Procedure for adjusting belt tension:

1.Loosen six nuts (top and bottom) A.

2.Adjust by turning (B).

3.Never loosen nuts (C).

4.Use belt tension checker to apply a perpendicular force to one belt at the midpoint of the span as shown. Deflection distance of 4mm (5/32”) is obtained.

To determine the deflection distance from normal position, use a straight edge from sheave to sheave as reference line. The recommended deflection force is as follows:

Tension new belts at the max. deflection force rec- ommended for the belt section. Check the belt ten- sion at least two times during the first 24 hours of operation. Any retensioning should fall between the min. and max. deflection force values.

5. After adjusting retighten nuts (A).

Unitary Products Group

23

Image 23
Contents Single Package Heat Pump High Efficiency Installation Manual 50 HzTable of Contents List of Figures List of Tables Inspection Safety ConsiderationsGeneral Approvals ReferenceRenewal Parts Nomenclature Ton York Model Number NomenclaturePreceding Installation InstallationInstallation Safety Information Location Unit Voltage LimitationsRigging and Handling Unit WeightsPoint Load Weight Detail B ClearancesUnit Clearances BttomPower Rear Duct Dimensions Ductwork Duct Covers Predator Roof Curb Dimensions Filters Thermostat WiringControl Wire Sizes CompressorsElectronic Thermostat Field Wiring Power Wiring DetailGroundlug Electrical Data 10 TON HP Electrical Data 7-1/2 TON HPElectric Heat Option Factory Installed Options Field Installed AccessoriesElectric Heat Accessory Physical DataElectric Heat Minimum Supply AIR Indoor AIR Quality AQ Enthalpy SET Point ChartBelt Tension Blower RotationSupply AIR Limitations Belt Adjustment Blower Performance 7-1/2 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct ImperialBlower Performance 10 TON Optional Motor Side Duct Metric Blower Performance 10 TON Optional Motor Side Duct ImperialBlower Performance 7-1/2 TON Standard Motor Downshot Metric Blower Performance 10 TON Standard Motor Downshot Metric Blower Performance 7-1/2 TON Optional Motor Downshot MetricBlower Performance 10 TON Standard Motor Downshot Imperial Blower Performance 10 TON Optional Motor Downshot Metric Indoor Blower SpecificationsBlower Performance 10 TON Optional Motor Downshot Imperial Method TWO AIR BalanceChecking AIR Quantity Method ONEDRY Coil Delta P Supply AIR Drive AdjustmentM3S Additional Static Resistance ImperialAdditional Static Resistance Metric CFMCooling Sequence of Operation OperationMotor Sheave Datum Sequence of Operations OverviewCooling Operation Errors Heating Sequence of Operation Safety ControlsReset Compressor ProtectionSTART-UP Superheat Charging Method Operating InstructionsPost Start Check List Cooling Superheat 7-1/2 TON Superheat ChargingPredator Flash Codes TroubleshootingCooling Superheat 10 TON Unit Control Board Unit Control Board Flash CodesCooling Troubleshooting Guide Page Page Unitary 5005 Norman Products York Group Drive 73069