Lochinvar 402 - 2072 operation manual Start-up

Page 47
￿ CAUTION

6 Start-up

Check/control water chemistry

Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and gaskets in the system could occur, resulting in substantial property damage.

Hardness less than 7 grains

1.Consult local water treatment companies for hard water areas (above 7 grains hardness).

Chlorine concentration less than 200 ppm

1.Do not fill boiler or operate with water containing chlorine in excess of 200 ppm.

2.Filling with chlorinated fresh water should be acceptable since drinking water chlorine levels are much lower.

3.Do not use the boiler to directly heat swimming pool or spa water.

Test/replace freeze protection fluid

1.For systems using freeze protection fluids, follow fluid manufacturer’s instructions.

2.Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time. Follow all fluid manufacturer’s instructions.

Freeze protection (when used)

1.Determine freeze protection fluid quantity using system water content, following fluid manufacturer’s instructions. Appliance water content is listed on page 8. Remember to include expansion tank water content.

2.Local codes may require a backflow preventer or actual disconnect from city water supply.

3.When using freeze protection fluid with automatic fill, install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing concentration to drop, reducing the freeze protection level.

Fill and test water system

1.

Fill system only after ensuring the water meets the

 

requirements of this manual.

2.

Close manual and automatic air vents and boiler drain

 

valve.

3. Fill to correct system pressure. Correct pressure will

 

vary with each application.

 

a. The minimum cold water fill pressure should be

 

12 PSI.

Installation & Operation Manual

￿WARNING Eliminate all system leaks. Continual fresh makeup water will reduce boiler life.

Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.

Purge air from water system

1.Purge air from system:

a.Connect a hose to the purge valve (see purge/drain valves, in the piping diagrams on pages 39 - 42). Route the hose to an area where water can drain and be seen.

b.Close the boiler or system isolation valve between the purge valve and fill connection to the system.

c.Close zone isolation valves.

d.Open quick-fill valve on cold water makeup line.

e.Open purge valve.

f.One zone at a time, open the isolation valves. Allow water to run through the zone, pushing out the air. Run until no noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all zones are purged.

g.Close the quick-fill water valve and purge valve and remove the hose. Open all isolation valves. Watch that system pressure rises to correct cold-fill pressure.

h.After the system has operated for a while, eliminate any residual air by using the manual air vents located throughout the system.

i.If purge valves are not installed in the system, open the manual air vents in the system one at a time, beginning with the lowest floor. Close the vent when water squirts out. Repeat with remaining vents.

2.Open automatic air vent (diaphragm-type or bladder-type expansion tank systems only) one turn.

3.Open other vents:

a.Starting on the lowest floor, open air vents one at a time until water squirts out.

b.Repeat with remaining vents.

4.Refill to correct pressure.

Check for gas leaks

￿WARNING Before starting the boiler, and during initial operation, smell near the floor and around

the boiler for gas odorant or any unusual odor. Remove the front access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.

b. Pressure will rise when boiler is turned on and

system water temperature increases.

4. At initial fill and during boiler startup and testing,

check system thoroughly for any leaks. Repair all leaks

before proceeding further.

￿WARNING

Propane boilers only – Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.

