York DR090, DR120, DR150 Dr Capacity Ratings, Unit Voltage Limitations, YTG-C-0606, Power Rating

Page 16

 

 

 

 

 

 

 

 

 

 

 

 

246721-YTG-C-0606

TABLE 3: DR CAPACITY RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Capacity

 

 

 

Nominal

 

Gas Heat Capacity

 

Gas

 

 

ARI Ratings1

 

 

Sound

 

 

 

 

 

 

Electric

 

 

 

 

 

 

 

 

 

 

Size

Model

 

 

 

 

CFM

Rating

Heat

 

 

 

 

Line

 

 

 

 

Input

Output

Seasonal

Temp.

Size

 

 

 

 

 

 

 

(dB)2

Capacity3

 

 

MBH

EER

IPLV

 

 

Efficiency

Rise

(in. OD)

 

 

 

 

 

(kW)

(MBH)

(MBH)

 

 

 

 

 

 

 

 

(%)

(°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

-

-

-

-

-

-

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

090

Electric

90

11.2

11.65

 

3000

84

9, 18, 24,

-

-

-

-

-

Heat

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

120

96

80

15-45

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

180

144

80

30-60

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

-

-

-

-

-

-

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

Electric

116

11.2

11.40

 

3480

90

18, 24, 36,

-

-

-

-

-

Heat

 

54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

180

144

80

20-50

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

240

192

80

35-65

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

-

-

-

-

-

-

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

Electric

148

11.1

11.7

 

3750

86

18, 24, 36,

-

-

-

-

-

Heat

 

54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

180

144

80

10-40

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat

 

 

 

 

 

 

-

240

192

80

25-55

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.

2.Rated in accordance with ARI 270 standard.

3.See Table 15.

TABLE 4: UNIT VOLTAGE LIMITATIONS

POWER RATING

MIN.

MAX.

208/230-3-60

187

252

460-3-60

432

504

 

 

 

575-3-60

540

630

16

Unitary Products Group

Image 16
Contents MagnaDRY DESCRIPTIONTECHNICAL GUIDETABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606FIGURE 2 - PREDATOR MagnaDRY DR150 FEATURES246721-YTG-C-0606 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606ALTERNATE” MODE FIGURE 3 - REHEAT CONTROL BOARD246721-YTG-C-0606 246721-YTG-C-0606 FIGURE 4 - DR090 & 120 REHEAT CONTROLSUnitary Products Group FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606NOMENCLATURE 7.5-12.5Ton York Model Number NomenclatureD R 090 N10 A 2 A AA 3 0 1 2 4 A 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606POWER RATING TABLE 3 DR CAPACITY RATINGSTABLE 4 UNIT VOLTAGE LIMITATIONS 246721-YTG-C-0606246721-YTG-C-0606 TABLE 5 COOLING CAPACITY DR090 UNITUnitary Products Group 246721-YTG-C-0606 Air On Evap. Coil246721-YTG-C-0606 TABLE 7 COOLING CAPACITY DR120 UNITUnitary Products Group 246721-YTG-C-0606 Air On Evap246721-YTG-C-0606 TABLE 9 COOLING CAPACITY DR150 UNITUnitary Products Group 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS TABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW DR 090 Standard Drive Assembly Side Flow246721-YTG-C-0606 246721-YTG-C-0606 DR 090 Optional Drive Assembly Side Flow100% Return Economizer DR 090 Standard Drive Assembly Down Flow DR 090 Optional Drive Assembly Down FlowTABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606246721-YTG-C-0606 TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOWUnitary Products Group DR120 Standard Drive Assembly Side Flow VolumetricVolumetric 246721-YTG-C-0606246721-YTG-C-0606 TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOWUnitary Products Group DR 120 Standard Drive Assembly Down Flow DR 120 Optional Drive Assembly Down Flow246721-YTG-C-0606 100% Return EconomizerDR150 Standard Drive Assembly Side Flow DR150 Optional Drive Assembly Side FlowTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW 246721-YTG-C-0606246721-YTG-C-0606 DR150 Optional Drive Assembly Side Flow100% Return Economizer 246721-YTG-C-0606 TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOWUnitary Products Group 246721-YTG-C-0606 100% Return EconomizerTABLE 32 INDOOR BLOWER SPECIFICATIONS TABLE 33 POWER EXHAUST SPECIFICATIONSTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD TABLE 36 UNIT WEIGHT FIGURE 18 - DR090/120 UNIT DIMENSIONS246721-YTG-C-0606 See Detail AFIGURE 19 - DR150 UNIT DIMENSIONS DETAIL ADETAIL B TABLE 37 UNIT CLEARANCESRIGHT FRONT 8or14246721-YTG-C-0606 2TYP18-1/45-5/32 31-11/162-31/3218-1/4 246721-YTG-C-0606FIGURE 24 - DR150 REAR DUCT DIMENSIONS FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 Dot Plugs 18-1/4 Return Air28-1/4 Supply AirTABLE 38 ECONOMIZER USAGE FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 246721-YTG-C-0606 FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZERUnitary Products Group 2EE04705524 Return Air Damper Field Installed 1EH0409 Fresh Air Hood Field Installed Duct Work Power Exhaust246721-YTG-C-0606 2EE04705X24 Slab Economizer 1EH0409FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING 246721-YTG-C-0606TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CSUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER THREE PHASE POWER SUPPLYUnitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 42 - DR150 REHEAT WIRING DIAGRAMUnitary Products Group GUIDE SPECIFICATIONS PREDATOR MagnaDRY DRGENERAL DESCRIPTIONUNIT OPERATING CHARACTERISTICS 246721-YTG-C-0606GAS HEATING SECTION IF EQUIPPED ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS