York DR120, DR090, DR150 manual Reheat Mode Sequence Of Operation, YTG-C-0606

Page 9

246721-YTG-C-0606

Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase 1EH0408 barometric relief when applying to a hori- zontal flow application.

Manual Outdoor Air Damper - Like the motorized out- door air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.

Motorized Outdoor Air Damper - The motorized out- door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out- door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.

Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

CO2 Sensor - Senses CO2 levels and automatically overrides the economizer when levels rise above the preset limits.

Dirty Filter Switch - This kit includes a differential pres- sure switch that energizes the fault light on the unit ther- mostat, indicating that there is an abnormally high pressure drop across the filters.

Coil Guard - Field installed decorative wire coil guard.

Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.

Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

-60°F Gas Heat Kit - For installations which require gas heat units to perform in low ambient temperatures, a gas section heating kit is available. This kit provides electric heat in the gas heat controls section to ensure the gas valve and controls will continue to function properly at extremely low temperatures.

Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Con- version kits are available for natural gas and propane.

Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It contains the main burner orifices and gas valve replacement springs.

Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.

Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the elec- tric heaters. Necessary hardware and connectors are

included with the heaters. All heaters are intended for single point power supply.

Low Limit / Compressor Lockout Kit

1.Compressor Lockout (CLO): To prevent mechanical (compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.

2.Low Limit Control (LLC): To prevent the supply air from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.

Metal Frame Filter Kit - Metal frame with polyester filter medium.

Permanent Filters - Permanent filters are available.

Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security con- cerns, burglar bars are available for the duct openings of the roof curbs.

Roof Curb Transition - Single Piece Adapter (10” High) - Roof curbs for transitioning from Sunline™ units to Pred- ator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.

Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.

Thermostat - The units are designed to operate with 24- volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two- stage heat/two-stage cool or two-stage cooling only ther- mostats, depending upon unit configuration.

REHEAT MODE SEQUENCE OF OPERATION

The reheat control board allows the user to select two differ- ent modes of operation via a jumper connection on the board. (See Figure 3.) Each mode is described below. Refer to Figures 3 - 5 when reading this section.

“NORMAL” MODE

When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for cooling, it energizes the hot gas relay (HGR), which energizes the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and de-energizes the reheat coil bleed valve (SOL 1). (In the DR150, SOL 2 is only energized when the discharge pressure in circuit #1 rises above 235 psig and de- energizes SOL 2 after the discharge pressure falls below 175 psig. Both outdoor fans of circuit #1 in the DR150 also disen- gage to conserve energy.) The Y1 signal is passed to the unit control board (UCB), which engages circuit # 1, resulting in circuit #1 reheat mode operation.

When the room thermostat calls for first stage cooling, with or without a call for dehumidification, the RCB senses a signal through "Y1", de-energizing the HGR, which de-energizes SOL 3 and SOL 2 and energizes SOL 1, engaging circuit #1, resulting in circuit #1 cooling mode operation.

Unitary Products Group

9

Image 9
Contents DESCRIPTION MagnaDRYTECHNICAL GUIDELIST OF FIGURES TABLE OF CONTENTSLIST OF TABLES 246721-YTG-C-060616 ELECTRICAL DATA DR150 W/PWRD 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 1 - PREDATOR MagnaDRY DR090FEATURES FIGURE 2 - PREDATOR MagnaDRY DR150246721-YTG-C-0606 246721-YTG-C-0606 FACTORY INSTALLED OPTIONSUnitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 FIELD INSTALLED ACCESSORIES246721-YTG-C-0606 REHEAT MODE SEQUENCE OF OPERATIONFIGURE 3 - REHEAT CONTROL BOARD ALTERNATE” MODE246721-YTG-C-0606 FIGURE 4 - DR090 & 120 REHEAT CONTROLS 246721-YTG-C-0606Unitary Products Group 246721-YTG-C-0606 FIGURE 5 - DR150 REHEAT CONTROLS246721-YTG-C-0606 TABLE 1 ACCESSORIES7.5-12.5Ton York Model Number Nomenclature NOMENCLATURED R 090 N10 A 2 A AA 3 0 1 2 4 A 246721-YTG-C-0606246721-YTG-C-0606 TABLE 2 PHYSICAL DATATABLE 3 DR CAPACITY RATINGS POWER RATINGTABLE 4 UNIT VOLTAGE LIMITATIONS 246721-YTG-C-0606TABLE 5 COOLING CAPACITY DR090 UNIT 246721-YTG-C-0606Unitary Products Group Air On Evap. Coil 246721-YTG-C-0606TABLE 7 COOLING CAPACITY DR120 UNIT 246721-YTG-C-0606Unitary Products Group Air On Evap 246721-YTG-C-0606TABLE 9 COOLING CAPACITY DR150 UNIT 246721-YTG-C-0606Unitary Products Group 10.7 246721-YTG-C-0606indoor dry bulb / wet bulb conditions 246721-YTG-C-0606 FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODEDR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS DR 090 Standard Drive Assembly Side Flow TABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW246721-YTG-C-0606 DR 090 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer DR 090 Optional Drive Assembly Down Flow DR 090 Standard Drive Assembly Down FlowTABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW 246721-YTG-C-0606246721-YTG-C-0606 DR 090 Standard Drive Assembly Down FlowTABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOW 246721-YTG-C-0606Unitary Products Group Volumetric DR120 Standard Drive Assembly Side FlowVolumetric 246721-YTG-C-0606TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOW 246721-YTG-C-0606Unitary Products Group DR 120 Optional Drive Assembly Down Flow DR 120 Standard Drive Assembly Down Flow246721-YTG-C-0606 100% Return EconomizerDR150 Optional Drive Assembly Side Flow DR150 Standard Drive Assembly Side FlowTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW 246721-YTG-C-0606DR150 Optional Drive Assembly Side Flow 246721-YTG-C-0606100% Return Economizer TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOW 246721-YTG-C-0606Unitary Products Group 100% Return Economizer 246721-YTG-C-0606TABLE 33 POWER EXHAUST SPECIFICATIONS TABLE 32 INDOOR BLOWER SPECIFICATIONSTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD FIGURE 18 - DR090/120 UNIT DIMENSIONS TABLE 36 UNIT WEIGHT246721-YTG-C-0606 See Detail ADETAIL A FIGURE 19 - DR150 UNIT DIMENSIONSDETAIL B TABLE 37 UNIT CLEARANCESFRONT 8or14 RIGHT246721-YTG-C-0606 2TYP31-11/162-31/32 18-1/45-5/3218-1/4 246721-YTG-C-0606FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL FIGURE 24 - DR150 REAR DUCT DIMENSIONS246721-YTG-C-0606 Dot Plugs 18-1/4 Return Air28-1/4 Supply AirFIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL TABLE 38 ECONOMIZER USAGE246721-YTG-C-0606 FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER 246721-YTG-C-0606Unitary Products Group 2EE04705524 Return Air Damper Field Installed Power Exhaust 1EH0409 Fresh Air Hood Field Installed Duct Work246721-YTG-C-0606 2EE04705X24 Slab Economizer 1EH0409246721-YTG-C-0606 FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRINGTYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CTHREE PHASE POWER SUPPLY SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWERUnitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products Group 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAMFIGURE 42 - DR150 REHEAT WIRING DIAGRAM 246721-YTG-C-0606Unitary Products Group PREDATOR MagnaDRY DR GUIDE SPECIFICATIONSGENERAL DESCRIPTION246721-YTG-C-0606 UNIT OPERATING CHARACTERISTICSGAS HEATING SECTION IF EQUIPPED ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS