York DR120 YTG-C-0606, Gas Heating Section If Equipped, Electric Heating Section If Equipped

Page 63

246721-YTG-C-0606

Refrigerant Circuit and Refrigerant Safety Components shall include:

A.Independent fixed-orifice or thermally operated expan- sion devices.

B.Solid core filter drier/strainer to eliminate any moisture or foreign matter.

C.Accessible service gage connections on both suction and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.

D.The unit shall have two independent refrigerant circuits, equally split in 50% capacity increments.

Unit Controls:

A.Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-volt transformer side.

B.Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor:

C.Loss-of-charge/Low-pressure switch.

(1)High-pressure switch.

(2)Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, an LED (light-emitting diode) indicator shall flash a diagnostic code that indi- cates which safety switch has tripped.

D.Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.

E.Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

F.Unit control board shall have on-board diagnostics and fault code display.

G.Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 ºF.

H.Control board shall monitor each refrigerant safety switch independently.

I.Control board shall retain last 5 fault codes in non-vola- tile memory, which will not be lost in the event of a power loss.

GAS HEATING SECTION (IF EQUIPPED)

Heat exchanger and exhaust system shall be constructed of aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed

air entering temperature of 40 ºF. Burners shall be of the in- shot type, constructed of aluminum-coated steel. All gas pip- ing shall enter the unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board shall provide timed control of evapo- rator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection:

A.Primary and auxiliary high-temperature limit switches.

B.Induced draft pressure sensor.

C.Flame roll out switch (manual reset).

D.Flame proving controls. Unit shall have two independent stages of capacity (60% 1st stage, 100% 2nd stage).

ELECTRIC HEATING SECTION (IF EQUIPPED)

An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heat- ing element system from operating at an excessive tempera- ture. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125 ºF out- door temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor tempera- ture. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)

ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES - Compressor – 5 Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years, Parts – 1 Year

FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

1.ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER – Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring- return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer oper- ation, a mixed-air temperature control shall modulate the

Unitary Products Group

63

Image 63
Contents GUIDE MagnaDRYDESCRIPTION TECHNICAL246721-YTG-C-0606 TABLE OF CONTENTSLIST OF FIGURES LIST OF TABLES16 ELECTRICAL DATA DR150 W/PWRD 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 1 - PREDATOR MagnaDRY DR090FEATURES FIGURE 2 - PREDATOR MagnaDRY DR150246721-YTG-C-0606 246721-YTG-C-0606 FACTORY INSTALLED OPTIONSUnitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 FIELD INSTALLED ACCESSORIES246721-YTG-C-0606 REHEAT MODE SEQUENCE OF OPERATIONFIGURE 3 - REHEAT CONTROL BOARD ALTERNATE” MODE246721-YTG-C-0606 FIGURE 4 - DR090 & 120 REHEAT CONTROLS 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 FIGURE 5 - DR150 REHEAT CONTROLS246721-YTG-C-0606 TABLE 1 ACCESSORIES246721-YTG-C-0606 NOMENCLATURE7.5-12.5Ton York Model Number Nomenclature D R 090 N10 A 2 A AA 3 0 1 2 4 A246721-YTG-C-0606 TABLE 2 PHYSICAL DATA246721-YTG-C-0606 POWER RATINGTABLE 3 DR CAPACITY RATINGS TABLE 4 UNIT VOLTAGE LIMITATIONSTABLE 5 COOLING CAPACITY DR090 UNIT 246721-YTG-C-0606Unitary Products Group Air On Evap. Coil 246721-YTG-C-0606TABLE 7 COOLING CAPACITY DR120 UNIT 246721-YTG-C-0606Unitary Products Group Air On Evap 246721-YTG-C-0606TABLE 9 COOLING CAPACITY DR150 UNIT 246721-YTG-C-0606Unitary Products Group 10.7 246721-YTG-C-0606indoor dry bulb / wet bulb conditions 246721-YTG-C-0606 FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODEDR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS DR 090 Standard Drive Assembly Side Flow TABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW246721-YTG-C-0606 DR 090 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer 246721-YTG-C-0606 DR 090 Standard Drive Assembly Down FlowDR 090 Optional Drive Assembly Down Flow TABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW246721-YTG-C-0606 DR 090 Standard Drive Assembly Down FlowTABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 DR120 Standard Drive Assembly Side FlowVolumetric VolumetricTABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW 246721-YTG-C-0606Unitary Products Group 100% Return Economizer DR 120 Standard Drive Assembly Down FlowDR 120 Optional Drive Assembly Down Flow 246721-YTG-C-0606246721-YTG-C-0606 DR150 Standard Drive Assembly Side FlowDR150 Optional Drive Assembly Side Flow TABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOWDR150 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW 246721-YTG-C-0606Unitary Products Group 100% Return Economizer 246721-YTG-C-0606TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM TABLE 32 INDOOR BLOWER SPECIFICATIONSTABLE 33 POWER EXHAUST SPECIFICATIONS TABLE 30 ADDITIONAL STATIC RESISTANCEFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD See Detail A TABLE 36 UNIT WEIGHTFIGURE 18 - DR090/120 UNIT DIMENSIONS 246721-YTG-C-0606TABLE 37 UNIT CLEARANCES FIGURE 19 - DR150 UNIT DIMENSIONSDETAIL A DETAIL B2TYP RIGHTFRONT 8or14 246721-YTG-C-0606246721-YTG-C-0606 18-1/45-5/3231-11/162-31/32 18-1/4Dot Plugs 18-1/4 Return Air28-1/4 Supply Air FIGURE 24 - DR150 REAR DUCT DIMENSIONSFIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL 246721-YTG-C-0606FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL TABLE 38 ECONOMIZER USAGE246721-YTG-C-0606 FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER 246721-YTG-C-0606Unitary Products Group 2EE04705524 Return Air Damper Field Installed 2EE04705X24 Slab Economizer 1EH0409 1EH0409 Fresh Air Hood Field Installed Duct WorkPower Exhaust 246721-YTG-C-0606R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC C FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING246721-YTG-C-0606 TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 CTERMINAL BLOCK TB1 FACTORY OR FIELD SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWERTHREE PHASE POWER SUPPLY Unitary Products Group246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAMFIGURE 42 - DR150 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group DESCRIPTION GUIDE SPECIFICATIONSPREDATOR MagnaDRY DR GENERALELECTRIC HEATING SECTION IF EQUIPPED UNIT OPERATING CHARACTERISTICS246721-YTG-C-0606 GAS HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS