Toshiba RAV-SM2802DT-E, RAV-SM2242DT-TR Drain Piping Work, Wire connection change of fan motor

Page 90

Concealed Duct High Static Pressure

Installation Manual

nWire connection change of fan motor

This duct is composed of 3 fan motors.

To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number (F1, F2 or F3) terminal.

The wires of the fan motor has been connected to (F2) [External static pressure 137Pa (14mmAq)] as factory default.

Low static pressure (F1)

FM

 

 

 

FM

 

 

 

FM

 

 

 

YEL : Yellow

 

 

 

 

 

 

 

 

 

BLU : Blue

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor

YEL

BLU

ORG

Fan motor

YEL

BLU

ORG

Fan motor

YEL

BLU

ORG

ORG : Orange

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

 

ORG

 

FAN3

ORG

 

FAN2

ORG

 

FAN1

 

Standard (Middle) static pressure (F2)

Fan tap changing terminal block

Concealed Duct High Static Pressure

Installation Manual

6 DRAIN PIPING WORK

CAUTION

Following the Installation Manual, perform the drain piping work that water is properly drained, and apply a heat insulation not to cause a dew condensation.

Inappropriate piping work may cause the water leakage in the room and wet of furniture.

REQUIREMENT

The drain piping flows the natural drainage. Make sure to set the drain piping from the unit with descending slope of 1/50 to 1/100 and do not make up-down or trap in the midway.

Set the horizontal pulling of the drain pipe to 20m or less. When drain piping is too long, attach the support bracket at intervals of 1.5m to 2m to avoid the pipe becomes undulant as shown in figure below.

<Example for installation of the main piping (Incl. piping support)>

1.5 to 2 m

As long as possible

– 90 –

FM

Fan motor

YEL

 

BLU

ORG

FM

 

 

Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN3

 

 

 

 

 

 

YEL

 

BLU

ORG

FM

 

 

Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN2

 

 

 

 

 

 

YEL

 

BLU

ORG

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN1

 

 

 

 

 

 

Electrical control box

Control

P.C. board

4P terminal block

3P terminal block

2P terminal block

Up-down bend

Descending slop of

Descending slop of

VP-30

Trap

1/50 to 1/100

1/50 to 1/100

 

 

High static pressure (F3)

FM

YEL

BLU

ORG

FM

YEL BLU

ORG

FM

YEL

BLU

ORG

 

Fan motor

Fan motor

Fan motor

 

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

 

 

ORG

FAN3

ORG

FAN2

 

ORG

FAN1

 

 

 

 

 

 

 

 

Terminal block No.

 

Fan motor wiring

External static pressure Pa (mmAq)

Remarks

 

F1

 

 

 

Yellow

 

 

 

69 (7)

 

 

 

 

Low static pressure

 

 

 

 

 

 

 

 

 

 

 

 

F2

 

 

 

Blue

 

 

 

137 (14)

Factory default

 

 

 

Middle static pressure

 

 

 

 

 

 

 

 

 

 

 

F3

 

 

 

Orange

 

 

 

196 (20)

 

 

 

 

High static pressure

 

 

 

 

 

 

 

 

 

 

 

Do not use F4.

NOTE

When the external static pressure is changed, write down the static pressure once change in the wiring diagram of the indoor unit is made.

Be sure to connect the drain pipe to the air conditioner with adhesive to avoid water leakage from the joint portion.

Condensation may occur on the drain pipes including collective pipes.

All drain pipes must be wrapped with heat insulator to prevent dew condensation.

Especially a part where drain pipe is connected to the indoor unit must be firmly insulated with the provided heat insulator.

