combustion Air Intake RH view E.Direct Venting Through a Sidewallc.The vent terminal shall not be located Page E1. Single-PipeSidewall Venting Option 5.Optional Direct Vent Terminations Install these optional kits according to the instructions provided with each kit. The location and clearance requirements are identical to those of the standard vent terminations described in this manual 1.Figures 6B, 7, and 8 follow depicting typical exhaust vent and air intake connections for the furnace model series CHX3 and the CDX3, respectively, as well as a list of required parts to correctly install each system Page Applications Furnace Model Series CHX3 Figure 9 Typical Internal VentPiping Arrangement for the 3. Connecting The Combustion Air Intake Piping Figure 14. TRAP ASSEMBLY MOUNTED ON CHX3 I.CONDENSATE DRAIN LINE AND TRAP ASSEMBLYFigure 15. TRAP ASSEMBLY MOUNTED ON CDX3 2.Determine on which side of furnace the condensate disposal line is to be run NOTICE On CHX3/CDX3’s this must be the same side as the flue outlet or bottom of unit. Attach the condensate trap to the furnace casing using the #8x3/4” sheet metal screws provided in the parts package. Pilot holes are provided on both sides of the casing for mounting J. GENERAL GAS PIPING J1. REQUIREMENTS AND SIZING OF DUCT WORK Figure 18A TABLE 2A 2. CDX3 MODELS COUNTERFLOWS K. FILTERS 1. CHX3 MODELS HIGHBOYSPage L. WIRING Table 4A Switch Settings S7 DIP SwitchOptions Time2-StageBlower Settings from factory Table 4C IV. STARTING THE UNIT A. SEQUENCE OF OPERATIONS IF NOT IF THERMOSTAT W2 CONTACTS ARE CLOSED OTHERWISE OPERATING INSTRUCTIONS B. INITIAL START UPObserve the following precautions when measuring C. Measuring And Adjusting Heat Input RateA.Burner manifold pressure with a pressure gauge B.Gas flowrate by clocking gas meterNOTICE A U-tubemanometer, measuring pressure in inches of water column, is recommended for all gas pressure measurements. However, an aneroid pressure gauge, in good working condition, capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated within the last year, is a satisfactory alternate. These two 2 devices will be considered as equivalent and interchangeable. Either device is referred to below as a “pressure gauge” Heat input rate in BTUH = Page Checking The Burner Flame 21.Go to Checkout Procedure belowCheckout Procedure TABLE 6 - CONVERTING GAS FLOW RATE V. INSTALLERS INSTRUCTIONS TO USER D. FURNACE CHECKOUT PROCEDUREFigure VI. TROUBLESHOOTING Power must be disconnected before servicing DIAGNOSTIC FEATURESTROUBLESHOOTING GUIDE IS INDUCER RUNNING ON LOW SPEED? YES DOES THE HOT DO BURNERS STAY LIT PAST PROOF OF FLAME CHECK? REPLACE THE 50V51-843CONTROL DOESBURNERSHUT OFF Appendix -AReplacement Parts List Page Page Page Appendix - B Wiring Diagrams