Toshiba RAV-SM2802DT-E External Dimensions, Installation of hanging bolt, Treatment of ceiling

Page 87

Concealed Duct High Static Pressure

Installation Manual

4 INSTALLATION

WARNING

Install the air conditioner certainly to sufficiently withstand the weight.

If the strength is insufficient, the unit may fall down resulting in human injury.

Perform a specified installation work to guard against strong wind or earthquake.

An incomplete installation can cause accidents by the units falling and dropping.

REQUIREMENT

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

Do not put a heavy article on the indoor unit. (Even units are packaged)

Carry in the indoor unit as it is packaged if possible.

If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.

To move the indoor unit, hold the hooking metals (4 positions) only.

Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).

Hanging bolt pitch of air inlet chamber side is different (centre position), make sure not to make mistake to install the setting direction.

Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.

n External Dimensions

(Unit: mm)

Concealed Duct High Static Pressure

nInstallation of hanging bolt

Consider the piping/wiring after the unit is hung when determining the location of the indoor unit installation and orientation.

After the location of the indoor unit installation has been determined, install hanging bolts.

For the dimensions of the hanging bolt pitches, refer to the external view.

When a ceiling already exists, lay the drain pipe, refrigerant pipe, system interconnection wires, and remote controller wires to their connection locations before hanging the indoor unit.

Procure hanging bolts washer and nuts for installing the indoor unit (these are not supplied).

Hanging bolt

M10 or W3/8

4 pieces

 

 

 

Nut

M10 or W3/8

12 pieces

 

 

 

Washer

M10

8 pieces

 

 

 

Installation of hanging bolt

Use M10 hanging bolts (4 pcs, to be local procure).

Matching to the existing structure, set pitch according to size in the unit external view as shown below.

Installation Manual

nInstallation of indoor unit

Treatment of ceiling

The ceiling differs according to structure of building.

For details, consult your constructor or interior finish contractor.

In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.

Attach the nuts and the M10 flat washers to the hanging bolt.

Put washers at up and down of the hanging bracket of the indoor unit to hang down the indoor unit.

Using a level vial, check that four sides are horizontal. (Horizontal degree: Within 5mm)

Hanging bolt

M10 flat washer

(W3/8 or M10)

 

Nut

 

(W3/8 or M10)

M10 flat washer

Nut

 

(W3/8 or M10)

 

– 87 –

4-M10 hanging bolt (Local procure)

1288 (Hanging bolt pitch)

1328

 

 

 

 

 

 

 

 

 

 

(Hanging bolt pitch)

1380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

New concrete slab

Install the bolts with insert brackets or anchor bolts.

 

 

Rubber

 

 

Anchor bolt

(Blade type

(Slide type

(Pipe hanging

bracket)

bracket)

anchor bolt)

Steel flame structure

Use existing angles or install new support angles.

Hanging bolt

Hanging bolt

Support angle

Check that four sides are horizontal using a level vial. (Horizontal degree: Within 5mm)

REQUIREMENT

Hang the unit in a horizontal position.

When unit is hanged to slant, it may cause overflow of drainage.

Install the unit within the dimension according to the figure below.

Using level vial or vinyl hose to confirm whether the unit is hang horizontally.

Electrical control box

Refrigerant pipe connecting port

(Gas side Ø22.2 Brazed) Refrigerant pipe connecting port (Liquid side Ø12.7 Flared)

 

 

1250

 

 

 

200 150

 

 

470

22

Drain pipe

31

 

45

46

624

 

 

65

connecting port

 

698

 

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

 

Front view

 

Side view

 

 

 

Water pouring

to5mm

 

±5mm

Vinyl hose

0

Set the drain pipe connecting

 

Set the air inlet and air outlet

 

 

 

port side within 5mm lower

 

sides are within 5mm with

 

than opposite side.

 

each other.

