York DR150, DR120, DR090 manual YTG-C-0606, DR 090 Standard Drive Assembly Down Flow

Page 32
DR 090 Standard Drive Assembly (Down Flow)

246721-YTG-C-0606

TABLE 21: BLOWER PERFORMANCE DR090 DOWNFLOW ECONOMIZER

DR090 Optional Drive Assembly (Down Flow) (100% Return Economizer)

ESP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

0.2

----

 

----

----

----

----

----

----

----

----

 

----

----

----

----

 

----

----

----

2755

 

729

970

1.04

2557

 

712

890

0.95

0.3

3355

 

854

1393

1.49

3132

815

1249

1.34

2903

 

781

1120

1.20

2737

 

753

1008

1.08

2544

 

730

912

0.98

2347

 

713

831

0.89

0.4

3154

 

855

1324

1.42

2924

816

1181

1.27

2692

 

782

1053

1.13

2494

 

754

940

1.01

2296

 

732

843

0.90

----

 

----

----

----

0.5

2945

 

857

1247

1.34

2719

818

1106

1.19

2487

 

784

978

1.05

2204

 

756

866

0.93

----

 

----

----

----

----

 

----

----

----

0.6

2720

 

859

1166

1.25

2505

820

1027

1.10

2277

 

786

901

0.97

----

 

----

----

----

----

 

----

----

----

----

 

----

----

----

0.7

2486

 

861

1089

1.17

2288

822

954

1.02

----

 

----

----

----

----

 

----

----

----

----

 

----

----

----

----

 

----

----

----

0.8

2284

 

863

1029

1.10

----

----

----

----

----

 

----

----

----

----

 

----

----

----

----

 

----

----

----

----

 

----

----

----

 

 

0 Turns Open

 

 

1 Turn Open

 

 

2 Turns Open

 

 

3 Turns Open

 

 

4 Turns Open

 

 

5 Turns Open

 

 

 

 

 

 

 

DR090 Optional Drive Assembly (Down Flow) (100% Return Economizer)

 

 

 

 

 

 

ESP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

CFM

RPM

WATT

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3

----

----

----

----

----

----

----

----

----

----

----

----

4096

898

1795

1.93

3825

863

1613

1.73

3523

832

1429

1.53

0.4

----

----

----

----

----

----

----

----

4134

936

1945

2.09

3891

899

1731

1.86

3621

864

1548

1.66

3322

832

1361

1.46

0.5

----

----

----

----

4192

977

2109

2.26

3946

937

1864

2.00

3690

900

1657

1.78

3421

865

1473

1.58

3125

834

1286

1.38

0.6

----

----

----

----

4007

978

2028

2.18

3759

938

1782

1.91

3495

901

1577

1.69

3227

867

1392

1.49

2934

835

1205

1.29

0.7

----

----

----

----

3823

980

1946

2.09

3574

940

1700

1.82

3306

903

1493

1.60

3040

868

1309

1.40

2750

837

1122

1.20

0.8

3872

1025

2139

2.30

3643

982

1863

2.00

3392

942

1617

1.73

3127

905

1410

1.51

2861

870

1227

1.32

----

----

----

----

0.9

3698

1027

2055

2.20

3466

984

1778

1.91

3214

944

1532

1.64

2957

907

1333

1.43

----

----

----

----

----

----

----

----

1

3530

1028

1967

2.11

3295

986

1691

1.81

3041

946

1445

1.55

----

----

----

----

----

----

----

----

----

----

----

----

1.1

3368

1030

1876

2.01

3130

988

1601

1.72

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

1.2

3214

1032

1780

1.91

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

 

 

0 Turns Open

 

 

1 Turn Open

 

 

2 Turns Open

 

 

3 Turns Open

 

 

4 Turns Open

 

 

5 Turns Open

 

 

DR 090 Standard Drive Assembly (Down Flow)

 

 

 

(100% Return Economizer)

 

 

 

 

3500

 

 

 

 

 

 

 

 

 

(cfm)

 

 

0 Turns

 

 

 

 

 

 

3250

 

 

 

 

 

 

 

 

 

Rate

 

 

 

1 Turn

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

 

Flow

 

2 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 Turns

 

3 Turns

 

 

 

 

 

 

Volumetric

2750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 Turns

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2250

 

 

 

 

 

 

 

 

 

 

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

 

 

 

External Static Pressure (iwg)

