Lochinvar 999 - 750, CF-CH(E)-i&s-08, 399 Installation, Clearances from Combustible Construction

Page 6

Hydronic Heating Boilers and Domestic Water Heaters

INSTALLATION

This unit meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gas-fired units, ANSI Z21.13/CSA 4.9 and ANSI Z21.10.3/CSA 4.3.

LOCATING UNIT

1.Maintain all clearances from combustible construction when locating unit. See Clearances from Combustible Construction, this page.

2.Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, install a suitable drain pan that is well-drained under the unit. The pan must not restrict combustion air flow. The appliance manufacturer is not responsible for water damage in connection with this unit, or any of its components.

3.Install indoor units so that the ignition system components are protected from any water while operating or during service.

4.Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46 cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.

5.DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.

6.You must install unit on a level, non-combustible floor.

7.Do not install unit directly on carpet or other combustible material. A concrete-over-wood floor is not considered non-combustible. Maintain required clearances from combustible surfaces.

If installing unit in an area with a combustible floor, you must use a special combustible floor base. See Base for Combustible Floors, on page 7.

8.For outdoor models, you must install an optional vent cap. Instructions for mounting the vent cap are included in the venting section. Do not install outdoor models directly on the ground. You must install the outdoor unit on a concrete, brick, block, or other non-combustible pad. Outdoor models have additional special location and clearance requirements. See Outdoor Installation Venting, page 26. A wind proof cabinet protects the unit from weather.

Clearances from Combustible

Construction

Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the unit. See rating plate for specific service clearance requirements.

Right Side

3" (7.5 cm)

Rear

3" (7.5 cm) (3" min.

 

from any surface)

Left Side

6" (15cm) (24" (0.61m)

 

suggested for service)

Front

Alcove* (30" (0.76m)

 

suggested for service)

Top

3" (7.5cm)

Flue

1" (25.4mm)

Hot Water Pipes

1" (25.4mm)

*An Alcove is a closet without a door.

Note: No additional clearance is needed on the right side of the unit for the observation port. An observation port is located on both the right and left side of the unit.

No additional clearances for combustibles are needed for use of the Direct Vent (DV) air inlet assembly.

3 INCH MINIMUM FROM UNIT TO WALL

FIG. 2 Clearances from Combustible Construction

6

Image 6
Contents Domestic Water Heaters Hydronic Heating Boilers and Domestic Water Heaters General Product Information UnpackingSafety Information Installation Installation Clearances from Combustible ConstructionFreeze Protection Outdoor Boiler InstallationLocation Pump OperationCombustion and Ventilation AIR Shut-Down and DrainingFreeze Protection for a Heating Boiler System if required Combustion Air FilterCombustion Air Options Outside Combustion Air, No DuctsCombustion Air from Interior Space General Information VentingExhaust Fans Vertical Vent Termination Clearances and LocationSidewall Vent Termination Clearances and Location ChimneyCombustion Air Inlet Piping Length of Air Inlet PipeSidewall Air Inlet Vertical Rooftop Air Inlet ClearancesVent System Options Combined Air Inlet PointsBarometric Damper Location Conventional Negative Draft Venting Negative DraftFlue Outlet Piping Vertical DirectAire Venting Vertical Vent Termination Clearances and LocationInstallation Vent Kits Venting of Flue ProductsSidewall Venting Termination Sidewall VentingSidewall Fan Sidewall Venting Without FanVenting Guidelines Masonry Chimney Installation Horizontal DirectAire VentingVent Kits Direct VentingVertical DV Venting Termination Flue Pipe Materials Connecting the Air Inlet Pipe to the UnitHorizontal DV Venting Termination Combustion Air Inlet PipingAir Inlet Piping Materials Sealing PVC, CPVC, ABS, Dryer Vent, and Flex Duct Vent PipeOutdoor Installation Venting MaximumOutdoor Vent/Air Inlet Location Outdoor Vent Cap KitGas Piping Connecting to GAS SupplyConnecting Gas Piping to Unit Gas Pressure TestBtu/hr Distance From Meter in feet Gas Train and ControlsTABLE-J Input 51-100 101-200 201-300 301-500Combination Gas Valves Checking Gas Supply PressureVenting of Combination Gas Valves Gas Manifold Pressure Adjustment Multiple Unit Installations Gas Supply Pipe SizingTable L Connecting to Water Supply Water Flow Switch Relief ValveLow Water Cutoff General Plumbing Rules Water Connections Heating Boilers OnlyCirculator Pump Requirements Pump Installation and Maintenance Heat Exchanger Pressure Drop ChartCirculator Pump Specifications Primary/Secondary Boiler PipingLow Temperature Return Water Systems Table O LTV Valve KitsInput LTV Valve Kit Btu/hr Radiant Floor and Snow Melt Heating Systems 10ºF 20ºF 30ºF 40ºFPlacing the Boiler in Operation Temperature/Pressure GaugeBoiler Flow Rate Boiler Bypass RequirementsInstallation with a Chilled Water System Boiler Operating Temperature ControlWater Treatment Terminal Strip Connection OptionsFor Your Safety Read Before Operating Remote ON/OFF Boiler or Water HeaterOperation To Turn Off Gas To Appliance Power UpQuick Programming Overview Standard Btu/hr ModelsTABLE-Q Adjust Menu Setting DescriptionsAdjust Menu Settings for Operating Modes TABLE-RIgnition Systems and Stages Operating ModesProgramming Buttons Access Levels Temperature ControlPlacement of Sensors Graphic Symbols Programming For Mode 1, Boiler OperationStaging Logic Remote Mounting of Sensors Programming For Mode 2, Water Heating OperationProgramming For Mode 3, Sequenced Operation TABLE-SHot Surface Igniter and Ignition Control Module Error and Warning MessagesHOT Surface Ignition System Hot Surface Ignition Control ModuleIgnition Control Diagnostic Codes Diagnostic Status IndicationAccess to Internal Control Panel Removing the Control PanelIgnition and Control Timings Operation and Diagnostic LightsStatus LED Diagnostic Codes Hot Surface Ignition Module Timings NominalWater Velocity Control Required Temperature RiseTemperature Rise Chart Water ChemistryTABLE-X Pipe Size RequirementsCirculating Pump 399,999 750,000 Btu/hr ModelsHeat Exchanger Potable Hot Water Temperature Control SettingsMinimum Pump Performance TABLE-YThermal Expansion High Water Temperature Limit ControlOptional Relief Valve Location of Cold Water Supply Piping ConnectionsAppliance Area Flue Gas Passageways Cleaning ProceduresBurner Removal and Cleaning Water Circulating PumpHeat Exchanger Cleaning ElectricalCombustion and Ventilation Air Adjusting Differential Air Pressure Set Up ProcedureAdjustment Procedure Servicing Hot Surface Igniter and Ignition Module Ignition System CheckoutSequence of Operation Ignition Troubleshooting Guide 990,000 2,070,000 Btu/hr Models Domestic Water Heaters Hydronic Heating Boilers Ladder Diagram 399,999 750,000 BTU/HR Models Hydronic Heating Boilers and Domestic Water Heaters Installation Ladder Diagram 990,000 2,070,000 BTU/HR Models Models Wiring Diagram Hydronic Heating Boilers and Domestic Water Heaters BTU/HR Models
Related manuals
Manual 76 pages 58.86 Kb

399, CF-CH(E)-i&s-08, 999 - 750 specifications

Lochinvar 999 - 750, CF-CH(E)-i&s-08,399 is a cutting-edge boiler designed for commercial heating applications. With its robust construction and high efficiency, this model stands out in the crowded market of heating solutions.

One of the main features of the Lochinvar 999 - 750 is its exceptional thermal efficiency rating. The unit incorporates advanced condensing technology that allows it to recover heat from flue gases, which helps in achieving efficiency levels of up to 99%. This efficiency not only reduces energy consumption but also lowers operational costs, making it an excellent investment for businesses looking to minimize their carbon footprint.

The boiler is designed to provide a powerful output of 750 kW, ensuring it meets the heating demands of larger buildings or commercial spaces. Its capacity makes it suitable for a range of applications including schools, hospitals, and industrial facilities. Moreover, the unit features a built-in cascading system that enables multiple boilers to be connected, enhancing system reliability and flexibility.

In terms of technology, the Lochinvar 999 - 750 is equipped with a user-friendly touchscreen interface. This innovative control system allows operators to monitor and adjust settings with ease, providing real-time performance data and alerts for maintenance needs. The intelligent controls optimize operation to match the heating load, further enhancing energy efficiency.

Safety is a top priority with this model. It is built with multiple safety features such as automatic shut-off valves, pressure relief valves, and flame monitoring systems, ensuring safe operation under various conditions. The unit also adheres to stringent industry standards and regulations, making it a reliable choice for commercial applications.

Furthermore, the Lochinvar 999 - 750 is designed with serviceability in mind. Its compact footprint and accessible components simplify maintenance, reducing downtime and associated costs. The unit also supports a variety of fuel sources, including natural gas, propane, and biodiesel, providing flexibility to meet different facility requirements.

In summary, the Lochinvar 999 - 750, CF-CH(E)-i&s-08,399 represents a blend of efficiency, reliability, and safety in commercial heating. Its advanced technologies and thoughtful design make it a powerful solution for various heating needs, making it an ideal choice for businesses aiming for excellence in energy management and operational efficiency.