– 11 –

– 12 –

Image 87
Contents Split Type Contents Original instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Relocation SpecificationsModel Sound power level dB Weight kg Cooling Heating Explanations given to userFlare nut Safety Caution Concerned to New RefrigerantPipe Materials Copper pipe PipingUsed tool Usage ToolsGeneral tools Conventional tools can be used R410A Conventional airModel Indoor unit Concealed Duct High static pressure TypeRAV-SM2242DT-TR RAV-SM2802DT-TR Concealed Duct High static pressure Type ContinedSM2242DT-E Indoor UnitIndoor unit Dimension tableUnit Indoor100 RAV-SM2242 type350 300 250 200 150 100 3200 3360 RAV-SM2802 typeHigh static pressure F3 Wire connection change of fan motorLow static pressure F1 Standard Middle static pressure F2Parts name Type Specifications Specifications of Electrical PartsOutdoor unit Indoor Controller Block DiagramConnection of Wired Simple Remote Controller Indoor unit #1 HeaderOutline of specifications Remarks Control outlineOutside temp Correction value a Indoor formation Setup dataTa ˚C Cooling +1.5 Tc, Tcj TcnConditions Tc n Control temp. C Setup at shipmentHeat Case of wired remote controllerUsual control MCC-1403 Print Circuit BoardFunction Connector Pin Specifications Remarks Optional Connector Specifications of Indoor P.C. BoardBefore troubleshooting Troubleshooting procedureWired remote controller type Procedure Main remote controller RBC-AMT32EConfirmation of error log How to read check monitor displayRemote controller switch monitoring function Check Code List Indoor Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Operation of diagnostic function Judgment and measuresCause of operation Status Error mode detected by outdoor unit AfterSeries H03 Current detection circuit error Stop Power supply error of remote controller, Indoor YES E09 errorE10 error E04 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P01 error P10 errorP19 error F01 error F02 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit Representative value Temperature Resistance value characteristic tableTemperature sensor TA, TC, TCJ TA, TC, TCJ sensorsResistance value Part name Checking procedureReplacement procedures Replacement of Service P.C. BoardSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom StepOperation is available again Indoor unit capacity Code No Type Code NoPractical operation Test Run Setup on Remote Controller Wired remote controllerTEMP. buttons, specify the Code No. DN Function Selection SetupLED Display on Indoor P.C. Board D002 Red D203 RedFunction selection item No. DN list ContentsWhen connected 2 remote controllers operate an indoor unit Wired remote controllerSetup method How to set wired remote controller as sub remote controllerContents System example Calling of error historyGroup control operation Pushing Test button returns the display to usual displayPower on Indoor unit power-ON sequenceModel name TCB-PCNT30TLE2 Microprocessor block diagramModel connection interface wiring connection Model Connection Interface FunctionC. board switch SW01 setup Wiring specificationsPush Test button External view of P.C. board assemblyAddress setup Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Code No Data at shipment Setup data range Address Setup & Group Control Terminology System ConfigurationOnly turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringPush Using the temperature setup ButtonsUsing timer time Buttons, set the line address Push SET Button. OK when display goes on Push TestProcedure Confirmation of indoor unit No. positionTo know the position of indoor unit body by address Contents Precautions for Safety Other cautions Description Symbol DescriptionExamples of indication on the carton Concealed Duct High Static Pressure RelocationWired Remote Controller Part NamesDisplay section Operation section Stop Correct UsagePreparation StartSet Timer OperationPower Saving Mode Push button during operationAdvanced Settings Power saving modeEnergy Saving Recommendations Preparing for long Shut Down Period MaintenanceCleaning air filters Maintenance ListBe careful with noise or vibrations InstallationDo not install the air conditioner in the following places AIR Conditioner Operations and PerformanceSpecifications TroubleshootingInstallation Manual Work undertaken Protective gear worn Definition of Protective GearRefrigerant piping Selection of installation locationElectrical wiring GeneralAccessory Parts New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Filter cleaning sign term setting Selection of Installation PlaceInstallation under high-humidity atmosphere Installation space Unit mmInstallation of hanging bolt External DimensionsInstallation of hanging bolt Installation of indoor unitAir outlet port flange Diagrams for making connecting flangesDuct installation example First floor Duct designFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Standard Middle static pressure F2 Wire connection change of fan motorDrain Piping Work Low static pressure F1Check the draining Connecting drain pipePipe material, size and insulator Drain upLiquid side refrigerant pipe connection Refrigerant Piping and EvacuatingHeat insulating process Refrigerant PipingEvacuation Gas side refrigerant pipe connectionElectrical Connection Wire connectionWiring diagram Power and Wiring SpecificationApplicable Controls Remote Controller WiringChanging of setting applicable control Wiring diagramTo secure better effect of heating Remote controller switch monitoring functionFilter sign setting Concealed Duct High Static Pressure ProcedureGroup control Procedure exampleManual address setup procedure Installation Manual Procedure8C Operation ProcedureExecute a test run Daily maintenanceTest RUN Before test runConfirmation of error log Concealed Duct High Static PressureInstallation ManualConfirmation and check Status Error codes and parts to be checkedHow to replace the parts Fan assembly and replacement Part name Work procedure RemarksFan assembly Fan/Fan case Pull out the fan assembly a fan toward you104 Fan motor 2242DT-E Location Description215, 216 219 218 214218 213 108 Check of Concentration Limit Toshiba Carrier Corporation
Related manuals
Manual 41 pages 43.38 Kb

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.