York DR120, DR090 YTG-C-0606, DR 090 Optional Drive Assembly Side Flow, 100% Return Economizer

Page 30
DR 090 Optional Drive Assembly (Side Flow)

246721-YTG-C-0606

TABLE 19: BLOWER PERFORMANCE DR090 SIDEFLOW ECONOMIZER

DR090 Standard Drive Assembly (Side Flow) (100% Return Economizer)

ESP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3

3886

 

846

1588

1.70

3655

807

1408

1.51

3388

 

774

1242

1.33

3252

 

747

1090

1.17

2979

 

726

952

1.02

2670

 

712

828

0.89

0.4

3709

 

847

1530

1.64

3478

808

1350

1.45

3211

 

775

1184

1.27

3027

 

748

1032

1.11

2754

 

727

894

0.96

2445

 

713

769

0.83

0.5

3517

 

848

1468

1.57

3286

809

1288

1.38

3019

 

776

1122

1.20

2782

 

749

970

1.04

2509

 

729

832

0.89

2199

 

714

707

0.76

0.6

3310

 

849

1401

1.50

3079

810

1221

1.31

2811

 

777

1055

1.13

2518

 

751

903

0.97

2245

 

730

765

0.82

1936

 

715

641

0.69

0.7

3088

 

851

1329

1.43

2857

812

1149

1.23

2590

 

779

983

1.05

2237

 

752

831

0.89

1964

 

731

693

0.74

 

 

 

 

 

0.8

2853

 

853

1250

1.34

2622

814

1070

1.15

2354

 

781

904

0.97

1940

 

754

752

0.81

 

 

 

 

 

 

 

 

 

 

0.9

2605

 

855

1164

1.25

2373

816

984

1.06

2106

 

783

818

0.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2343

 

858

1070

1.15

2112

819

890

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 Turns Open

 

 

1 Turn Open

 

 

2 Turns Open

 

 

3 Turns Open

 

 

4 Turns Open

 

 

5 Turns Open

 

 

 

 

 

 

 

 

DR090 Optional Drive Assembly (Side Flow) (100% Return Economizer)

 

 

 

 

 

 

ESP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

0.3

----

 

----

----

----

----

----

----

----

----

----

----

----

4651

913

2124

2.28

4331

871

1846

1.98

3990

828

1595

1.71

0.4

----

 

----

----

----

----

----

----

----

----

----

----

----

4434

912

2037

2.18

4114

871

1759

1.89

3772

828

1508

1.62

0.5

----

 

----

----

----

----

----

----

----

----

----

----

----

4232

913

1948

2.09

3912

871

1670

1.79

3571

828

1419

1.52

0.6

----

 

----

----

----

----

----

----

----

4319

954

2161

2.32

4040

914

1857

1.99

3720

873

1580

1.69

3379

829

1328

1.42

0.7

----

 

----

----

----

----

----

----

----

4159

955

2068

2.22

3852

916

1764

1.89

3532

874

1486

1.59

3190

831

1235

1.32

0.8

----

 

----

----

----

----

----

----

----

3996

958

1972

2.12

3660

918

1668

1.79

3340

876

1391

1.49

2999

833

1139

1.22

0.9

----

 

----

----

----

4137

998

2202

2.36

3825

960

1873

2.01

3459

920

1569

1.68

3139

879

1291

1.39

2797

835

1040

1.12

1

----

 

----

----

----

3949

1000

2100

2.25

3637

962

1770

1.90

3242

923

1466

1.57

2922

881

1189

1.28

----

----

----

----

1.1

----

 

----

----

----

3738

1003

1993

2.14

3427

965

1663

1.78

3002

925

1360

1.46

----

----

----

----

----

----

----

----

1.2

----

 

----

----

----

3498

1005

1882

2.02

3186

967

1553

1.67

----

----

----

----

----

----

----

----

----

----

----

----

 

 

0 Turns Open

 

 

1 Turn Open

 

 

2 Turns Open

 

 

3 Turns Open

 

 

4 Turns Open

 

 

5 Turns Open

 

 

DR 090 Standard Drive Assembly (Side Flow)

 

 

 

 

 

(100% Return Economizer)

 

 

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

 

0 Turns

 

 

 