 

 

DR 090 Optional Drive Assembly (Down Flow)

(100% Return Economizer)

 

4500

 

 

 

 

 

 

 

 

 

 

 

(cfm)

4250

 

 

1 Turn

 

 

 

 

 

 

 

 

 

2 Turns

 

 

 

 

 

 

 

 

3 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rate

4000

 

 

 

 

 

0 Turns

 

 

 

 

 

4 Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow

3750

 

 

 

 

 

 

 

 

 

 

 

 

5 Turns

 

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

Volumetric

 

 

 

 

 

 

 

 

 

 

 

3250

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2750

 

 

 

 

 

 

 

 

 

 

 

 

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

External Static Pressure (iwg)

32

Unitary Products Group

Image 32
Contents MagnaDRY DESCRIPTIONTECHNICAL GUIDETABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606246721-YTG-C-0606 FEATURESFIGURE 2 - PREDATOR MagnaDRY DR150 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 3 - REHEAT CONTROL BOARDALTERNATE” MODE Unitary Products Group FIGURE 4 - DR090 & 120 REHEAT CONTROLS246721-YTG-C-0606 FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606NOMENCLATURE 7.5-12.5Ton York Model Number NomenclatureD R 090 N10 A 2 A AA 3 0 1 2 4 A 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606POWER RATING TABLE 3 DR CAPACITY RATINGSTABLE 4 UNIT VOLTAGE LIMITATIONS 246721-YTG-C-0606Unitary Products Group TABLE 5 COOLING CAPACITY DR090 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On Evap. CoilUnitary Products Group TABLE 7 COOLING CAPACITY DR120 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On EvapUnitary Products Group TABLE 9 COOLING CAPACITY DR150 UNIT246721-YTG-C-0606 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS 246721-YTG-C-0606 DR 090 Standard Drive Assembly Side FlowTABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW 100% Return Economizer DR 090 Optional Drive Assembly Side Flow246721-YTG-C-0606 DR 090 Standard Drive Assembly Down Flow DR 090 Optional Drive Assembly Down FlowTABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606Unitary Products Group TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW246721-YTG-C-0606 DR120 Standard Drive Assembly Side Flow VolumetricVolumetric 246721-YTG-C-0606Unitary Products Group TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW246721-YTG-C-0606 DR 120 Standard Drive Assembly Down Flow DR 120 Optional Drive Assembly Down Flow246721-YTG-C-0606 100% Return EconomizerDR150 Standard Drive Assembly Side Flow DR150 Optional Drive Assembly Side FlowTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW 246721-YTG-C-0606100% Return Economizer DR150 Optional Drive Assembly Side Flow246721-YTG-C-0606 Unitary Products Group TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW246721-YTG-C-0606 246721-YTG-C-0606 100% Return EconomizerTABLE 32 INDOOR BLOWER SPECIFICATIONS TABLE 33 POWER EXHAUST SPECIFICATIONSTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD TABLE 36 UNIT WEIGHT FIGURE 18 - DR090/120 UNIT DIMENSIONS246721-YTG-C-0606 See Detail AFIGURE 19 - DR150 UNIT DIMENSIONS DETAIL ADETAIL B TABLE 37 UNIT CLEARANCESRIGHT FRONT 8or14246721-YTG-C-0606 2TYP18-1/45-5/32 31-11/162-31/3218-1/4 246721-YTG-C-0606FIGURE 24 - DR150 REAR DUCT DIMENSIONS FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 Dot Plugs 18-1/4 Return Air28-1/4 Supply Air246721-YTG-C-0606 FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAILTABLE 38 ECONOMIZER USAGE Unitary Products Group FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER246721-YTG-C-0606 2EE04705524 Return Air Damper Field Installed 1EH0409 Fresh Air Hood Field Installed Duct Work Power Exhaust246721-YTG-C-0606 2EE04705X24 Slab Economizer 1EH0409FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING 246721-YTG-C-0606TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CSUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER THREE PHASE POWER SUPPLYUnitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group FIGURE 42 - DR150 REHEAT WIRING DIAGRAM246721-YTG-C-0606 GUIDE SPECIFICATIONS PREDATOR MagnaDRY DRGENERAL DESCRIPTIONUNIT OPERATING CHARACTERISTICS 246721-YTG-C-0606GAS HEATING SECTION IF EQUIPPED ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS