York BP120, BP 090 Physical Data, Factory Installed Options Field Installed Accessories

Page 19

66307-YIM-B-0606

TABLE 10: PHYSICAL DATA

 

Component

Models

 

 

 

 

090

120

 

 

 

 

 

 

Evaporator

Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm)

15 x 15 (381 x 381)

15 x 15 (381 x 381)

 

 

 

Motor, Standard HP (kW)

1-1/2 (1.1)

2 (1.5)

Blower

 

 

 

 

Motor, Optional HP (kW)

2 (1.5)

4 (3)

 

 

 

 

 

Rows

3

4

 

 

 

 

Evaporator Coil

Fins per Inch (2.54 cm.)

15

15

 

 

 

Height in. (mm)

40 (1020)

40 (1020)

 

 

 

 

 

 

Face Area ft.2 each (m2)

13.2 (1.23)

13.2 (1.23)

Condenser Fan

Propeller Dia. in., each (mm)

24 (610)

24 (610)

 

 

 

Motor HP, each (kW)

3/4 (.56)

3/4 (.56)

(2 per Unit)

 

 

 

 

CFM, Nominal (each)

4000

4000

 

 

 

 

 

Rows (each)

1

2

 

 

 

 

Condenser Coil

Fins per Inch (2.54 cm)

20

20

 

 

 

(2 per unit)

Height in., each (mm)

44 (1120)

44 (1120)

 

 

 

 

 

Face Area ft.2 each (mm)

14.5 (1.35)

14.5 (1.35)

Refrigerant

System 1 lb./oz. (kg)

9 lbs. 4 oz. (4.20)

15 lbs. 4 oz. (6.92)

Charge

 

 

 

System 2 lb./oz. (kg)

9 lbs. 0 oz. (4.06)

15 lbs. 0 oz. (6.80)

 

 

 

 

Compressors

Quantity

2

2

 

 

 

Type

Recip

Scroll

 

 

 

 

 

 

Size Wd. x Ht. x Thickness in. (Wd. x Ht x Thickness

25x20x2

25x20x2

Air Filters

mm)

(635 x 508 x 51)

(635 x 508 x 51)

 

Number Per Unit

4

4

 

 

 

 

FACTORY INSTALLED OPTIONS/

FIELD INSTALLED ACCESSORIES

ELECTRIC HEAT ACCESSORY

Electric heaters are available as field installed accessories. Refer to electric heat instructions for installation. These heat- ers mount in the heat compartment with the heating elements extending into the supply air chamber. All electric heaters are fused and intended for use with single point power supply.

ELECTRIC HEAT OPTION

The factory-installed heaters are wired for single point power supply. Power supply need only be brought into the single point terminal block.

These CSA approved heaters are located within the central compartment of the unit with the heater elements extending into the supply air chamber.

Fuses are supplied, where required, by the factory. Some kW sizes require fuses and other do not. Refer to Table 11 for minimum CFM limitations and to Tables 8 and 9 for electrical data.

Unitary Products Group

19

Image 19
Contents Single Package Heat Pump High Efficiency Installation Manual 50 HzTable of Contents List of Figures List of Tables General Safety ConsiderationsInspection Renewal Parts ReferenceApprovals Nomenclature Ton York Model Number NomenclatureInstallation Safety Information InstallationPreceding Installation Location Unit Voltage LimitationsPoint Load Weight Unit WeightsRigging and Handling Unit Clearances ClearancesDetail B BttomPower Rear Duct Dimensions Ductwork Duct Covers Predator Roof Curb Dimensions Filters Thermostat WiringControl Wire Sizes CompressorsElectronic Thermostat Field Wiring Power Wiring DetailGroundlug Electrical Data 10 TON HP Electrical Data 7-1/2 TON HPElectric Heat Option Factory Installed Options Field Installed AccessoriesElectric Heat Accessory Physical DataElectric Heat Minimum Supply AIR Indoor AIR Quality AQ Enthalpy SET Point ChartSupply AIR Limitations Blower RotationBelt Tension Belt Adjustment Blower Performance 7-1/2 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct ImperialBlower Performance 10 TON Optional Motor Side Duct Metric Blower Performance 10 TON Optional Motor Side Duct ImperialBlower Performance 7-1/2 TON Standard Motor Downshot Metric Blower Performance 10 TON Standard Motor Downshot Imperial Blower Performance 7-1/2 TON Optional Motor Downshot MetricBlower Performance 10 TON Standard Motor Downshot Metric Blower Performance 10 TON Optional Motor Downshot Imperial Indoor Blower SpecificationsBlower Performance 10 TON Optional Motor Downshot Metric Method TWO AIR BalanceChecking AIR Quantity Method ONEDRY Coil Delta P Supply AIR Drive AdjustmentM3S Additional Static Resistance ImperialAdditional Static Resistance Metric CFMCooling Sequence of Operation OperationMotor Sheave Datum Sequence of Operations OverviewCooling Operation Errors Heating Sequence of Operation Safety ControlsReset Compressor ProtectionSTART-UP Post Start Check List Operating InstructionsSuperheat Charging Method Cooling Superheat 7-1/2 TON Superheat ChargingCooling Superheat 10 TON TroubleshootingPredator Flash Codes Unit Control Board Unit Control Board Flash CodesCooling Troubleshooting Guide Page Page Unitary 5005 Norman Products York Group Drive 73069