York DR150, DR120 Guide Specifications, PREDATOR MagnaDRY DR, General, Description, YTG-C-0606

Page 62

246721-YTG-C-0606

GUIDE SPECIFICATIONS

PREDATOR® MagnaDRY™

DR 090, 120 & 150

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® Predator® MagnaDRY™ units are convertible single pack- ages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to pro- vide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator® MagnaDRY™ units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Inde- pendent economizer designs are used on side and down dis- charge applications, as well as all tonnage sizes. Predator® MagnaDRY™ units are available in the following configura- tions: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or field-installed accessories.

the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, con- structed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate con- nection shall be a minimum of ¾” I.D. female and be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with for- ward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no mainte- nance. Entire blower assembly and motor shall be slide out design.

OUTDOOR (CONDENSER) FAN ASSEMBLY

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, Gas/Elec), designed for outdoor installation. Units shall have a minimum EER of 9.0. They shall have built in field convert- ible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with fac- tory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-22 refriger- ant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1/2” thick insulation coated on the airside. Aluminum foil faced insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with tool-less access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished and be accessible through hinged access door. Fan perfor- mance measuring ports shall be provided on the outside of

The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically bal- anced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.

REFRIGERANT COMPONENTS

Compressors:

A.Shall be fully hermetic type, direct drive, internally pro- tected with internal high-pressure relief and over temper- ature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.

B.Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

Coils:

A.Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

B.Evaporator and condenser coils shall be of the direct expansion, draw-thru design.

62

Unitary Products Group

Image 62
Contents TECHNICAL MagnaDRYDESCRIPTION GUIDELIST OF TABLES TABLE OF CONTENTSLIST OF FIGURES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606246721-YTG-C-0606 FEATURESFIGURE 2 - PREDATOR MagnaDRY DR150 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 3 - REHEAT CONTROL BOARDALTERNATE” MODE Unitary Products Group FIGURE 4 - DR090 & 120 REHEAT CONTROLS246721-YTG-C-0606 FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606D R 090 N10 A 2 A AA 3 0 1 2 4 A NOMENCLATURE7.5-12.5Ton York Model Number Nomenclature 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606TABLE 4 UNIT VOLTAGE LIMITATIONS POWER RATINGTABLE 3 DR CAPACITY RATINGS 246721-YTG-C-0606Unitary Products Group TABLE 5 COOLING CAPACITY DR090 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On Evap. CoilUnitary Products Group TABLE 7 COOLING CAPACITY DR120 UNIT246721-YTG-C-0606 246721-YTG-C-0606 Air On EvapUnitary Products Group TABLE 9 COOLING CAPACITY DR150 UNIT246721-YTG-C-0606 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS 246721-YTG-C-0606 DR 090 Standard Drive Assembly Side FlowTABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW 100% Return Economizer DR 090 Optional Drive Assembly Side Flow246721-YTG-C-0606 TABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW DR 090 Standard Drive Assembly Down FlowDR 090 Optional Drive Assembly Down Flow 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606Unitary Products Group TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW246721-YTG-C-0606 Volumetric DR120 Standard Drive Assembly Side FlowVolumetric 246721-YTG-C-0606Unitary Products Group TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW246721-YTG-C-0606 246721-YTG-C-0606 DR 120 Standard Drive Assembly Down FlowDR 120 Optional Drive Assembly Down Flow 100% Return EconomizerTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW DR150 Standard Drive Assembly Side FlowDR150 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer DR150 Optional Drive Assembly Side Flow246721-YTG-C-0606 Unitary Products Group TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW246721-YTG-C-0606 246721-YTG-C-0606 100% Return EconomizerTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 32 INDOOR BLOWER SPECIFICATIONSTABLE 33 POWER EXHAUST SPECIFICATIONS TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD 246721-YTG-C-0606 TABLE 36 UNIT WEIGHTFIGURE 18 - DR090/120 UNIT DIMENSIONS See Detail ADETAIL B FIGURE 19 - DR150 UNIT DIMENSIONSDETAIL A TABLE 37 UNIT CLEARANCES246721-YTG-C-0606 RIGHTFRONT 8or14 2TYP18-1/4 18-1/45-5/3231-11/162-31/32 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 24 - DR150 REAR DUCT DIMENSIONSFIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL Dot Plugs 18-1/4 Return Air28-1/4 Supply Air246721-YTG-C-0606 FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAILTABLE 38 ECONOMIZER USAGE Unitary Products Group FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER246721-YTG-C-0606 2EE04705524 Return Air Damper Field Installed 246721-YTG-C-0606 1EH0409 Fresh Air Hood Field Installed Duct WorkPower Exhaust 2EE04705X24 Slab Economizer 1EH0409TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING246721-YTG-C-0606 R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CUnitary Products Group SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWERTHREE PHASE POWER SUPPLY TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group FIGURE 42 - DR150 REHEAT WIRING DIAGRAM246721-YTG-C-0606 GENERAL GUIDE SPECIFICATIONSPREDATOR MagnaDRY DR DESCRIPTIONGAS HEATING SECTION IF EQUIPPED UNIT OPERATING CHARACTERISTICS246721-YTG-C-0606 ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS