Thermo Products CHX3-75N, CDX3-75N, CHX3-125N IF THERMOSTAT W2 CONTACTS ARE CLOSED OTHERWISE

Page 43
IF THERMOSTAT

All installations and services must be performed by qualified service personnel.

IF THERMOSTAT

W2 CONTACTS

ARE CLOSED

OTHERWISE

AFTER DELAY-TO-FAN-ON PERIOD ENDS (45 SECONDS), CIRCULATING AIR FAN IS ENERGIZED AT LOW FIRE HEATING SPEED OR HIGH FIRE IF W2 IS ENERGIZED. THE (OPTIONAL) ELECTRONIC AIR CLEANER AND HUMIDIFIER

ARE ENERGIZED.

IF SYSTEM IS IN LOCKOUT,

THE MODULE WILL RESET

ITSELF AFTER 60 MINUTES

OR MAY BE MANUALLY

RESET BY INTERRUPTING

THE POWER TO THE FURNACE

AT THE DISCONNECT OR

INTERRUPTING THE CALL FOR

HEAT AT THE THERMOSTAT.

IF THIS DOES NOT RESTART

THE SYSTEM, REFER TO THE

TROUBLESHOOTING SECTION

OF THIS MANUAL.

 

 

 

THERMOSTAT CLOSES W2

 

 

 

CALLING FOR HIGH FIRE

CALL

 

 

HEATING.

FOR

 

 

 

 

HIGH

 

 

 

FIRE

 

 

 

 

 

 

 

 

NO CALL

FOR

HIGH FIRE

WHEN THERMOSTAT W1 IS SATISFIED, CONTACTS OPEN AND THE GAS VALVE IS DE-ENERGIZED. AFTER PROOF OF FLAME LOSS, INDUCER STARTS 5 SECOND POST PURGE

AND (OPTIONAL) HUMIDIFIER IS DE-ENERGIZED. THE DELAY-TO- FAN-OFF PERIOD BEGINS (120 SECONDS)

AFTER THE DELAY-TO-FAN-OFF PERIOD ENDS, THE CIRCULATING AIR FAN AND (OPTIONAL) ELECTRONIC AIR CLEANER ARE DE-ENERGIZED.

GAS VALVE, INDUCER AND AIR FAN ARE ENERGIZED TO HIGH FIRE SETTINGS

WHEN THERMOSTAT HAS SATISFIED W2, CONTACTS OPEN AND THE GAS VALVE AND AIR FAN HIGH FIRE SETTINGS ARE DE-ENERGIZED AFTER 30 SECOND DELAY.

37

Image 43
Contents OR LP GAS PROPANE CDX3-75N CDX3-100N CDX3-125N MODELSTWO STAGE CONDENSING GAS FURNACE I. SAFETY INFORMATION This and the previous page contain reproductions of the various warning and instruction labels placed on the Thermo Pride Two Stage Condensing Gas Furnaces. Please read and comply with the contents of these labels 1.A windows be opened The CHX3/CDX3 furnace models are sealed combustion design, which does not require an air shutter adjustment air shutters are not used for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace SECTION INDEXBEGINNING PAGE II. FURNACE SPECIFICATIONS CHX3 SERIES CDX3 SERIES INSTALLATION PARTS PACKAGES - CHX3-75 INSTALLATION PARTS PACKAGES - CDX3-75 Grounding instructions III. GENERAL INSTALLATION B1. CDX3 HORIZONTAL APPLICATION B. FURNACE LOCATIONPage PVC Pipe Designation Maximum Quantity of Elbows Outside Combustion Air Intake RH view E.Direct Venting Through a Sidewallc.The vent terminal shall not be located Page E1. Single-PipeSidewall Venting Option 5.Optional Direct Vent Terminations Install these optional kits according to the instructions provided with each kit. The location and clearance requirements are identical to those of the standard vent terminations described in this manual 1.Figures 6B, 7, and 8 follow depicting typical exhaust vent and air intake connections for the furnace model series CHX3 and the CDX3, respectively, as well as a list of required parts to correctly install each system Page Applications Piping Arrangement for the Figure 9 Typical Internal VentFurnace Model Series CHX3 3. Connecting The Combustion Air Intake Piping Figure 14. TRAP ASSEMBLY MOUNTED ON CHX3 I.CONDENSATE DRAIN LINE AND TRAP ASSEMBLYFigure 15. TRAP ASSEMBLY MOUNTED ON CDX3 2.Determine on which side of furnace the condensate disposal line is to be run NOTICE On CHX3/CDX3’s this must be the same side as the flue outlet or bottom of unit. Attach the condensate trap to the furnace casing using the #8x3/4” sheet metal screws provided in the parts package. Pilot holes are provided on both sides of the casing for mounting J. GENERAL GAS PIPING J1. REQUIREMENTS AND SIZING OF DUCT WORK Figure 18A TABLE 2A 2. CDX3 MODELS COUNTERFLOWS K. FILTERS 1. CHX3 MODELS HIGHBOYSPage L. WIRING Table 4A Time S7 DIP SwitchSwitch Settings Options2-StageBlower Settings from factory Table 4C IV. STARTING THE UNIT A. SEQUENCE OF OPERATIONS IF NOT IF THERMOSTAT W2 CONTACTS ARE CLOSED OTHERWISE OPERATING INSTRUCTIONS B. INITIAL START UPB.Gas flowrate by clocking gas meter C. Measuring And Adjusting Heat Input RateObserve the following precautions when measuring A.Burner manifold pressure with a pressure gaugeNOTICE A U-tubemanometer, measuring pressure in inches of water column, is recommended for all gas pressure measurements. However, an aneroid pressure gauge, in good working condition, capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated within the last year, is a satisfactory alternate. These two 2 devices will be considered as equivalent and interchangeable. Either device is referred to below as a “pressure gauge” Heat input rate in BTUH = Page Checking The Burner Flame 21.Go to Checkout Procedure belowCheckout Procedure TABLE 6 - CONVERTING GAS FLOW RATE V. INSTALLERS INSTRUCTIONS TO USER D. FURNACE CHECKOUT PROCEDUREFigure VI. TROUBLESHOOTING Power must be disconnected before servicing DIAGNOSTIC FEATURESTROUBLESHOOTING GUIDE IS INDUCER RUNNING ON LOW SPEED? YES DOES THE HOT DO BURNERS STAY LIT PAST PROOF OF FLAME CHECK? REPLACE THE 50V51-843CONTROL DOESBURNERSHUT OFF Appendix -AReplacement Parts List Page Page Page Appendix - B Wiring Diagrams