47

Image 47
Contents Save this manual for future reference Models 402Contents Removal of Combustion Chamber Lining or Base Panels Please read before proceedingSpecial instructions Owner warning Safety informationCopper-fin II How it works Copper-fin II How it works Copper-fin II How it works Copper-fin =B=R Rating RatingsFreeze protection Determine unit locationLocation of unit Indoor clearances from combustible constructionCombustion and ventilation air Outdoor boiler installationLocation Hydronic systems anti-freezeMinimum Recommended Combustion AIR Supply to Equipment Room Outside Combustion Air Using Direct VentingCombustion air filter Exhaust fansCAT I Negative pressure non-condensing VentingIdentify your appliance’s vent system CAT IV Flue pipe materialsDirect Vent see Barometric damper location General informationVenting support Common Venting Systems Conventional negative draft venting seeNegative draft Flue outlet pipingInspection of a masonry chimney Masonry chimney installationsVertical vent termination clearances and location 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Sidewall air inlet Vertical DirectAire venting seeCombustion air inlet piping Length of air inlet pipeClearances Vertical Rooftop Air InletCombined air inlet points Directaire Kits Model Horizontal KIT Vertical KIT Venting of flue productsSidewall vent termination clearances and location Sidewall venting seeSidewall with fan Sidewall venting terminationSidewall venting without fan Drain tee installationModels 402 Venting of flue products Horizontal DirectAire venting Powered Venting seeVertical DV venting termination Direct venting seeFlue outlet piping Combustion air inlet piping Masonry chimney installationHorizontal DV venting termination Horizontal Vent Termination Clearances and LocationSealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipe Connecting the air inlet pipe to the unitAir inlet piping materials Length of air inlet pipeVertical Combustion Air Inlet Clearances Multiple sidewall direct vent installationsVertical and sidewall combustion air inlet Horizontal combustion air inlet clearancesOutdoor vent cap kit Outdoor installation seeOutdoor vent/air inlet location Gas connection Connecting to gas supplyGas connections Gas pressure testVenting of combination gas valves Combination gas valvesGas train and controls Checking gas supply pressure GAS Piping Size ChartHeat exchanger Water flow switchWater connections Inlet and outlet connectionsWater connections heating boilers only Heating boiler installationsRelief valve Piping of the boiler systemLTV Valve Kits Model LTV Valve KIT Minimum boiler water temperaturesLow Temperature Return Water Systems Low temperature bypass requirementsMaximum Flow for Heating Boiler Low system water volumeThree way valves in system Radiant floor and snow melt heating systemsDHW installation Temperature / pressure gaugeTypical heating boiler installations Installation with a chilled water systemDiameter GPM4Primary/Secondary Piping of Multiple Boilers Floor Drain Heating Supply Loop 6Primary/Secondary Piping with Buffer Tank AMP Draw Data Installation must comply withElectrical connections Boiler operating control moduleDHW Domestic Hot Water thermostat Line voltage connectionsEMS or remote thermostat connection Low voltage connectionsSystem supply sensor recommended use Louver proving switchAlarm contacts Louver relay4Low Voltage Field Wiring Connections Wiring of the cascadeStart-up Start the boiler Check thermostat circuitsCheck vent and air piping Placing the boiler in operation1Lighting Instructions Set clock Configuration of the cascadeSet DHW operation How the control module operates Operating informationGeneral How the appliance operatesProtection features Temperature controlCascade Boiler temperature regulationOutdoor reset operation, if used boilers only Sequence of the cascade DHW, Night Setback, and Ramp Delay operation with cascadeDAY Switching on Sequence Operation Display Sequence of operationCopper-fin II control module MENU/EXIT Display Screen ENTER/RESET UpdownTo save parameters and exit programming Access modesInstaller UserStatus display screens Syssup ***F Inlet ***FInlet Open Inlet ShortedFAN Speed Unit Pump DelayDHW Pump Delay STG DemandMIX VAL POS ** % Operation of the cascadeMaximum Water Flow Temperature Rise AT Full Rate Fire 90 GPM FlowModel Temperature Rise F Domestic water heatersWater chemistry 1Typical Water Heater Piping with Storage Tank 2Single Water Heater Piping with Two Storage Tanks 3Multiple Water Heater Piping with a Single Storage Tank 4Multiple Water Heater Piping with Multiple Storage Tanks Ft. Hd Pump operationHeat exchanger Minimum Pump PerformanceDomestic water temperatures Thermostat adjustment procedureMinimum water temperatures domestic hot water use Location of Cold Water Supply Piping Connections Optional relief valveThermal expansion Cathodic protectionOwner maintenance Maintenance Maintenance and annual startupService technician Maintenance Ignition system checkout Check all wiringCheck control settings Check relief valve Inspect/replace hot surface igniterCheck flue gas passageways Inspect and clean burnerPerform start-up and checks Check burner flameOiled bearing circulators Inspect and clean the heat exchangerReview with owner Digital Harness Connection diagramSplay Ladder DiagramFlow Switch
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 44 pages 8.33 Kb

402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.