Toshiba RAV-SM2802DT-E Remote controller switch monitoring function, Filter sign setting

Page 96

Concealed Duct High Static Pressure

Procedure 6

When settings have been completed, push button to determine the settings.

When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote controller is accepted.)

Installation Manual

nPower saving mode

1.Push button for at least four seconds when the air conditioner is not working.

flashes.

Indicates CODE No. “C2.”

2. Select an indoor unit to be set by pushing (left side of the button).

Each time you push the button, unit numbers change as follows:

Concealed Duct High Static Pressure

Installation Manual

nRemote controller switch monitoring function

This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.

nFilter sign setting

According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

( 1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [01].

For the [SET DATA] in Procedure 4, select the SET DATA of filter sign term from the following table.

 

SET DATA

Filter sign term

 

 

 

 

0000

None

 

 

 

0001

150H

96

0002

2500H (Factory default)

 

 

0003

5000H

 

 

0004

10000H

 

UNIT No.

 

UNIT No.

 

UNIT No.

1-1

 

1-2

 

1-3

UNIT No.

1-4

The fan of the selected unit runs.

3.Adjust the power save setting by pushing

TIME / buttons.

Each push of the button changes the power level by 1% within the range from 100% to 50%.

The factory default is 75%.

2

4

1 3

1.Push and buttons simultaneously for at least 4 seconds to call the service monitor mode. The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No. ￿￿ is also displayed.

2.Pushing TEMP. / buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)

3.Pushing (left side of the button), select an indoor unit to be monitored.

The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.

4.Push button to return to the normal display.

n To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised.

Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

( 1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [06].

For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.

SET DATA

Detection temperature shift value

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C (Factory default)

0003

+3°C

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

Setting of power level in power saving mode

4.Determine the setting by pushing button.

5.Push button to complete the setting.

 

Indoor unit data

 

 

CODE No.

Data name

 

 

01

Room temperature (remote controller)

 

 

02

Indoor unit intake air temperature (TA)

 

 

03

Indoor unit heat exchanger (coil)

temperature (TCJ)

 

 

 

04

Indoor unit heat exchanger (coil)

temperature (TC)

 

 

 

F3

Indoor unit fan cumulative operating hours

(× 1 h)

 

 

 

 

Outdoor unit data

 

 

CODE No.

Data name

 

 

60

Outdoor unit heat exchanger (coil)

temperature (TE)

 

 

 

61

Outside air temperature (TO)

 

 

62

Compressor discharge temperature (TD)

 

 

63

Compressor suction temperature (TS)

 

 

64

 

 

65

Heatsink temperature (THS)

 

 

6A

Operating current (× 1/10)

 

 

F1

Compressor cumulative operating hours

(× 100)

 

 

 

