Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.

Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.

BAS - Building Automation System Controls Simplicity® Intelli-Comfort™ Control - The York Simplicity® Intelli-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the Intelli-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the Intelli-Start algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® Intelli-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

Simplicity® Intelli-Comfort™ with ModLINC Control - The York Simplicity® Intelli-Comfort™ with ModLINC control is factory installed. It includes all the features of the Intelli-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.

Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto- mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed.

246721-YTG-C-0606

Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

FIELD INSTALLED ACCESSORIES

YORK® offers several equipment accessories for field instal- lation, for the Predator® line.

Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out- door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand ventila- tion. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a sec- ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.

Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.

You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.

Slab Economizer for Energy Recovery Ventilator- (Without barometric relief or Fresh Air Hood) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out- door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand ventila- tion.With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a sec- ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.

You can order 1EH0409 Barometric Relief/FA Hood for field installations without an ERV.

Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.

8

Unitary Products Group

Image 8
Contents MagnaDRY DESCRIPTIONTECHNICAL GUIDETABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606246721-YTG-C-0606 FEATURESFIGURE 2 - PREDATOR MagnaDRY DR150 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 3 - REHEAT CONTROL BOARDALTERNATE” MODE Unitary Products Group FIGURE 4 - DR090 & 120 REHEAT CONTROLS246721-YTG-C-0606 FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606NOMENCLATURE 7.5-12.5Ton York Model Number NomenclatureD R 090 N10 A 2 A AA 3 0 1 2 4 A 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606POWER RATING TABLE 3 DR CAPACITY RATINGSTABLE 4 UNIT VOLTAGE LIMITATIONS 246721-YTG-C-0606Unitary Products Group TABLE 5 COOLING CAPACITY DR090 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On Evap. CoilUnitary Products Group TABLE 7 COOLING CAPACITY DR120 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On EvapUnitary Products Group TABLE 9 COOLING CAPACITY DR150 UNIT246721-YTG-C-0606 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS 246721-YTG-C-0606 DR 090 Standard Drive Assembly Side FlowTABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW 100% Return Economizer DR 090 Optional Drive Assembly Side Flow246721-YTG-C-0606 DR 090 Standard Drive Assembly Down Flow DR 090 Optional Drive Assembly Down FlowTABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606Unitary Products Group TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW246721-YTG-C-0606 DR120 Standard Drive Assembly Side Flow VolumetricVolumetric 246721-YTG-C-0606Unitary Products Group TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW246721-YTG-C-0606 DR 120 Standard Drive Assembly Down Flow DR 120 Optional Drive Assembly Down Flow246721-YTG-C-0606 100% Return EconomizerDR150 Standard Drive Assembly Side Flow DR150 Optional Drive Assembly Side FlowTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW 246721-YTG-C-0606100% Return Economizer DR150 Optional Drive Assembly Side Flow246721-YTG-C-0606 Unitary Products Group TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW246721-YTG-C-0606 246721-YTG-C-0606 100% Return EconomizerTABLE 32 INDOOR BLOWER SPECIFICATIONS TABLE 33 POWER EXHAUST SPECIFICATIONSTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD TABLE 36 UNIT WEIGHT FIGURE 18 - DR090/120 UNIT DIMENSIONS246721-YTG-C-0606 See Detail AFIGURE 19 - DR150 UNIT DIMENSIONS DETAIL ADETAIL B TABLE 37 UNIT CLEARANCESRIGHT FRONT 8or14246721-YTG-C-0606 2TYP18-1/45-5/32 31-11/162-31/3218-1/4 246721-YTG-C-0606FIGURE 24 - DR150 REAR DUCT DIMENSIONS FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 Dot Plugs 18-1/4 Return Air28-1/4 Supply Air246721-YTG-C-0606 FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAILTABLE 38 ECONOMIZER USAGE Unitary Products Group FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER246721-YTG-C-0606 2EE04705524 Return Air Damper Field Installed 1EH0409 Fresh Air Hood Field Installed Duct Work Power Exhaust246721-YTG-C-0606 2EE04705X24 Slab Economizer 1EH0409FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING 246721-YTG-C-0606TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CSUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER THREE PHASE POWER SUPPLYUnitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group FIGURE 42 - DR150 REHEAT WIRING DIAGRAM246721-YTG-C-0606 GUIDE SPECIFICATIONS PREDATOR MagnaDRY DRGENERAL DESCRIPTIONUNIT OPERATING CHARACTERISTICS 246721-YTG-C-0606GAS HEATING SECTION IF EQUIPPED ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS