Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit: N•m)

 

 

Outer dia. of copper pipe

Tightening torque

 

 

12.7 mm (dia.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

uTightening torque of flare pipe connections

Pressure of R410A is higher than that of R22. (Approx. 1.6 times)

Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers.

Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union

Flare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

nGas side refrigerant pipe connection

Turn up the pipe heat insulator to the unit side.

Wrap the pipe with wet cloth.

Turn up pipe heat insulator

Wet cloth

Remove the all brazed part.

Remove the cup on the gas side piping by using a brazing machine.

CAUTION

Do not burn the pipe heat insulator.

Remove the cap.

Attached joint part

Connection pipe Locally procured Ø28.6 mm

Braze the attached joint part to the gas side piping and braze the connection piping to the joint part.

Brazing

Braze all around

Brazing

Turn back the pipe heat insulator and tie up with a banding band.

Tie up with a banding band.

Piping with outdoor unit

For details of installation, refer to the Installation Manual of the outdoor unit.

nEvacuation

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for evacuation.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor unit.

Be sure to use a scale to charge the refrigerant of specified amount.

REQUIREMENT

Charging an excessive or too little amount of refrigerant causes a trouble of the compressor.

Be sure to charge the refrigerant of specified amount.

A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit.

It is necessary to fix the compressor and refrigeration cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully.

A 4mm-hexagonal wrench is required for opening the valve.

For details, refer to the Installation Manual attached to the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

Heat insulation process

Apply heat insulation for the pipes separately at liquid side and gas side.

For the heat insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 120°C or higher.

Using the attached heat insulation material, apply the heat insulation to the pipe connecting section of the indoor unit securely without gap.

REQUIREMENT

Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe.

(The pipe exposed to the outside causes water leak.)

Wrap heat insulator with its slits facing up (ceiling side).

Indoor unit

Union

 

Heat insulator

Heat insulation

Flare nut of the pipe

(Accessory)

 

– 23

 

– 24 –

Image 93
Contents Split Type Contents Original instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Model Sound power level dB Weight kg Cooling Heating SpecificationsExplanations given to user RelocationPipe Materials Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsR410A Conventional air Used tool UsageModel Indoor unit Concealed Duct High static pressure TypeRAV-SM2242DT-TR RAV-SM2802DT-TR Concealed Duct High static pressure Type ContinedSM2242DT-E Indoor UnitIndoor unit Dimension tableUnit Indoor100 RAV-SM2242 type350 300 250 200 150 100 3200 3360 RAV-SM2802 typeLow static pressure F1 Wire connection change of fan motorStandard Middle static pressure F2 High static pressure F3Parts name Type Specifications Specifications of Electrical PartsConnection of Wired Simple Remote Controller Indoor Controller Block DiagramIndoor unit #1 Header Outdoor unitOutline of specifications Remarks Control outlineOutside temp Correction value a Indoor formation Setup dataTa ˚C Cooling +1.5 Tc, Tcj TcnConditions Tc n Control temp. C Setup at shipmentHeat Case of wired remote controllerUsual control MCC-1403 Print Circuit BoardFunction Connector Pin Specifications Remarks Optional Connector Specifications of Indoor P.C. BoardBefore troubleshooting Troubleshooting procedureWired remote controller type Confirmation of error log Main remote controller RBC-AMT32EHow to read check monitor display ProcedureRemote controller switch monitoring function Check Code List Indoor Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Operation of diagnostic function Judgment and measuresCause of operation Status Error mode detected by outdoor unit AfterSeries H03 Current detection circuit error Stop Power supply error of remote controller, Indoor YES E09 errorE10 error E04 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P01 error P10 errorP19 error F01 error F02 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit Temperature sensor TA, TC, TCJ Temperature Resistance value characteristic tableTA, TC, TCJ sensors Representative valueResistance value Part name Checking procedureReplacement procedures Replacement of Service P.C. BoardSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom StepOperation is available again Indoor unit capacity Code No Type Code NoPractical operation Test Run Setup on Remote Controller Wired remote controllerLED Display on Indoor P.C. Board D002 Red Function Selection SetupD203 Red TEMP. buttons, specify the Code No. DNFunction selection item No. DN list ContentsSetup method Wired remote controllerHow to set wired remote controller as sub remote controller When connected 2 remote controllers operate an indoor unitContents Group control operation Calling of error historyPushing Test button returns the display to usual display System examplePower on Indoor unit power-ON sequenceModel connection interface wiring connection Microprocessor block diagramModel Connection Interface Function Model name TCB-PCNT30TLE2C. board switch SW01 setup Wiring specificationsAddress setup External view of P.C. board assemblyPush Test + Vent buttons for 4 seconds or more Push Test buttonDuring unset time, At shipment from factory is displayed Code No Data at shipment Setup data range Address Setup & Group Control Terminology System ConfigurationOnly turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringUsing timer time Buttons, set the line address Using the temperature setup ButtonsPush SET Button. OK when display goes on Push Test PushProcedure Confirmation of indoor unit No. positionTo know the position of indoor unit body by address Contents Precautions for Safety Examples of indication on the carton Symbol DescriptionConcealed Duct High Static Pressure Relocation Other cautions DescriptionWired Remote Controller Part NamesDisplay section Operation section Preparation Correct UsageStart StopPower Saving Mode Timer OperationPush button during operation SetAdvanced Settings Power saving modeEnergy Saving Recommendations Cleaning air filters MaintenanceMaintenance List Preparing for long Shut Down PeriodDo not install the air conditioner in the following places InstallationAIR Conditioner Operations and Performance Be careful with noise or vibrationsSpecifications TroubleshootingInstallation Manual Work undertaken Protective gear worn Definition of Protective GearElectrical wiring Selection of installation locationGeneral Refrigerant pipingAccessory Parts New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Installation under high-humidity atmosphere Selection of Installation PlaceInstallation space Unit mm Filter cleaning sign term settingInstallation of hanging bolt External DimensionsInstallation of indoor unit Installation of hanging boltDuct installation example First floor Diagrams for making connecting flangesDuct design Air outlet port flangeFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Drain Piping Work Wire connection change of fan motorLow static pressure F1 Standard Middle static pressure F2Pipe material, size and insulator Connecting drain pipeDrain up Check the drainingHeat insulating process Refrigerant Piping and EvacuatingRefrigerant Piping Liquid side refrigerant pipe connectionEvacuation Gas side refrigerant pipe connectionWiring diagram Wire connectionPower and Wiring Specification Electrical ConnectionChanging of setting applicable control Remote Controller WiringWiring diagram Applicable ControlsFilter sign setting Remote controller switch monitoring functionConcealed Duct High Static Pressure Procedure To secure better effect of heatingManual address setup procedure Procedure exampleInstallation Manual Procedure Group control8C Operation ProcedureTest RUN Daily maintenanceBefore test run Execute a test runConfirmation of error log Concealed Duct High Static PressureInstallation ManualConfirmation and check Status Error codes and parts to be checkedHow to replace the parts Fan assembly and replacement Part name Work procedure RemarksFan assembly Fan/Fan case Pull out the fan assembly a fan toward you104 Fan motor 2242DT-E Location Description215, 216 219 218 214218 213 108 Check of Concentration Limit Toshiba Carrier Corporation
Related manuals
Manual 41 pages 43.38 Kb

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.