Lochinvar 402 - 2072 Conventional negative draft venting see, Negative draft, Flue outlet piping

Page 16

Installation & Operation Manual

2 Venting

A

Conventional negative draft venting - see page 14.

NOTICE

Before installing a venting system, follow requirements found in the General Venting section.

 

This option uses Type-B double-wall flue outlet piping. The blower brings in combustion air. The buoyancy of the heated flue products cause them to rise up through the flue pipe. The flue outlet terminates at the rooftop.

Negative draft

The negative draft in a conventional vent installation must be within the range of 0.02 to 0.08 inches w.c. to ensure proper operation. Make all draft readings while the unit is in stable operation (approximately 2 to 5 minutes).

Connect the flue vent directly to the flue outlet opening on the top of the unit. No additional draft diverter or barometric damper is needed on single unit installations with a dedicated stack and a negative draft within the specified range of 0.02 to 0.08 inches w.c. If the draft in a dedicated stack for a single unit installation exceeds the maximum specified draft, you must install a barometric damper to control draft. Multiple unit installations with combined venting or common venting with other Category I negative draft appliances require each boiler to have a barometric damper installed to regulate draft within the proper range.

Do not connect vent connectors serving appliances vented by natural draft (negative draft) to any portion of a mechanical draft system operating under positive pressure. Connecting to a positive pressure stack may cause flue products to be discharged into the living space causing serious health injury.

Flue outlet piping

With this venting option, you must use Type-B double-wall vent materials. Vent materials must be listed by a nationally-recognized test agency for use as vent materials. Make the connections from the unit vent to the outside stack as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for double- wall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.

Provide adequate clearance to combustibles for the vent connector and firestop.

When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings, and floors. Locate the unit as close as possible to a chimney or gas vent.

Avoid long horizontal runs of the vent pipe, 90° elbows, reductions and restrictions.

No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.02 to 0.08 inches w.c.

Common Venting Systems

You can combine the flue with the vent from any other negative draft, Category I appliance. Using common venting for multiple negative draft appliances requires you to install a barometric damper with each unit. This will regulate draft within the proper range. You must size the common vent and connectors from multiple units per the venting tables for Type-B double-wall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1 and/or CAN/ CGA-B149 Installation Code.

Common venting systems may be too large when an existing unit is removed.

At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting system are not in operation.

1.Seal any unused opening in the common venting system.

2.Visually inspect the venting system for proper size and horizontal pitch. Make sure there is no blockage or restriction, leakage, corrosion and other unsafe conditions.

3.If possible, close all building doors and windows. Close all doors between the space in which the appliances remaining connected to the common venting system are located and other building spaces.

16

Image 16
Contents Models 402 Save this manual for future referenceContents Special instructions Please read before proceedingRemoval of Combustion Chamber Lining or Base Panels Safety information Owner warningCopper-fin II How it works Copper-fin II How it works Copper-fin II How it works Ratings Copper-fin =B=R RatingDetermine unit location Location of unitIndoor clearances from combustible construction Freeze protectionOutdoor boiler installation LocationHydronic systems anti-freeze Combustion and ventilation airOutside Combustion Air Using Direct Venting Minimum Recommended Combustion AIR Supply to Equipment RoomExhaust fans Combustion air filterVenting Identify your appliance’s vent systemCAT IV Flue pipe materials CAT I Negative pressure non-condensingDirect Vent see Venting support General informationBarometric damper location Conventional negative draft venting see Negative draftFlue outlet piping Common Venting SystemsVertical vent termination clearances and location Masonry chimney installationsInspection of a masonry chimney 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Vertical DirectAire venting see Combustion air inlet pipingLength of air inlet pipe Sidewall air inletCombined air inlet points Vertical Rooftop Air InletClearances Venting of flue products Directaire Kits Model Horizontal KIT Vertical KITSidewall venting see Sidewall with fanSidewall venting termination Sidewall vent termination clearances and locationDrain tee installation Sidewall venting without fanModels 402 Horizontal DirectAire venting Powered Venting see Venting of flue productsFlue outlet piping Direct venting seeVertical DV venting termination Masonry chimney installation Horizontal DV venting terminationHorizontal Vent Termination Clearances and Location Combustion air inlet pipingConnecting the air inlet pipe to the unit Air inlet piping materialsLength of air inlet pipe Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeMultiple sidewall direct vent installations Vertical and sidewall combustion air inletHorizontal combustion air inlet clearances Vertical Combustion Air Inlet ClearancesOutdoor vent/air inlet location Outdoor installation seeOutdoor vent cap kit Connecting to gas supply Gas connectionsGas pressure test Gas connectionGas train and controls Combination gas valvesVenting of combination gas valves GAS Piping Size Chart Checking gas supply pressureWater flow switch Water connectionsInlet and outlet connections Heat exchangerHeating boiler installations Relief valvePiping of the boiler system Water connections heating boilers onlyMinimum boiler water temperatures Low Temperature Return Water SystemsLow temperature bypass requirements LTV Valve Kits Model LTV Valve KITLow system water volume Three way valves in systemRadiant floor and snow melt heating systems Maximum Flow for Heating BoilerTemperature / pressure gauge Typical heating boiler installationsInstallation with a chilled water system DHW installationGPM Diameter4Primary/Secondary Piping of Multiple Boilers Floor Drain Heating Supply Loop 6Primary/Secondary Piping with Buffer Tank Installation must comply with Electrical connectionsBoiler operating control module AMP Draw DataLine voltage connections EMS or remote thermostat connectionLow voltage connections DHW Domestic Hot Water thermostatLouver proving switch Alarm contactsLouver relay System supply sensor recommended useWiring of the cascade 4Low Voltage Field Wiring ConnectionsStart-up Check thermostat circuits Check vent and air pipingPlacing the boiler in operation Start the boiler1Lighting Instructions Set DHW operation Configuration of the cascadeSet clock Operating information GeneralHow the appliance operates How the control module operatesTemperature control Protection featuresOutdoor reset operation, if used boilers only Boiler temperature regulationCascade DAY Switching on Sequence DHW, Night Setback, and Ramp Delay operation with cascadeSequence of the cascade Sequence of operation Operation DisplayMENU/EXIT Display Screen ENTER/RESET Updown Copper-fin II control moduleAccess modes InstallerUser To save parameters and exit programmingStatus display screens Inlet ***F Inlet OpenInlet Shorted Syssup ***FUnit Pump Delay DHW Pump DelaySTG Demand FAN SpeedOperation of the cascade MIX VAL POS ** %Temperature Rise AT Full Rate Fire 90 GPM Flow Model Temperature Rise FDomestic water heaters Maximum Water FlowWater chemistry 1Typical Water Heater Piping with Storage Tank 2Single Water Heater Piping with Two Storage Tanks 3Multiple Water Heater Piping with a Single Storage Tank 4Multiple Water Heater Piping with Multiple Storage Tanks Pump operation Heat exchangerMinimum Pump Performance Ft. HdMinimum water temperatures domestic hot water use Thermostat adjustment procedureDomestic water temperatures Optional relief valve Thermal expansionCathodic protection Location of Cold Water Supply Piping ConnectionsService technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check all wiring Check control settingsCheck relief valve Inspect/replace hot surface igniter Ignition system checkoutInspect and clean burner Perform start-up and checksCheck burner flame Check flue gas passagewaysReview with owner Inspect and clean the heat exchangerOiled bearing circulators Connection diagram Digital HarnessSplay Diagram LadderFlow Switch
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 44 pages 8.33 Kb

402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.