– 17 –

– 18 –

Image 90
Contents Split Type Contents Original instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit DescriptionPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Explanations given to user SpecificationsModel Sound power level dB Weight kg Cooling Heating RelocationCopper pipe Piping Safety Caution Concerned to New RefrigerantPipe Materials Flare nutR410A Conventional air ToolsGeneral tools Conventional tools can be used Used tool UsageConcealed Duct High static pressure Type Model Indoor unitConcealed Duct High static pressure Type Contined RAV-SM2242DT-TR RAV-SM2802DT-TRIndoor Unit SM2242DT-EDimension table Indoor unitIndoor UnitRAV-SM2242 type 100RAV-SM2802 type 350 300 250 200 150 100 3200 3360Standard Middle static pressure F2 Wire connection change of fan motorLow static pressure F1 High static pressure F3Specifications of Electrical Parts Parts name Type SpecificationsIndoor unit #1 Header Indoor Controller Block DiagramConnection of Wired Simple Remote Controller Outdoor unitOutline of specifications Remarks Control outlineOutside temp Correction value a Setup data Indoor formationTa ˚C Cooling +1.5 Tc, Tcj TcnConditions Tc n Setup at shipment Control temp. CCase of wired remote controller HeatUsual control Print Circuit Board MCC-1403Optional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksBefore troubleshooting Troubleshooting procedureWired remote controller type How to read check monitor display Main remote controller RBC-AMT32EConfirmation of error log ProcedureRemote controller switch monitoring function Check Code List Indoor Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Operation of diagnostic function Judgment and measuresCause of operation Status Error mode detected by outdoor unit AfterSeries H03 Current detection circuit error Stop Power supply error of remote controller, Indoor E09 error YESE04 error E10 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P10 error P01 errorP19 error F02 error F01 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit TA, TC, TCJ sensors Temperature Resistance value characteristic tableTemperature sensor TA, TC, TCJ Representative valuePart name Checking procedure Resistance valueReplacement of Service P.C. Board Replacement proceduresSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom StepOperation is available again Type Code No Indoor unit capacity Code NoTest Run Setup on Remote Controller Wired remote controller Practical operationD203 Red Function Selection SetupLED Display on Indoor P.C. Board D002 Red TEMP. buttons, specify the Code No. DNContents Function selection item No. DN listHow to set wired remote controller as sub remote controller Wired remote controllerSetup method When connected 2 remote controllers operate an indoor unitContents Pushing Test button returns the display to usual display Calling of error historyGroup control operation System exampleIndoor unit power-ON sequence Power onModel Connection Interface Function Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLE2Wiring specifications C. board switch SW01 setupPush Test + Vent buttons for 4 seconds or more External view of P.C. board assemblyAddress setup Push Test buttonDuring unset time, At shipment from factory is displayed Code No Data at shipment Setup data range System Configuration Address Setup & Group Control TerminologyAutomatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionPush SET Button. OK when display goes on Push Test Using the temperature setup ButtonsUsing timer time Buttons, set the line address PushProcedure Confirmation of indoor unit No. positionTo know the position of indoor unit body by address Contents Precautions for Safety Concealed Duct High Static Pressure Relocation Symbol DescriptionExamples of indication on the carton Other cautions DescriptionWired Remote Controller Part NamesDisplay section Operation section Start Correct UsagePreparation StopPush button during operation Timer OperationPower Saving Mode SetAdvanced Settings Power saving modeEnergy Saving Recommendations Maintenance List MaintenanceCleaning air filters Preparing for long Shut Down PeriodAIR Conditioner Operations and Performance InstallationDo not install the air conditioner in the following places Be careful with noise or vibrationsTroubleshooting SpecificationsInstallation Manual Definition of Protective Gear Work undertaken Protective gear wornGeneral Selection of installation locationElectrical wiring Refrigerant pipingAccessory Parts New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Installation space Unit mm Selection of Installation PlaceInstallation under high-humidity atmosphere Filter cleaning sign term settingInstallation of indoor unit External DimensionsInstallation of hanging bolt Installation of hanging boltDuct design Diagrams for making connecting flangesDuct installation example First floor Air outlet port flangeFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Low static pressure F1 Wire connection change of fan motorDrain Piping Work Standard Middle static pressure F2Drain up Connecting drain pipePipe material, size and insulator Check the drainingRefrigerant Piping Refrigerant Piping and EvacuatingHeat insulating process Liquid side refrigerant pipe connectionGas side refrigerant pipe connection EvacuationPower and Wiring Specification Wire connectionWiring diagram Electrical ConnectionWiring diagram Remote Controller WiringChanging of setting applicable control Applicable ControlsConcealed Duct High Static Pressure Procedure Remote controller switch monitoring functionFilter sign setting To secure better effect of heatingInstallation Manual Procedure Procedure exampleManual address setup procedure Group controlProcedure 8C OperationBefore test run Daily maintenanceTest RUN Execute a test runConfirmation of error log Concealed Duct High Static PressureInstallation ManualConfirmation and check Error codes and parts to be checked StatusHow to replace the parts Fan assembly and replacement Part name Work procedure RemarksFan assembly Pull out the fan assembly a fan toward you Fan/Fan case104 Fan motor Location Description 2242DT-E215, 216 219 218 214218 213 108 Check of Concentration Limit Toshiba Carrier Corporation
Related manuals
Manual 41 pages 43.38 Kb

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.