 

 

 

 

 

(cfm)

3750

1 Turn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

2 Turns

 

 

 

 

 

 

 

 

Rate

 

 

 

 

 

 

 

 

 

3250

3 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow

 

 

 

 

 

 

 

 

 

3000

4 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volumetric

2750

5 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

 

2250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

 

 

 

External Static Pressure (iwg)

 

 

DR 090 Optional Drive Assembly (Side Flow)

(100% Return Economizer)

 

4750

3 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(cfm)

4500

 

 

 

 

 

 

 

 

 

 

 

 

 

4 Turns

 

 

2 Turns

 

 

 

 

 

 

4250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Turn

 

 

 

 

Rate

 

 

 

 

 

 

 

 

 

 

 

 

4000

5 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow

3750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volumetric

3500

 

 

 

 

 

 

 

 

 

 

 

 

3250

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2750

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

External Static Pressure (iwg)

30

Unitary Products Group

Image 30
Contents TECHNICAL MagnaDRYDESCRIPTION GUIDELIST OF TABLES TABLE OF CONTENTSLIST OF FIGURES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606FEATURES FIGURE 2 - PREDATOR MagnaDRY DR150246721-YTG-C-0606 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606FIGURE 3 - REHEAT CONTROL BOARD ALTERNATE” MODE246721-YTG-C-0606 FIGURE 4 - DR090 & 120 REHEAT CONTROLS 246721-YTG-C-0606Unitary Products Group FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606D R 090 N10 A 2 A AA 3 0 1 2 4 A NOMENCLATURE7.5-12.5Ton York Model Number Nomenclature 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606TABLE 4 UNIT VOLTAGE LIMITATIONS POWER RATINGTABLE 3 DR CAPACITY RATINGS 246721-YTG-C-0606TABLE 5 COOLING CAPACITY DR090 UNIT 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 Air On Evap. CoilTABLE 7 COOLING CAPACITY DR120 UNIT 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 Air On EvapTABLE 9 COOLING CAPACITY DR150 UNIT 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS DR 090 Standard Drive Assembly Side Flow TABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW246721-YTG-C-0606 DR 090 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer TABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW DR 090 Standard Drive Assembly Down FlowDR 090 Optional Drive Assembly Down Flow 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW 246721-YTG-C-0606Unitary Products Group Volumetric DR120 Standard Drive Assembly Side FlowVolumetric 246721-YTG-C-0606TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 DR 120 Standard Drive Assembly Down FlowDR 120 Optional Drive Assembly Down Flow 100% Return EconomizerTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW DR150 Standard Drive Assembly Side FlowDR150 Optional Drive Assembly Side Flow 246721-YTG-C-0606DR150 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 100% Return EconomizerTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 32 INDOOR BLOWER SPECIFICATIONSTABLE 33 POWER EXHAUST SPECIFICATIONS TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD 246721-YTG-C-0606 TABLE 36 UNIT WEIGHTFIGURE 18 - DR090/120 UNIT DIMENSIONS See Detail ADETAIL B FIGURE 19 - DR150 UNIT DIMENSIONSDETAIL A TABLE 37 UNIT CLEARANCES246721-YTG-C-0606 RIGHTFRONT 8or14 2TYP18-1/4 18-1/45-5/3231-11/162-31/32 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 24 - DR150 REAR DUCT DIMENSIONSFIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL Dot Plugs 18-1/4 Return Air28-1/4 Supply AirFIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL TABLE 38 ECONOMIZER USAGE246721-YTG-C-0606 FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER 246721-YTG-C-0606Unitary Products Group 2EE04705524 Return Air Damper Field Installed 246721-YTG-C-0606 1EH0409 Fresh Air Hood Field Installed Duct WorkPower Exhaust 2EE04705X24 Slab Economizer 1EH0409TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING246721-YTG-C-0606 R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CUnitary Products Group SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWERTHREE PHASE POWER SUPPLY TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606FIGURE 42 - DR150 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group GENERAL GUIDE SPECIFICATIONSPREDATOR MagnaDRY DR DESCRIPTIONGAS HEATING SECTION IF EQUIPPED UNIT OPERATING CHARACTERISTICS246721-YTG-C-0606 ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS