York DR090, DR120, DR150 manual Additional Factory Installed Options

Page 64
ADDITIONAL FACTORY INSTALLED OPTIONS

outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy con- trol that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief or power exhaust.

2.MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and posi- tioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventila- tion requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi- tions – regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

ADDITIONAL FACTORY INSTALLED OPTIONS

ALTERNATE INDOOR BLOWER MOTOR – For appli- cations with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.

CONVENIENCE OUTLET (POWERED/NON-POW- ERED) – Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.

ELECTRIC HEAT - Electric Heaters range from 9 kW to 54 kW and are available in all the voltage options of the base unit.

PHASE MONITOR - Designed to prevent damage in out- of-phase condition.

COIL GUARD - Designed to prevent condenser coil damage.

BAS CONTROLS - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.

DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high- pressure drop across the filters.

BREAKER – An HACR breaker can be factory installed on gas heat units or cooling units with electric heat.

DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest elec- tric heat available.

STAINLESS STEEL HEAT EXCHANGER – For applica- tions in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.

STAINLESS STEEL DRAIN PAN - Provides years of trouble free operation in corrosive environments.

SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air com- partments.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.

BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.

PROPANE CONVERSION KIT – Contains new orifices and gas valve springs to convert from natural to L.P. gas.

60 ºF GAS HEAT KIT – Provides an electric heat kit for the gas compartment for use in extreme low ambient conditions.

ECONOMIZER (Downflow and Horizontal flow)

POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow)

DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.

Subject to change without notice. Printed in U.S.A.246721-YTG-C-0606 Copyright © 2006 by Unitary Products Group . All rights reserved. Supersedes: 246721-YTG-B-0305/036-21551-001-B-0305

