Page 11
In inches and millimeters, in.(mm).

66307-YIM-B-0606

CLEARANCES

All units require particular clearances for proper operation and service. Refer to Table 6 for clearances required for con- struction, servicing, and proper unit operation.

Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets.

30-11/32

50-3/4 (770)

(1290)

Power Entry Ø2-1/2 (65)

4-1/4

(110)

 

30-3/16

17-3/16

 

(435)

 

 

(765)

 

 

 

6-3/16

59

24-3/16

(1500)

(615)

(155)

LEFT

Control

Entry Ø7/8 (22)

Power Entry Ø2-1/2 (65)

Convenience

Power

Outlet

Entry

Ø7/8

(22)

ForDrain

Dimensions

SeeDetailB

27 89

(685)(2260)

ForBaserail

FRONT Dimensions

SeeDetailA

FIGURE 8 - UNIT DIMENSIONS

NOTE:(xxx)indicatesdimensions

giveninmilimeters

TABLE 6: UNIT CLEARANCES *

Top

72 (1830)

Right

12 (305)

Front

36 (915)

Left

36 (915)

Rear

36 (915)

Bottom**

0 (0)

*.

†.Units must be installed outdoors. Overhanging structure or shrubs should not obstruct condenser air discharge outlet.

‡.To remove the slide-out drain pan, a rear clearance of 60” (1525 mm) is required. If space is unavailable, the drain pan can be removed through the front by separating the corner wall.

**. Units may be installed on combustible floors.

NOTE: A one-inch clearance must be provided between any combustible material and the supply ductwork for a distance of 3 feet from the unit.

DETAIL A

2-3/8

 

 

(60)

3-3/4

(95)

3-9/16

(90)

DETAIL B

5-3/8

(135)

Unitary Products Group

11

Image 11
Contents Single Package Heat Pump High Efficiency Installation Manual 50 HzTable of Contents List of Figures List of Tables Inspection Safety ConsiderationsGeneral Approvals ReferenceRenewal Parts Nomenclature Ton York Model Number NomenclaturePreceding Installation InstallationInstallation Safety Information Location Unit Voltage LimitationsRigging and Handling Unit WeightsPoint Load Weight Detail B ClearancesUnit Clearances BttomPower Rear Duct Dimensions Ductwork Duct Covers Predator Roof Curb Dimensions Filters Thermostat WiringControl Wire Sizes CompressorsElectronic Thermostat Field Wiring Power Wiring DetailGroundlug Electrical Data 10 TON HP Electrical Data 7-1/2 TON HPElectric Heat Option Factory Installed Options Field Installed AccessoriesElectric Heat Accessory Physical DataElectric Heat Minimum Supply AIR Indoor AIR Quality AQ Enthalpy SET Point ChartBelt Tension Blower RotationSupply AIR Limitations Belt Adjustment Blower Performance 7-1/2 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct ImperialBlower Performance 10 TON Optional Motor Side Duct Metric Blower Performance 10 TON Optional Motor Side Duct ImperialBlower Performance 7-1/2 TON Standard Motor Downshot Metric Blower Performance 10 TON Standard Motor Downshot Metric Blower Performance 7-1/2 TON Optional Motor Downshot MetricBlower Performance 10 TON Standard Motor Downshot Imperial Blower Performance 10 TON Optional Motor Downshot Metric Indoor Blower SpecificationsBlower Performance 10 TON Optional Motor Downshot Imperial Method TWO AIR BalanceChecking AIR Quantity Method ONEDRY Coil Delta P Supply AIR Drive AdjustmentM3S Additional Static Resistance ImperialAdditional Static Resistance Metric CFMCooling Sequence of Operation OperationMotor Sheave Datum Sequence of Operations OverviewCooling Operation Errors Heating Sequence of Operation Safety ControlsReset Compressor ProtectionSTART-UP Superheat Charging Method Operating InstructionsPost Start Check List Cooling Superheat 7-1/2 TON Superheat ChargingPredator Flash Codes TroubleshootingCooling Superheat 10 TON Unit Control Board Unit Control Board Flash CodesCooling Troubleshooting Guide Page Page Unitary 5005 Norman Products York Group Drive 73069