Page 84

– 84 –

Concealed Duct High Static Pressure

Installation Manual

1 PRECAUTIONS FOR SAFETY

WARNING

General

Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.

Only a qualified installer (*1) or qualified service person (*1) is allowed to install the air conditioner.

If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.

Only a qualified installer (1) or qualified service person (1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.

Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result.

Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is

being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.

Only a qualified installer (1) or qualified service person (1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.

Wear protective gloves and safety work clothing during installation, servicing and removal.

Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so.

If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.

Do not climb onto or place objects on top of the outdoor unit.

You may fall or the objects may fall off of the outdoor unit and result in injury.

When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.

When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.

When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below.

The refrigerant used by this air conditioner is the R410A.

You shall ensure that the air conditioner is transported in stable condition.

Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when removing the cover and main unit.

Selection of installation location

If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks.

Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.

Do not install the air conditioner in a location that may be subject to a risk of exposure to a combustible gas. If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.

When transporting the air conditioner, wear shoes with additional protective toe caps.

When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.

Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.

Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.

Installation

When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be used.

Install the air conditioner at enough strong places to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury.

Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage, etc.

The designated bolts (M10, M12) and nuts (M10, M12) for securing the outdoor unit must be used when installing the unit.

Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.

Concealed Duct High Static Pressure

Installation Manual

Refrigerant piping

Install the refrigerant pipe securely during the installation work before operating the air conditioner.

If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.

Tighten the flare nut with a torque wrench in the specified manner.

Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.

When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle.

Failure to purge the air completely may cause the air conditioner to malfunction.

Nitrogen gas must be used for the airtight test.

The charge hose must be connected in such a way that it is not slack.

If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.

Electrical wiring

Only a qualified installer (1) or qualified service person (1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.

When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.

Failure to wear this protective gear may result in electric shocks.

Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws.

Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.

Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock.

Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.

After completing the repair or relocation work, check that the ground wires are connected properly.

Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.

Install the circuit breaker where it can be easily accessed by the agent.

When installing the circuit breaker outdoors, install one which is designed to be used outdoors.

Under no circumstances must the power cable be extended.

Connection trouble in the places where the cable is extended may give rise to smoking and/or a fire.

Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.

Test run

Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position.

You may receive an electric shock if the power is turned on without first conducting these checks.

When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person.

Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives.

Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks, etc.

After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 MΩ or more between the charge section and the non-charge metal section (Earth section).

If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.

Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.

Explanations given to user

Upon completion of the installation work, tell the user where the circuit breaker is located.

If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.

If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person (1) to have the repairs done.

Do not set the circuit breaker to the ON position until the repairs are completed.

After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.

Relocation

Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner.

It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.

(1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”

– 5 –

– 6 –

Image 84
Contents Split Type Contents Original instruction Explanation of indications Explanation of illustrated marksWork undertaken Protective gear worn Indication ExplanationConfirmation of warning label on the main unit DescriptionPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Specifications Model Sound power level dB Weight kg Cooling HeatingExplanations given to user RelocationSafety Caution Concerned to New Refrigerant Pipe MaterialsCopper pipe Piping Flare nutTools General tools Conventional tools can be usedR410A Conventional air Used tool UsageConcealed Duct High static pressure Type Model Indoor unitConcealed Duct High static pressure Type Contined RAV-SM2242DT-TR RAV-SM2802DT-TRIndoor Unit SM2242DT-EDimension table Indoor unitIndoor UnitRAV-SM2242 type 100RAV-SM2802 type 350 300 250 200 150 100 3200 3360Wire connection change of fan motor Low static pressure F1Standard Middle static pressure F2 High static pressure F3Specifications of Electrical Parts Parts name Type SpecificationsIndoor Controller Block Diagram Connection of Wired Simple Remote ControllerIndoor unit #1 Header Outdoor unitOutline of specifications Remarks Control outlineOutside temp Correction value a Setup data Indoor formationTa ˚C Cooling +1.5 Tc, Tcj TcnConditions Tc n Setup at shipment Control temp. CCase of wired remote controller HeatUsual control Print Circuit Board MCC-1403Optional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksBefore troubleshooting Troubleshooting procedureWired remote controller type Main remote controller RBC-AMT32E Confirmation of error logHow to read check monitor display ProcedureRemote controller switch monitoring function Check Code List Indoor Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Operation of diagnostic function Judgment and measuresCause of operation Status Error mode detected by outdoor unit AfterSeries H03 Current detection circuit error Stop Power supply error of remote controller, Indoor E09 error YESE04 error E10 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P10 error P01 errorP19 error F02 error F01 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit Temperature Resistance value characteristic table Temperature sensor TA, TC, TCJTA, TC, TCJ sensors Representative valuePart name Checking procedure Resistance valueReplacement of Service P.C. Board Replacement proceduresSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents Writing the setting data to Eeprom StepOperation is available again Type Code No Indoor unit capacity Code NoTest Run Setup on Remote Controller Wired remote controller Practical operationFunction Selection Setup LED Display on Indoor P.C. Board D002 RedD203 Red TEMP. buttons, specify the Code No. DNContents Function selection item No. DN listWired remote controller Setup methodHow to set wired remote controller as sub remote controller When connected 2 remote controllers operate an indoor unitContents Calling of error history Group control operationPushing Test button returns the display to usual display System exampleIndoor unit power-ON sequence Power onMicroprocessor block diagram Model connection interface wiring connectionModel Connection Interface Function Model name TCB-PCNT30TLE2Wiring specifications C. board switch SW01 setupExternal view of P.C. board assembly Address setupPush Test + Vent buttons for 4 seconds or more Push Test buttonDuring unset time, At shipment from factory is displayed Code No Data at shipment Setup data range System Configuration Address Setup & Group Control TerminologyAutomatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionUsing the temperature setup Buttons Using timer time Buttons, set the line addressPush SET Button. OK when display goes on Push Test PushProcedure Confirmation of indoor unit No. positionTo know the position of indoor unit body by address Contents Precautions for Safety Symbol Description Examples of indication on the cartonConcealed Duct High Static Pressure Relocation Other cautions DescriptionWired Remote Controller Part NamesDisplay section Operation section Correct Usage PreparationStart StopTimer Operation Power Saving ModePush button during operation SetAdvanced Settings Power saving modeEnergy Saving Recommendations Maintenance Cleaning air filtersMaintenance List Preparing for long Shut Down PeriodInstallation Do not install the air conditioner in the following placesAIR Conditioner Operations and Performance Be careful with noise or vibrationsTroubleshooting SpecificationsInstallation Manual Definition of Protective Gear Work undertaken Protective gear wornSelection of installation location Electrical wiringGeneral Refrigerant pipingAccessory Parts New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Selection of Installation Place Installation under high-humidity atmosphereInstallation space Unit mm Filter cleaning sign term settingExternal Dimensions Installation of hanging boltInstallation of indoor unit Installation of hanging boltDiagrams for making connecting flanges Duct installation example First floorDuct design Air outlet port flangeFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Wire connection change of fan motor Drain Piping WorkLow static pressure F1 Standard Middle static pressure F2Connecting drain pipe Pipe material, size and insulatorDrain up Check the drainingRefrigerant Piping and Evacuating Heat insulating processRefrigerant Piping Liquid side refrigerant pipe connectionGas side refrigerant pipe connection EvacuationWire connection Wiring diagramPower and Wiring Specification Electrical ConnectionRemote Controller Wiring Changing of setting applicable controlWiring diagram Applicable ControlsRemote controller switch monitoring function Filter sign settingConcealed Duct High Static Pressure Procedure To secure better effect of heatingProcedure example Manual address setup procedureInstallation Manual Procedure Group controlProcedure 8C OperationDaily maintenance Test RUNBefore test run Execute a test runConfirmation of error log Concealed Duct High Static PressureInstallation ManualConfirmation and check Error codes and parts to be checked StatusHow to replace the parts Fan assembly and replacement Part name Work procedure RemarksFan assembly Pull out the fan assembly a fan toward you Fan/Fan case104 Fan motor Location Description 2242DT-E215, 216 219 218 214218 213 108 Check of Concentration Limit Toshiba Carrier Corporation
Related manuals
Manual 41 pages 43.38 Kb

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.