Unitary

5005

Norman

Products

York

OK

Group

Drive

73069

Image 64
Contents MagnaDRY DESCRIPTIONTECHNICAL GUIDETABLE OF CONTENTS LIST OF FIGURESLIST OF TABLES 246721-YTG-C-0606246721-YTG-C-0606 16 ELECTRICAL DATA DR150 W/PWRDFIGURE 1 - PREDATOR MagnaDRY DR090 246721-YTG-C-0606FIGURE 2 - PREDATOR MagnaDRY DR150 FEATURES246721-YTG-C-0606 FACTORY INSTALLED OPTIONS 246721-YTG-C-0606246721-YTG-C-0606 Unitary Products GroupFIELD INSTALLED ACCESSORIES 246721-YTG-C-0606REHEAT MODE SEQUENCE OF OPERATION 246721-YTG-C-0606ALTERNATE” MODE FIGURE 3 - REHEAT CONTROL BOARD246721-YTG-C-0606 246721-YTG-C-0606 FIGURE 4 - DR090 & 120 REHEAT CONTROLSUnitary Products Group FIGURE 5 - DR150 REHEAT CONTROLS 246721-YTG-C-0606TABLE 1 ACCESSORIES 246721-YTG-C-0606NOMENCLATURE 7.5-12.5Ton York Model Number NomenclatureD R 090 N10 A 2 A AA 3 0 1 2 4 A 246721-YTG-C-0606TABLE 2 PHYSICAL DATA 246721-YTG-C-0606POWER RATING TABLE 3 DR CAPACITY RATINGSTABLE 4 UNIT VOLTAGE LIMITATIONS 246721-YTG-C-0606246721-YTG-C-0606 TABLE 5 COOLING CAPACITY DR090 UNITUnitary Products Group 246721-YTG-C-0606 Air On Evap. Coil246721-YTG-C-0606 TABLE 7 COOLING CAPACITY DR120 UNITUnitary Products Group 246721-YTG-C-0606 Air On Evap246721-YTG-C-0606 TABLE 9 COOLING CAPACITY DR150 UNITUnitary Products Group 246721-YTG-C-0606 10.7indoor dry bulb / wet bulb conditions FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE 246721-YTG-C-0606DR150 Moisture Removal @ 5000cfm Compressors Unitary Products Group TABLE 17 ELECTRIC HEAT MULTIPLIERS TABLE 18 BLOWER PERFORMANCE DR090 SIDEFLOW DR 090 Standard Drive Assembly Side Flow246721-YTG-C-0606 246721-YTG-C-0606 DR 090 Optional Drive Assembly Side Flow100% Return Economizer DR 090 Standard Drive Assembly Down Flow DR 090 Optional Drive Assembly Down FlowTABLE 20 BLOWER PERFORMANCE DR090 DOWNFLOW 246721-YTG-C-0606DR 090 Standard Drive Assembly Down Flow 246721-YTG-C-0606246721-YTG-C-0606 TABLE 22 BLOWER PERFORMANCE DR120 SIDEFLOWUnitary Products Group DR120 Standard Drive Assembly Side Flow VolumetricVolumetric 246721-YTG-C-0606246721-YTG-C-0606 TABLE 24 BLOWER PERFORMANCE DR120 DOWNFLOWUnitary Products Group DR 120 Standard Drive Assembly Down Flow DR 120 Optional Drive Assembly Down Flow246721-YTG-C-0606 100% Return EconomizerDR150 Standard Drive Assembly Side Flow DR150 Optional Drive Assembly Side FlowTABLE 26 BLOWER PERFORMANCE DR150 SIDEFLOW 246721-YTG-C-0606246721-YTG-C-0606 DR150 Optional Drive Assembly Side Flow100% Return Economizer 246721-YTG-C-0606 TABLE 28 BLOWER PERFORMANCE DR150 DOWNFLOWUnitary Products Group 246721-YTG-C-0606 100% Return EconomizerTABLE 32 INDOOR BLOWER SPECIFICATIONS TABLE 33 POWER EXHAUST SPECIFICATIONSTABLE 30 ADDITIONAL STATIC RESISTANCE TABLE 31 ELECTRIC HEAT MINIMUM SUPPLY AIR CFMFIGURE 12 - DR090, 120 UNITS 4 POINT LOAD TABLE 36 UNIT WEIGHT FIGURE 18 - DR090/120 UNIT DIMENSIONS246721-YTG-C-0606 See Detail AFIGURE 19 - DR150 UNIT DIMENSIONS DETAIL ADETAIL B TABLE 37 UNIT CLEARANCESRIGHT FRONT 8or14246721-YTG-C-0606 2TYP18-1/45-5/32 31-11/162-31/3218-1/4 246721-YTG-C-0606FIGURE 24 - DR150 REAR DUCT DIMENSIONS FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 Dot Plugs 18-1/4 Return Air28-1/4 Supply AirTABLE 38 ECONOMIZER USAGE FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL246721-YTG-C-0606 246721-YTG-C-0606 FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZERUnitary Products Group 2EE04705524 Return Air Damper Field Installed 1EH0409 Fresh Air Hood Field Installed Duct Work Power Exhaust246721-YTG-C-0606 2EE04705X24 Slab Economizer 1EH0409FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING 246721-YTG-C-0606TYPICAL THERMOSTAT RC RH Y1 Y2 G W1 W2 C R Y1 Y2 RCB GREHEAT CONTROL W1 BOARD W2 OCC CSUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER THREE PHASE POWER SUPPLYUnitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products Group246721-YTG-C-0606 246721-YTG-C-0606 Unitary Products GroupFIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM 246721-YTG-C-0606246721-YTG-C-0606 FIGURE 42 - DR150 REHEAT WIRING DIAGRAMUnitary Products Group GUIDE SPECIFICATIONS PREDATOR MagnaDRY DRGENERAL DESCRIPTIONUNIT OPERATING CHARACTERISTICS 246721-YTG-C-0606GAS HEATING SECTION IF EQUIPPED ELECTRIC HEATING SECTION IF EQUIPPEDADDITIONAL FACTORY INSTALLED OPTIONS