TABLE 8: ELECTRICAL DATA - 7-1/2 TON HP
|
|
| OD | Supply Air | Pwr |
|
|
|
|
| MCA |
| Max Fuse | Max Fuse Size | ||||
|
|
|
|
|
| Minimum Circuit | with Power | |||||||||||
| Compressors | Fan | BLower | Exh |
|
|
| Size* | w/Pwr. Exh.* | |||||||||
|
|
|
| Exhaust | ||||||||||||||
Voltage |
|
| Motors | Motor FLA | Motor | Electric Heater | Actual | Heater | Ampacity (Amps) | (Amps) | (Amps) | |||||||
|
| (Amps) | ||||||||||||||||
|
|
|
|
|
|
| Model No. | Kw | Amps |
|
|
|
|
|
|
|
|
|
| RLA | LRA | FLA | 1.5 HP | 2 HP | FLA |
|
|
| 1.5 HP | 2 HP | 1.5 HP |
| 2 HP | 1.5 HP | 2 HP | 1.5 HP | 2 HP |
| ea | ea | ea | (1.1 kW) | (1.5 kW) |
|
|
| (1.1 kW) | (1.5 kW) | (1.1 kW) | (1.5 kW) | (1.1 kW) | (1.5 kW) | (1.1 kW) | (1.5 kW) | ||
|
|
|
|
|
|
| None | - | - | 25.2 | 26.1 | 27.4 |
| 28.3 | 30 | 30 | 35 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2TP04520950 | 5.6 | 8.5 | 35.8 | 36.7 | 38.0 |
| 38.9 | 40 | 40 | 40 | 45 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
380 | 8.3 | 62 | 1.1 | 4.3 | 5.2 | 2.2 | 2TP04521850 | 11.3 | 17.2 | 46.6 | 47.5 | 48.8 |
| 49.7 | 50 | 50 | 50 | 50 |
|
|
|
|
|
|
| 2TP04522450 | 15.0 | 22.8 | 53.7 | 54.6 | 55.9 |
| 56.8 | 60 | 60 | 60 | 60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2TP04523650 | 21.3 | 32.4 | 65.6 | 66.5 | 67.8 |
| 68.7 | 70 | 70 | 70 | 70 |
|
|
|
|
|
|
| None | - | - | 25.2 | 26.1 | 27.4 |
| 28.3 | 30 | 30 | 35 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2TP04520950 | 6.7 | 9.3 | 36.8 | 37.7 | 39.0 |
| 39.9 | 40 | 40 | 40 | 45 |
415 | 8.3 | 62 | 1.1 | 4.3 | 5.2 | 2.2 | 2TP04521850 | 13.5 | 18.8 | 48.7 | 49.6 | 50.9 |
| 51.8 | 50 | 50 | 60 | 60 |
|
|
|
|
|
|
| 2TP04522450 | 17.9 | 24.9 | 56.3 | 57.2 | 58.5 |
| 59.4 | 60 | 60 | 60 | 60 |
|
|
|
|
|
|
| 2TP04523650 | 25.4 | 35.3 | 69.3 | 70.2 | 71.5 |
| 72.4 | 70 | 80 | 80 | 80 |
*. Maximum HACR breaker of the same amp size is acceptable.
TABLE 9: ELECTRICAL DATA - 10 TON HP
|
|
| OD | Supply Air | Pwr |
|
|
|
|
| MCA | Max Fuse | Max Fuse Size | ||||
|
|
|
|
|
| Minimum Circuit | with Power | ||||||||||
| Compressors | Fan | BLower | Exh |
|
|
| Size* | w/Pwr. Exh.* | ||||||||
|
|
|
| Exhaust | |||||||||||||
Voltage |
|
| Motors | Motor FLA | Motor | Electric Heater | Actual | Heater | Ampacity (Amps) | (Amps) | (Amps) | ||||||
|
| (Amps) | |||||||||||||||
|
|
|
|
|
|
| Model No. | Kw | Amps |
|
|
|
|
|
|
|
|
| RLA | LRA | FLA | 2 HP | 4HP | FLA |
|
|
| 2 HP | 4 HP | 2 HP | 4 HP | 2 HP | 4 HP | 2 HP | 4 HP |
| ea | ea | ea | (1.5 kW) | (3 kW) |
|
|
| (1.5 kW) | (3 kW) | (1.5 kW) | (3 kW) | (1.5 kW) | (3 kW) | (1.5 kW) | (3 kW) | |
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
| None | 25.6 | 27.9 | 27.8 | 30.1 | 30 | 35 | 35 | 35 | ||
|
|
|
|
|
|
| 2TP04521850 | 11.3 | 17.2 | 47.1 | 49.4 | 49.3 | 51.6 | 50 | 50 | 50 | 60 |
380 | 8.1 | 73.0 | 1.1 | 5.2 | 7.5 | 2.2 | 2TP04522450 | 15.0 | 22.8 | 54.1 | 56.4 | 56.3 | 58.6 | 60 | 60 | 60 | 60 |
|
|
|
|
|
|
| 2TP04523650 | 21.3 | 32.4 | 66.1 | 68.4 | 68.3 | 70.6 | 70 | 70 | 70 | 80 |
|
|
|
|
|
|
| 2HP04535450† | 33.8 | 51.4 | 70.7 | 73.6 | 73.4 | 76.3 | 80 | 80 | 80 | 80 |
|
|
|
|
|
|
| None | 25.6 | 27.9 | 27.8 | 30.1 | 30 | 35 | 35 | 35 | ||
|
|
|
|
|
|
| 2TP04521850 | 13.5 | 18.8 | 49.1 | 51.4 | 51.3 | 53.6 | 50 | 60 | 60 | 60 |
415 | 8.1 | 73.0 | 1.1 | 5.2 | 7.5 | 2.2 | 2TP04522450 | 17.9 | 24.9 | 56.8 | 59.1 | 59.0 | 61.3 | 60 | 60 | 60 | 70 |
|
|
|
|
|
|
| 2TP04523650 | 25.4 | 35.3 | 69.8 | 72.1 | 72.0 | 74.3 | 70 | 80 | 80 | 80 |
|
|
|
|
|
|
| 2HP04535450† | 40.4 | 56.2 | 76.8 | 79.6 | 79.5 | 82.4 | 80 | 80 | 80 | 90 |
*. Maximum HACR breaker of the same amp size is acceptable.
†.Only 25.4 kW of electric heat can be simultaneously energized with the mechanical heating. The full 40.4 kW operates only if both compressors are locked out.
18 | Unitary Products Group |