York BP120, BP 090 installation manual Enthalpy SET Point Chart, Indoor AIR Quality AQ

Page 21

66307-YIM-B-0606

For a dual enthalpy operation, carefully turn the set point adjusting screw fully clockwise past the "D" setting.

POWER EXHAUST DAMPER SET POINT (WITH OR WITH- OUT POWER EXHAUST)

With no power exhaust option, adjust the Exhaust Air Adjustment Screw fully clockwise. This will allow 2nd stage cooling to operate.

With power exhaust option, each building pressurization requirement will be different. The point at which the power exhaust comes on is determined by the econo- mizer damper position (Percent Open). The Exhaust Air Adjustment Screw should be set at the Percent Open of the economizer damper at which the power exhaust is needed. It can be set from 0 to 100% damper open.

INDOOR AIR QUALITY AQ

Indoor Air Quality (indoor sensor input): Terminal AQ accepts a +2 to +10 Vdc signal with respect to the (AQ1) terminal.

When the signal is below it's set point, the actuator is allowed to modulate normally in accordance with the enthalpy and mixed air sensor inputs. When the AQ signal exceeds it's set point setting and there is no call for free cooling, the actuator is proportionately modulated from the 2 to 10 Vdc signal, with 2 Vdc corresponding to full closed and 10 Vdc corresponding to full open. When there is no call for free cooling, the damper position is limited by the IAQ Max damper position setting. When the signal exceeds it's set point (Demand Control Ven- tilation Set Point) setting and there is a call for free cooling, the actuator modulates from the minimum position to the full open position based on the highest call from either the mixed air sensor input or the AQ voltage input.

Optional CO2 Space Sensor Kit Part # 2AQ04700324

Optional CO2 Sensor Kit Part # 2AQ04700424 Replace the top rear access panel on the unit.

FIGURE 20 - ENTHALPY SET POINT CHART

Unitary Products Group

21

Image 21
Contents Single Package Heat Pump High Efficiency Installation Manual 50 HzTable of Contents List of Figures List of Tables Safety Considerations GeneralInspection Reference Renewal PartsApprovals Nomenclature Ton York Model Number NomenclatureInstallation Installation Safety InformationPreceding Installation Location Unit Voltage LimitationsUnit Weights Point Load WeightRigging and Handling Clearances Unit ClearancesDetail B BttomPower Rear Duct Dimensions Ductwork Duct Covers Predator Roof Curb Dimensions Control Wire Sizes Thermostat WiringCompressors FiltersElectronic Thermostat Field Wiring Power Wiring DetailGroundlug Electrical Data 10 TON HP Electrical Data 7-1/2 TON HPElectric Heat Accessory Factory Installed Options Field Installed AccessoriesPhysical Data Electric Heat OptionElectric Heat Minimum Supply AIR Indoor AIR Quality AQ Enthalpy SET Point ChartBlower Rotation Supply AIR LimitationsBelt Tension Belt Adjustment Blower Performance 7-1/2 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct Metric Blower Performance 10 TON Standard Motor Side Duct ImperialBlower Performance 10 TON Optional Motor Side Duct Metric Blower Performance 10 TON Optional Motor Side Duct ImperialBlower Performance 7-1/2 TON Standard Motor Downshot Metric Blower Performance 7-1/2 TON Optional Motor Downshot Metric Blower Performance 10 TON Standard Motor Downshot ImperialBlower Performance 10 TON Standard Motor Downshot Metric Indoor Blower Specifications Blower Performance 10 TON Optional Motor Downshot ImperialBlower Performance 10 TON Optional Motor Downshot Metric Checking AIR Quantity AIR BalanceMethod ONE Method TWODRY Coil Delta P Supply AIR Drive AdjustmentAdditional Static Resistance Metric Additional Static Resistance ImperialCFM M3SMotor Sheave Datum OperationSequence of Operations Overview Cooling Sequence of OperationCooling Operation Errors Reset Safety ControlsCompressor Protection Heating Sequence of OperationSTART-UP Operating Instructions Post Start Check ListSuperheat Charging Method Cooling Superheat 7-1/2 TON Superheat ChargingTroubleshooting Cooling Superheat 10 TONPredator Flash Codes Unit Control Board Unit Control Board Flash CodesCooling Troubleshooting Guide Page Page Unitary 5005 Norman Products York Group Drive 73069