ECONOMIZER AND POWER EXHAUST SET POINT ADJUSTMENTS AND INFORMATION

Remove the top rear access panel from the unit. Locate the economizer control module, where the following adjustments will be made.

Extreme care must be exercised in turning all set point, maximum and minimum damper positioning adjustment screws to prevent twisting them off.

MINIMUM POSITION ADJUSTMENT

Check that the damper blades move smoothly with bind- ing; carefully turn the Minimum Position Adjust screw (found on the damper control module) fully clockwise and then set the thermostat indoor fan switch to the ON position and then OFF or energize and de-energize ter- minals “R” to “G”.

With the thermostat set to the indoor fan ON position or terminals “R” to “G” energized, turn the Minimum Posi- tion Adjusting screw (located on the damper control module) counterclockwise until the desired minimum damper position has been attained.

ENTHALPY SET POINT ADJUSTMENT

The enthalpy set point may now be set by selecting the desired set point shown in the Enthalpy Set Point Adjustment Figure 22. Adjust as follows:

For a single enthalpy operation carefully turn the set point adjusting screw (found on the damper control mod- ule) to the "A", "B", "C" or "D" setting corresponding to the lettered curve of the Enthalpy Set Point Adjustment Figure 22.

For a dual enthalpy operation, carefully turn the set point adjusting screw fully clockwise past the "D" setting.

POWER EXHAUST DAMPER SET POINT (WITH OR WITH- OUT POWER EXHAUST)

With no power exhaust option, adjust the Exhaust Air Adjustment Screw fully clockwise. This will allow 2nd stage cooling to operate.

With power exhaust option, each building pressurization requirement will be different. The point at which the power exhaust comes on is determined by the econo- mizer damper position (Percent Open). The Exhaust Air Adjustment Screw should be set at the Percent Open of the economizer damper at which the power exhaust is needed. It can be set from 0 to 100% damper open.

INDOOR AIR QUALITY AQ

Indoor Air Quality (indoor sensor input): Terminal AQ accepts a +2 to +10 Vdc signal with respect to the (AQ1) terminal. When the signal is below it's set point, the actuator is allowed to modulate normally in accordance with the enthalpy and mixed air sensor inputs. When the AQ signal exceeds it's set point setting and there is no call for free cooling, the actuator is proportionately modulated from the 2 to 10 Vdc signal, with 2 Vdc corresponding to full closed and 10 Vdc corresponding to full open. When there is no call for free cooling, the damper position is limited by the IAQ Max damper position setting. When the signal exceeds it's set point (Demand Control Ven- tilation Set Point) setting and there is a call for free cooling, the actuator modulates from the minimum position to the full open position based on the highest call from either the mixed air sensor input or the AQ voltage input.

Optional CO2 Space Sensor Kit Part # 2AQ04700324

Optional CO2 Sensor Kit Part # 2AQ04700424 Replace the top rear access panel on the unit.

26

Unitary Products Group

Image 26
Contents Installation Manual Table of Contents List of Figures List of TablesInspection Safety ConsiderationsGeneral Renewal Parts ReferenceApprovals 12½ Ton Predator Model Number Nomenclature 150 N15 NomenclatureNOMENCLATURE, Additional Options Preceding Installation InstallationInstallation Safety Information Compressor Section LimitationsPREDATOR Magnum Component Location Rigging and Handling Unit Temperature LimitationsUnit Voltage Limitations LocationClearances Unit WeightsPoint Load Weight Unit Dimensions Detail CBottom Duct Openings from Above Rear Duct Dimensions Ductwork Duct CoversPREDATOR Magnum Roof Curb Dimensions Power and Control Wiring Thermostat WiringControl Wire Sizes FiltersPower Wiring Detail Electronic Thermostat Field WiringField Wiring 24 Volt Thermostat Contactor 1M Factory or Field Ground MCA Minimum Supply AIR CFM Physical DataOptional Electric Heat GAS Piping Optional GAS HeatGAS Heat Application Data GAS Connection LP UNITS, Tanks and PipingFactory Installed Options Field Installed Accessories Indoor AIR Quality AQ Minimum Position AdjustmentEnthalpy SET Point Adjustment Enthalpy SET Point Chart Supply AIR Limitations PhasingBlower Rotation Belt TensionTurns Open ESP‡ CFM BHP Blower performance includes dry coil and two-inch Checking AIR Quantity Indoor Blower SpecificationsAIR Balance Method ONEDRY Coil Delta P Supply AIR Drive Adjustment Motor Sheave Datum Diameters OperationAdditional Static Resistance Cooling Sequence of OperationHIGH-PRESSURE Limit Switch Economizer Single or Dual with Power ExhaustCooling Operation Errors No Outdoor AIR OptionsSafety Controls Compressor ProtectionElectric Heating Sequence of Operations Electric Heating Operation ErrorsElectric Heat Limit Setting Electric Heat Anticipator SetpointsIgnition Control Board GAS Heating Operation ErrorsGAS Heating Sequence of Operations GAS Heat Limit Control Settings START-UP Cooling START-UP GAS HeatShut Down Post Start ChecklistManifold GAS Pressure Adjustment Checking GAS InputGAS Rate Cubic Feet PER Hour Adjustment of Temperature Rise BURNERS/ORIFICES INSPECTION/SERVICINGPREDATOR Magnum Flash Codes TroubleshootingCharging the Unit Unit Control Board Flash CodesBasic Troubleshooting Flowchart Trip Failure Flow Chart Cooling Troubleshooting Guide Unitary Products Group 035-19046-002-B-0104 GAS Heat Troubleshooting Guide Unitary Products Group 035-19046-002-B-0104 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069

DJ150 specifications

The York DJ150 is a standout model in the world of portable DJ equipment, designed to cater to both budding DJs and seasoned professionals. Its sleek and compact form factor makes it highly portable, allowing for easy transporting to gigs, parties, or personal events.

One of the main features of the DJ150 is its user-friendly interface, which includes a simplified control layout. This design boils down essential functions into accessible buttons and knobs, enabling DJs to focus on their mixes without distractions. The large jog wheels are not only responsive but also provide precision when scratching and cueing tracks, making it a joy to use for both live performances and practice sessions.

In terms of sound quality, the York DJ150 is equipped with high-performance audio circuitry. It ensures that sound clarity is maintained, with a dynamic range that captures the intricacies of music. The device supports multiple audio formats, offering versatility for DJs that work with various types of digital music files.

The DJ150 integrates advanced technologies that facilitate seamless mixing and creative expression. With features such as built-in sound effects, loops, and samples, DJs can add their personal touch to sets. Additionally, the model includes an intelligent beat matching function which automatically syncs the tempo of different tracks, allowing for smooth transitions and uninterrupted flow.

Connectivity is another strong point for the York DJ150. It offers multiple input and output options, including USB ports for quick connections to a laptop or external devices, line inputs for instruments or microphones, and headphones output for monitoring. This ensures that users can connect a wide range of equipment while maintaining a clean setup.

Durability plays a key role in the DJ150's design, as it is built to withstand the rigors of frequent use. Its robust construction and quality materials contribute to its longevity, appealing to those who value reliable gear.

In conclusion, the York DJ150 represents a versatile solution for DJs seeking a blend of portability, functionality, and sound quality. Its comprehensive features and professional-grade technologies position it as a strong contender in the DJ equipment market, making it suitable for performances of all levels. Whether you are a novice starting your DJ journey or a seasoned pro looking for an efficient tool, the DJ150 ticks all the boxes.