– 29 –

– 30 –

Image 96
Contents Split Type Contents Original instruction Explanation of indications Explanation of illustrated marksWork undertaken Protective gear worn Indication ExplanationConfirmation of warning label on the main unit DescriptionPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Specifications Model Sound power level dB Weight kg Cooling HeatingExplanations given to user RelocationSafety Caution Concerned to New Refrigerant Pipe MaterialsCopper pipe Piping Flare nutTools General tools Conventional tools can be usedR410A Conventional air Used tool UsageConcealed Duct High static pressure Type Model Indoor unitConcealed Duct High static pressure Type Contined RAV-SM2242DT-TR RAV-SM2802DT-TRIndoor Unit SM2242DT-EDimension table Indoor unitIndoor UnitRAV-SM2242 type 100RAV-SM2802 type 350 300 250 200 150 100 3200 3360Wire connection change of fan motor Low static pressure F1Standard Middle static pressure F2 High static pressure F3Specifications of Electrical Parts Parts name Type SpecificationsIndoor Controller Block Diagram Connection of Wired Simple Remote ControllerIndoor unit #1 Header Outdoor unitOutline of specifications Remarks Control outlineOutside temp Correction value a Setup data Indoor formationTa ˚C Cooling +1.5 Tc, Tcj TcnConditions Tc n Setup at shipment Control temp. CCase of wired remote controller HeatUsual control Print Circuit Board MCC-1403Optional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksBefore troubleshooting Troubleshooting procedureWired remote controller type Main remote controller RBC-AMT32E Confirmation of error logHow to read check monitor display ProcedureRemote controller switch monitoring function Check Code List Indoor Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Operation of diagnostic function Judgment and measuresCause of operation Status Error mode detected by outdoor unit AfterSeries H03 Current detection circuit error Stop Power supply error of remote controller, Indoor E09 error YESE04 error E10 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P10 error P01 errorP19 error F02 error F01 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit Temperature Resistance value characteristic table Temperature sensor TA, TC, TCJTA, TC, TCJ sensors Representative valuePart name Checking procedure Resistance valueReplacement of Service P.C. Board Replacement proceduresSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom StepOperation is available again Type Code No Indoor unit capacity Code NoTest Run Setup on Remote Controller Wired remote controller Practical operationFunction Selection Setup LED Display on Indoor P.C. Board D002 RedD203 Red TEMP. buttons, specify the Code No. DNContents Function selection item No. DN listWired remote controller Setup methodHow to set wired remote controller as sub remote controller When connected 2 remote controllers operate an indoor unitContents Calling of error history Group control operationPushing Test button returns the display to usual display System exampleIndoor unit power-ON sequence Power onMicroprocessor block diagram Model connection interface wiring connectionModel Connection Interface Function Model name TCB-PCNT30TLE2Wiring specifications C. board switch SW01 setupExternal view of P.C. board assembly Address setupPush Test + Vent buttons for 4 seconds or more Push Test buttonDuring unset time, At shipment from factory is displayed Code No Data at shipment Setup data range System Configuration Address Setup & Group Control TerminologyAutomatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionUsing the temperature setup Buttons Using timer time Buttons, set the line addressPush SET Button. OK when display goes on Push Test PushProcedure Confirmation of indoor unit No. positionTo know the position of indoor unit body by address Contents Precautions for Safety Symbol Description Examples of indication on the cartonConcealed Duct High Static Pressure Relocation Other cautions DescriptionWired Remote Controller Part NamesDisplay section Operation section Correct Usage PreparationStart StopTimer Operation Power Saving ModePush button during operation SetAdvanced Settings Power saving modeEnergy Saving Recommendations Maintenance Cleaning air filtersMaintenance List Preparing for long Shut Down PeriodInstallation Do not install the air conditioner in the following placesAIR Conditioner Operations and Performance Be careful with noise or vibrationsTroubleshooting SpecificationsInstallation Manual Definition of Protective Gear Work undertaken Protective gear wornSelection of installation location Electrical wiringGeneral Refrigerant pipingAccessory Parts New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Selection of Installation Place Installation under high-humidity atmosphereInstallation space Unit mm Filter cleaning sign term settingExternal Dimensions Installation of hanging boltInstallation of indoor unit Installation of hanging boltDiagrams for making connecting flanges Duct installation example First floorDuct design Air outlet port flangeFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Wire connection change of fan motor Drain Piping WorkLow static pressure F1 Standard Middle static pressure F2Connecting drain pipe Pipe material, size and insulatorDrain up Check the drainingRefrigerant Piping and Evacuating Heat insulating processRefrigerant Piping Liquid side refrigerant pipe connectionGas side refrigerant pipe connection EvacuationWire connection Wiring diagramPower and Wiring Specification Electrical ConnectionRemote Controller Wiring Changing of setting applicable controlWiring diagram Applicable ControlsRemote controller switch monitoring function Filter sign settingConcealed Duct High Static Pressure Procedure To secure better effect of heatingProcedure example Manual address setup procedureInstallation Manual Procedure Group controlProcedure 8C OperationDaily maintenance Test RUNBefore test run Execute a test runConfirmation of error log Concealed Duct High Static PressureInstallation ManualConfirmation and check Error codes and parts to be checked StatusHow to replace the parts Fan assembly and replacement Part name Work procedure RemarksFan assembly Pull out the fan assembly a fan toward you Fan/Fan case104 Fan motor Location Description 2242DT-E215, 216 219 218 214218 213 108 Check of Concentration Limit Toshiba Carrier Corporation
Related manuals
Manual 41 pages 43.38 Kb

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.